You are on page 1of 3

PROJECT

PLOT NO
CLIENT
DATE PREPARED BY ENG. MANOJ

LOBBY SMOKE EXTRACT CALCULATION

Lobby Area 48.42 Sqm


Height 3.1 Meter
ACH 10

Lobby Smoke Extract System


= Area x Height x ACH / 60

= 416.95 L/s

Total Supply for one Floor = 500 L/s

Fan Capacity = 500 L/s

LOBBY MAKE UP DUCT


Design Concept
Lobby Make up air shall be provided (50% Make Air to above Fire Floor
and 50% Make Up Air to Below Fire Floor )

Total Supply for one Floor (50%


= 250 L/s
of Extract Air Flow )
Fan Capacity = 500 L/s