You are on page 1of 21

Release Date: Jan. 2010 / Manual Revision: 5.

00

APPENDIX

ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright © 2002 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
APPENDIX http://www.entecene.co.kr

TABLE OF CONTENTS

Appendix A. OPTO INPUT FUNCTION ………………………………………………………...1

Appendix B. RELAY OUTPUT FUNCTION ……………………………………………………2

Appendix C. SYSTEM STATUS ………………………………………………………………….3

Appendix D. DIAGNOSTIC EVENT …………………………………………………………….5

Appendix E. MENU MESSAGE & HELP MESSAGE DESCRIPTION ..……...……………..6

Appendix F. Ordering Guide …………………….………………………..................................18

ENHANCED TECHNOLOGY i
APPENDIX http://www.entecene.co.kr

APPENDIX A. OPTO INPUT FUNCTION

Table A-1. OPTO INPUT FUNCTION


Function Explanation
NONE Not in use
TRIP Use for Trip(open) Order
CLOSE Use for Close Order
PROTEC E/D Use for PROTECTION Enable/Disable function
GND E/D Use for GROUND Enable/Disable function
SEF E/D Use for SEF Enable/Disable function
REC E/D Use for RECLOSE Enable/Disable function
C LOCK E/D Use for CONTROL Locked/Unlocked function
Use to change the setting value of ALTERNATE SETTINGS Enable/Disable
ALT E/D
to Primary/Alternate
PG1 E/D Use for PROGRAM1 Enable/Disable function
PG2 E/D Use for PROGRAM2 Enable/Disable function
HLT E/D Use for HOT LINE TAG Enable/Disable function
FI RESET Use for FAULT INDICATION Reset function
BATT LT Use for BATTERY LOAD TEST function
OUT1~8 RESET Use for OUTPUT RELAY 1~8 RESET function

ENHANCED TECHNOLOGY 1
APPENDIX http://www.entecene.co.kr

Appendix B. RELAY OUTPUT FUNCTION

Table B-1. RELAY OUTPUT FUNCTION


Function Explanation
NONE Not in use
TRIP Use for External Output when TRIP order occurs
CLOSE Use for External Output when CLOSE order occurs
FAIL TRIP Use for External Output when TRIP fails
FAIL CLOSE Use for External Output when CLOSE fails
FAIL AC Use for External Output when AC lost
FAIL BATT Use for External Output when Battery discharges
27 Use for External Output when 27 Element appears
59 Use for External Output when 59 Element appears
25 Use for External Output when 25 Element appears
81 Use for External Output when 81 Element appears
79 RS Use for External Output when 79 Element appears
79 CY Use for External Output when 79 Cycle appears
79 LO Use for External Output when 79 Lockout appears
SELFCHECK Use for External Output when Self check appears
PRO ENABLE Use for External Output when Protection Enable
GND ENABLE Use for External Output when Ground Enable
SEF ENABLE Use for External Output when SEF Enable
RECL ENABLE Use for External Output when RECLOSE Enable
CONTR LOCK Use for External Output when Control locked
REM ENABLE Use for External Output when Remote Enable
ALT ENABLE Use for External Output when Alternate Settings Enable
PG1 ENABLE Use for External Output when Program1 Enable
PG2 ENABLE Use for External Output when Program2 Enable
HLT ENABLE Use for External Output when HOT LINE TAG Enable
FAULT INDI Use for External Output when Fault indicator appears
ALARM Use for External Output when Alarm
52A Use for External Output when 52A on (close status)
INPUT01~08 Use for External Output when Input01~08 input appears

2 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Appendix C. SYSTEM STATUS

Table C-1. SYSTEM STATUS (1/2)


Element LCD Text Explanation
PHASE F Phase fast protection element
PHASE D Phase delay protection element
GROUND F Ground fast protection element
GROUND D Ground delay protection element
NEG SEQ F Negative Sequence fast protection element
NEG SEQ D Negative Sequence fast protection element
P HIGH LO Phase High Current lockout protection element
G HIGH LO Ground High Current lockout protection element
N HIGH LO Neutral High Current lockout protection element
NEG HIGH LO Negative Sequence High Current lockout protection element
P HIGH TR Phase High Current Trip protection element
PROTECTION G HIGH TR Ground High Current Trip protection element
N HIGH TR Neutral High Current Trip protection element
NEG HIGH TR Negative Sequence High Current Trip protection element
SEF TR Sensitive Earth Fault protection element
P-DEMT TR Phase demand Trip element
G DEMT TR Phase demand Trip element
FREQ TR Frequency Protection element
UNDER1VOLT Under-voltage 1 protection element
UNDER2VOLT Under-voltage 2 protection element
OVER1 VOLT Over-voltage 1 protection element
OVER2 VOLT Over-voltage 2 protection element
SYNCH CHK Syncro Check
52A CONTACT 52A 52A contact status
79 RESET Sequence reset status
SEQUENCE STATUS 79 CYCLE Sequence cycle status
79LOCKOUT Sequence lockout status
LOCAL CL Front Panel CLOSE pushbutton
FRONT PANEL CONTROL
LOCAL OP Front Panel OPEN pushbutton

ENHANCED TECHNOLOGY 3
APPENDIX http://www.entecene.co.kr

Table C-1. SYSTEM STATUS (2/2)


Element LCD Text Explanation
LOCAL FI/R Front Panel FI RESET pushbutton
LOCAL BT Front Panel BATTERY LOAD TEST pushbutton
PROT EN Front Panel PROTECTION ENABLED pushbutton
GND EN Front Panel GROUND ENABLED pushbutton
SEF EN Front Panel SEF ENABLED pushbutton
RECLOSE EN Front Panel SEF ENABLED pushbutton
FRONT PANEL CONTROL
CONTR LOCK Front Panel SEF ENABLED pushbutton
REMOTE EN Front Panel SEF ENABLED pushbutton
ALT EN Front Panel SEF ENABLED pushbutton
PROG1 EN Front Panel SEF ENABLED pushbutton
PROG2 EN Front Panel SEF ENABLED pushbutton
HOTLINE EN Front Panel SEF ENABLED pushbutton
AC SUPPLY AC POWER AC supply status
EXT OPEN External OPEN element
EXTERNAL CONTROL
EXT CLOSE External CLOSE element
CB LOCK Circuit Breaker (Recloser) LOCK
FAIL OPERATION FAIL TRIP FAIL TRIP
FAIL CLOSE FAIL CLOSE
EXTERNAL INPUT STATUS EXT IN01-08 External INPUT01-08 Active
SYSTEM ALARM SYS ALARM System Alarm Active
TRIP-SIG Trip Signal
TRIP/CLOSE
CLOSE-SIG Close Signal

4 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Appendix D. DIAGNOSTIC EVENT

Table D-1. DIAGNOSTIC EVENT


Element LCD TEXT Explanation
AC FAIL External power FAIL
CHGBD FAIL Battery charge circuit FAIL
BATT DISCHG Battery Discharge (Value < 21V)
NO BATTERY NO Battery (Value < 15V)
SYSTEM POWER BATT FAIL Battery Discharge or No Battery
SYSPOW FAIL System power FAIL
+12V FAIL System power +12V FAIL
+5 V FAIL System power +5V FAIL
-12V FAIL System power -12V FAIL
SLEEP MODE SLEEP MODE Panel sleep mode
POWER DOWN MODE POWER DOWN Power down mode
GAS LOW Gas pressure Low (Value < 0.1 Bar)
GAS STATUS
GAS HIGH Gas pressure High (Value > 1.5 Bar)
AD BUSY A/D conversion FAIL
A/D CONVERSION REF1V FAIL A/D converter reference voltage 1 FAIL
REF2V FAIL A/D converter reference voltage 2 FAIL
SETTING SET CHANGE Setting Changed
SYSTEM RESTART RESTART System restarted
P-ROM FAIL Parallel EEPROM FAIL
S-ROM FAIL Serial EEPROM FAIL
D-RAM FAIL Data RAM FAIL
S-RAM FAIL Setting RAM FAIL
MEMORY R-RAM FAIL RTC NV RAM FAIL
RTC FAIL RTC Time FAIL
RTC BAT LO RTC Battery LOW
I-VAL FAIL Initial Value FAIL
I-SET FAIL Initial Setting Value FAIL
C-BD FAIL Commuicaton Option Board FAIL
COMMUNICATION
COLD RST Cold Restarted

ENHANCED TECHNOLOGY 5
APPENDIX http://www.entecene.co.kr

Appendix E. MENU MESSAGE & HELP MESSAGE DESCRIPTION

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (1/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT

SELECT SETBANK
Primary Select BANK for Primary Setting (BANK1-BANK6) BANK1
Alternate Select BANK for Alternate Setting (BANK1-BANK6) BANK2
Edit Select BANK for EditBank Setting (BANK1-BANK6) BANK3

PRIMARY / ALTERNATE / EDITBANK SETTING

1.RELAY SETUP
1.PASSCODE : Passcode Change Setup
2.COMMUNICATION
1. REMOTE METHOD
Select Remote protocol (DNP3.0,MODBUS,IEC101,IEC104) DNP3.0
2. COMM SETTING (DNP3.0)
D/L Confirm Enable data link layer confirm (NO,YES,SOMETIMES) SOME
D/L Retries Data link layer retries (0-2) 1 2
D/L Timeout Data link layer time-out (1-255 sec) 1 55
A/L Retries Application layer retries (0-2) 1 1
A/L Timeout Application layer time-out (1-255 sec) 1 55
PowUp Unsol Enable unsolicited reporting at power-up (DISABLE,ENABLE) ENABLE
Unsol time Age of oldest event to transmit on (0-255 sec) 1 5
Master Addr Master station address (0-65535) 1 65534
SBO Time Select before operate time-out (1-255 sec) 1 15
DNP Address DNP address (0-65535) 1 1
Multi Inter Transmission interval at multiframe (0.01-300.00 sec) 0.01 0.10
Tx Delay Transmission time delay (0.00(OFF), 0.01-300.00 sec) 0.01 0.05
Class 1 Enable unsolicited class 1 (DISABLE,ENABLE) DISABLE
Class 2 Enable unsolicited class 2 (DISABLE,ENABLE) DISABLE
Class 3 Enable unsolicited class 3 (DISABLE,ENABLE) DISABLE
Time Req(m) Time Synch’ Request Interval (OFF,1-30000 minute) 1 OFF
Use Port Use port of control (P2-232,P3-485,P4-TCP) P2-232
2. COMM SETTING (MODBUS)
Modbus Type Modbus protocol type ( RTU,ASCII) RTU
Slave Address Modbus address (1-254) 1 1
Tx Delay Transmission time delay(OFF, 0.01-300.00 sec) 0.01 0.05

6 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (2/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
2. COMM SETTING (IEC60870-5-101/104)
ASDU Addr Application service data unit address (0~65535) 1 0
Cyclic Period Cyclic period (1~60000 sec) 1 60
Time Out(t0) Timeout for connection establishment (1~255 sec) 1 120
Time Out(t1) Timeout for send or test APDUs (1~255 sec) 1 15
Time Out(t2) Timeout for ack in case of no data message (1~255 sec) 1 10
Time Out(t3) Timeout for sending test frame in case of a long idle state (1~255 sec) 1 20
Event Period Event period (0~255sec) 1 5
Use Port--101 IEC101 Use port of control (P2-232,P3-485) P2-232
2. COMM SETTING (ETIMS DNP3.0)
Function Enable ETIMS DNP3.0 (DISABLE,ENABLE) DISABLE
D/L Timeout Data link layer time-out (1-255 sec) 1 5
A/L Timeout Application layer time-out (1-255 sec) 1 15
Master Addr Master station address (0-65535) 1 65534
DNP Address DNP address (0-65535) 1 1000
3. DIALLING MODEM(Calling String)
Calling String AT command for dial (ATD, ATDT, ATDP) ATD
3. DIALLING MODEM(Calling Number)
Calling Number Modem(Master station) phone number
3. DIALLING MODEM(Initial String)
Initial String Initial commands for your modem AT+FCLASS=0
4. PORT SETTING(RS232)
Line Speed Baud rate for RS232 port (1200,2400,4800,9600,19200 bps) 19200
Line Type Type of communication wire (2-wire,4-wire) 4-wire
RTS Off Dly RTS off Time delay (0.01-300.00 sec) 0.01 0.05
CTS Chk Out CTS check-out time (0.01-300.00 sec) 0.01 5.00
DCD Timeout DCD check-out time (0.01-300.00 sec) 0.01 5.00
RTS Function Select whether to use RTS signal or not (OFF, ON, AUTO) AUTO
CTS Function Select whether to use CTS signal or not. (OFF, ON) ON
DCD Function Select whether to use DCD signal or not. (OFF, ON) OFF
4. PORT SETTING(RS485/422)
Line Speed Baud rate for RS485/422 port (1200,2400,4800,9600,19200 bps) 1200
Line Type Port line type (485line, 422 line) 485LINE
Parity Chk Parity Check Select (NONE,ODD,EVEN) NONE
Data Bit Data Bit Select (7,8) 8
Stop Bit Stop Bit Select (1,2) 1
4. PORT SETTING(ETHERNET)
IP Addr’ 1 IP address 1 (0~255) 1 0
IP Addr’ 2 IP address 2 (0~255) 1 0

ENHANCED TECHNOLOGY 7
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (3/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
IP Addr’ 3 IP address 3 (0~255) 1 0
IP Addr’ 4 IP address 4 (0~255) 1 0
Gateway Addr’ 1 Gateway address 1 (0~255) 1 0
Gateway Addr’ 2 Gateway address 2 (0~255) 1 0
Gateway Addr’ 3 Gateway address 3 (0~255) 1 0
Gateway Addr’ 4 Gateway address 4 (0~255) 1 0
S/M Subnet mask (255.000.000.000~255.255.255.252) 255.255.255.000
Tcp Port(DNP) Tcp port number for DNP3.0 communication(1~65535) 1 20000
Tcp Port(104) Tcp port number for IEC60870-5-104 communication(1~65535) 1 2404
Tcp Port(IMS) Tcp port number for ETIMS communication(1~65535) 1 22000
3.CLOCK : Present Time Change Setup
4.TIME DISP’TYPE
Time Disp’Type Time Display Type (YMD, MDY) YMD
5.EVENT RECORDER
Fault Cycle Fault cycle event record (OFF,ON) ON
Len’ of Pre F Length of prefault in fault cycle (0-14 cycle) 1 4
Load Profile Load profile event record (OFF,ON) ON
L.P save time(m) Load profile event recording interval(5,10,15,20,30,60 min) 15
6.CLEAR SAVED DATA : Stored Value Clear
7.FATORY DEBUG : Fatory Debug Setup
8.Gas Sensor Type
Type Select Gas sensor type (NONE, TYPE1, TYPE2) TYPE2

2.SYSTEM SETUP
1.CURRENT SENSING
PHA CT Ratio Phase current transformer ratio (1-1200:1) 1 1000
GND CT Ratio Ground current transformer ratio (1-1200:1) 1 1000
SEF CT Ratio SEF current transformer ratio (1-1200:1) 1 1000
2.LINE VS SENSING
Connect Type Line VT connect type (NONE, WYE, DELTA, CVD-W, CVD-D) CVD-W
nd
VT 2 (v) Line VT secondary nominal volt (50.0-250.0 V) 0.1 100.0
VT Ratio Line VT Ratio (10.0-760.0:1) 0.1 86.6
3.LINE VL SENSING
Connect Type Line VT connect type (NONE, WYE, DELTA, CVD-W, CVD-D) CVD-W
nd
VT 2 (v) Line VT secondary nominal volt (50.0-250.0 V) 0.1 100.0
VT Ratio Line VT Ratio (10.0-760.0:1) 0.1 86.6
4.SYSTEM POWER
Frequency Power line nominal frequency (50,60 Hz) 50
Phase Rotation Power line phase rotation (ABC,ACB) ABC

8 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (4/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
5.PANEL SLEEP TIME
Interval(m) Display panel sleep time (0(OFF),1-100 min) 1 5
6.OPTO INPUT SET
I1 Func Opto input 1 function (NONE,TRIP,..,OUT8 RESET) NONE

OPTO INPUT FUNCTION


NONE TRIP CLOSE PROTEC E/D GND E/D SEF E/D
REC E/D C LOCK E/D ALT E/D PG1 E/D PG2 E/D HLT E/D
FI RESET BATT LT OUT1 RESET OUT2 RESET OUT3 RESET OUT4 RESET
OUT5 RESET OUT6 RESET OUT7 RESET OUT8 RESET

I1 Debounce Opto input 1 debounce time (0.01-9.99 sec) 0.01 0.02


I2 Func Opto input 2 function (NONE,TRIP,..,OUT8 RESET) NONE
I2 Debounce Opto input 2 debounce time (0.01-9.99 sec) 0.01 0.02
I3 Func Opto input 3 function (NONE,TRIP,..,OUT8 RESET) NONE
I3 Debounce Opto input 3 debounce time (0.01-9.99 sec) 0.01 0.02
I4 Func Opto input 4 function (NONE,TRIP,..,OUT8 RESET) NONE
I4 Debounce Opto input 4 debounce time (0.01-9.99 sec) 0.01 0.02
I5 Func Opto input 5 function (NONE,TRIP,..,OUT8 RESET) NONE
I5 Debounce Opto input 5 debounce time (0.01-9.99 sec) 0.01 0.02
I6 Func Opto input 6 function (NONE,TRIP,..,OUT8 RESET) NONE
I6 Debounce Opto input 6 debounce time (0.01-9.99 sec) 0.01 0.02
I7 Func Opto input 7 function (NONE,TRIP,..,OUT8 RESET) NONE
I7 Debounce Opto input 7 debounce time (0.01-9.99 sec) 0.01 0.02
I8 Func Opto input 8 function (NONE,TRIP,..,OUT8 RESET) NONE
I8 Debounce Opto input 8 debounce time (0.01-9.99 sec) 0.01 0.02
7.OUTPUT RELAY SET
O1 Func Output relay 1 function (NONE,..,INPUT08) NONE

OUTPUT RELAY FUNCTION


NONE TRIP CLOSE FAIL TRIP FAIL CLOSE FAIL AC
FAIL BATT 27 59 25 81 79RS
79CY 79LO SELFCHECK PRO ENABLE GND ENABLE SEF ENABLE
REC ENABLE CONTR LOCK REM ENABLE ALT BNABLE PG1 ENABLE PG2 ENABLE
HLT ENABLE FAULT INDI ALARM 52A INPUT01 INPUT02
INPUT03 INPUT04 INPUT05 INPUT06 INPUT07 INPUT08

O1 Type Output relay 1 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O1 Pulse T Output relay 1 pulse output time (0.01-99.99 sec) 0.01 0.05
O2 Func Output relay 2 function (NONE,..,INPUT08) NONE
O2 Type Output relay 2 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH

ENHANCED TECHNOLOGY 9
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (5/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
O2 Pulse T Output relay 2 pulse output time (0.01-99.99 sec) 0.01 0.05
O3 Func Output relay 3 function (NONE,..,INPUT08) NONE
O3 Type Output relay 3 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O3 Pulse T Output relay 3 pulse output time (0.01-99.99 sec) 0.01 0.05
O4 Func Output relay 4 function (NONE,..,INPUT08) NONE
O4 Type Output relay 4 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O4 Pulse T Output relay 4 pulse output time (0.01-99.99 sec) 0.01 0.05
O5 Func Output relay 5 function (NONE,..,INPUT08) NONE
O5 Type Output relay 5 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O5 Pulse T Output relay 5 pulse output time (0.01-99.99 sec) 0.01 0.05
O6 Func Output relay 6 function (NONE,..,INPUT08) NONE
O6 Type Output relay 6 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O6 Pulse T Output relay 6 pulse output time (0.01-99.99 sec) 0.01 0.05
O7 Func Output relay 7 function (NONE,..,INPUT08) NONE
O7 Type Output relay 7 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O7 Pulse T Output relay 7 pulse output time (0.01-99.99 sec) 0.01 0.05
O8 Func Output relay 8 function (NONE,..,INPUT08) NONE
O8Type Output relay 8 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O8 Pulse T Output relay 8 pulse output time (0.01-99.99 sec) 0.01 0.05
8.LOOP CONTROL
Type Select Select Recloser Type (NONE,SEC,MID,TIE) NONE
VRS – S/M Voltage response side to SEC & MID (VS,VL) VS
VRS – Tie Voltage response side to TIE (VS,VL,VS&VL) VS
Line VS wire (3PN,3PP,1PN(A),1PN(B),1PN(C),1PP(AB),
VS wire 3PN
1PP(BC),1PP(CA))
VL wire Line VL wire (1PN(A),1PN(B),1PN(C),1PP(AB),1PP(BC),1PP(CA)) 1PN(A)
Cng Alt – Mid Select auto change to Alternate Setting at Mid Point (OFF, ON) OFF
Select auto change to Alternate Setting at Tie Point
Cng Alt – Tie OFF
(OFF,ON(VS),ON(VL),ON(BOTH))
LC After Cl Select after manual close (DISABLE, ENABLE) DISABLE
LC After Op Select after manual open (DISABLE, ENABLE) DISABLE
OT Both DL Open time on both dead Line (0.01 ~ 600.00 sec) 0.01 10.00
Auto Rest’ T Auto restoration Time (0.01 ~ 600.00 sec) 0.01 5.00
DL V Max(%) Dead Line maximum voltage (20.0 ~ 70.0 %) 0.1 50.0
LL V Min(%) Live Line minimum voltage (50.0 ~ 85.0 %) 0.1 70.0
DL Pickup T Dead Line Pickup time delay (0.01 ~ 600.00 sec) 0.01 50.00
LL Regain T Live Line Pickup time delay (0.01 ~ 600.00 sec) 0.01 10.00
DL Reset T Dead Line Reset time delay (0.01 ~ 600.00 sec) 0.01 5.00
NRT After LC Non Recloser Time after LC Action(0.00 ~ 600.00 sec) 0.01 10.00

10 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (6/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT

3.PROTECTION
1.OPERATIONS
Lockout-PHA Operations to lockout – phase (1-5) 1 4
Lockout-GND Operations to lockout – ground (1-5) 1 4
Lockout-SEF Operations to lockout – SEF (1-5) 1 4
Lockout-NEQ Operations to lockout – NEQ (1-5) 1 4
Fast Curve-PHA Operations – phase fast curve (0-5) 1 2
Fast Curve-GND Operations – ground fast curve (0-5) 1 2
Fast Curve-NEQ Operations – NEQ fast curve (0-5) 1 2
2.INTERVALS
Reclose 1 Reclosing time 1 (0.50-600.00 sec) 0.01 0.60
Reclose 2 Reclosing time 2 (1.00-600.00 sec) 0.01 2.00
Reclose 3 Reclosing time 3 (1.00-600.00 sec) 0.01 15.00
Reclose 4 Reclosing time 4 (1.00-600.00 sec) 0.01 15.00
Reset T(AR) Reset time from autoreclose cycle (1.00-600.00 sec) 0.01 30.00
Reset T(LO) Reset time from lockout (1.00-600.00 sec) 0.01 10.00
C/P Wait Limit time to waiting closing power (1.00-600.00 sec) 0.01 60.00
3.PICKUP CURRENT
Phase Pickup current - phase (0.00(OFF),0.04-3.20 xCT phase ratio) 0.01 0.50
Ground Pickup current - ground (0.00(OFF),0.02-3.20 xCT ground ratio) 0.01 0.25
S.E.F Pickup current - SEF (0.000(OFF),0.005-0.160 xCT SEF ratio) 0.001 OFF
NEG Seq Pickup current - NEQ (0.00(OFF),0.04-3.20 xCT phase ratio) 0.01 OFF
4.PHASE FAST
Function Phase fast protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-STI

OPERATIONS CURVE
ANSI-MI ANSI-NI ANSI-VI ANSI-EI ANSI-STI ANSI-STVI
IEC-SI IEC-VI IEC-EI IEC-LTI IEC-STI ESB-SI
ESB-VI ESB-LTVI USER-1 USER-2 USER-3 USER-4
DEF-1S DEF-10S A(101) B(117) C(133) D(116)
E(132) F(163) H(122) J(164) KP(162) L(107)
M(118) N(104) P(115) R(105) T(161) V(137)
W(138) Y(120) Z(134) 1(102) 2(135) 3(140)
4(106) 5(114) 6(136) 7(152) 8(113) 8*(111)
9(131) 11(141) 13(142) 14(119) 15(112) 16(139)
17(103) 18(151) KG(165)

ENHANCED TECHNOLOGY 11
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (7/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
Time Dial Time dial (0.05-15.00) 0.01 0.50
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
5.PHASE DELAY
Function Phase delay protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-VI
Time Dial Time dial (0.05-15.00) 0.01 3.00
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
6.GROUND FAST
Function Ground fast protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-STI
Time Dial Time dial (0.05-15.00) 0.01 0.50
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
7.GROUND DELAY
Function Ground delay protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-VI
Time Dial Time dial (0.05-15.00) 0.01 3.00
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
8.SEF ELEMENT
Function SEF protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Time Delay Time delay (0.00-10.00 sec) 0.01 1.00
9.NEG SEQ FAST
Function Negative sequence fast protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-STI
Time Dial Time dial (0.05-15.00) 0.01 0.50
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00

12 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (8/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
Reset Method Select reset method (INST,LINEAR) INST
10.NEG SEQ DELAY
Function Negative sequence delay protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-VI
Time Dial Time dial (0.05-15.00) 0.01 3.00
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
11.H/C TRIP-PHA
Function High current trip - phase function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - phase (1.00-20.00 xCT phase ratio) 0.01 4.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
12.H/C TRIP-GND
Function High current trip – ground function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - ground (1.00-20.00 xCT phase ratio) 0.01 4.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
13.H/C TRIP-NEQ
Function High current trip - NEQ function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current – NEQ (1.00-20.00 xCT phase ratio) 0.01 4.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active trip Active trip (OFF,1-5) OFF
14.H/C LOCKOUT-PHA
Function High current lockout - phase function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - phase (1.00--20.00 xCT phase ratio) 0.01 8.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
15.H/C LOCKOUT-GND
Function High current lockout - ground function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - ground (1.00--20.00 xCT phase ratio) 0.01 8.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF

ENHANCED TECHNOLOGY 13
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (9/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
16.H/C LOCKOUT-NEQ
Function High current lockout - NEQ function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - NEQ (1.00-20.00 xCT phase ratio) 0.01 8.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
17.COLD LOAD PICKUP
Function Cold load pickup function (OFF,TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
PHA(xCT) Pickup current - phase (1.00-20.00 xCT phase ratio) 0.01 2.00
GND(xCT) Pickup current - ground (1.00-20.00 xCT ground ratio) 0.01 2.00
SEF(xCT) Pickup current – SEF (1.00-20.00 xCT SEF ratio) 0.01 2.00
NEQ(xCT) Pickup current – NEQ (1.00-20.00 xCT phase ratio) 0.01 2.00
Outage Time Outage time (0.00-600.00 sec) 0.01 10.00
RMT Time Restore minimum trip current time limit (0.00-600.00 sec) 0.01 5.00
RMT Func-PHA Restore minimum trip – phase (OFF,ON) ON
RMT Func-GND Restore minimum trip – ground (OFF,ON) ON
RMT Func-SEF Restore minimum trip – SEF (OFF,ON) ON
RMT Func-NEQ Restore minimum trip – NEQ (OFF,ON) ON
Reset Time Cold load pickup function reset time (0.00-600.00 sec) 0.01 0.60
18.DIRECTION
1.PHASE DIRECTION
Type Direction of current flow – phase (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 300
nd
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2 norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
2.GROUND DIRECTION
Type Direction of current flow – ground (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 135
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
3.SEF DIRECTION
Type Direction of current flow – SEF (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 135
nd
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2 norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
4.NEQ DIRECTION
Type Direction of current flow – NEQ (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 135

14 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (10/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
19.VOLTAGE
1.UNDER VOLTAGE 1
Function Under voltage 1 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
nd
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2 norminal volt) 0.01 0.70
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
nd
Min. V(xVT) Minimum voltage (0.00-1.25 xVT 2 norminal volt) 0.01 0.10
Pickup Type Under voltage 1 pickup type (1,2,3 phase) 1P
2.UNDER VOLTAGE 2
Function Under voltage 2 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
nd
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2 norminal volt) 0.01 0.70
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
nd
Min. V(xVT) Minimum voltage (0.00-1.25 xVT 2 norminal volt) 0.01 0.10
Pickup Type Under voltage 2 pickup type (1,2,3 phase) 1P
3.OVER VOLTAGE 1
Function Over voltage 1 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 1.20
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
Pickup Type Over voltage 1 pickup type (1,2,3 phase) 1P
4.OVER VOLTAGE 2
Function Over voltage 2 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 1.20
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
Pickup Type Over voltage 2 pickup type (1,2,3 phase) 1P
20.FREQUENCY
Function Frequency function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Under PU(Hz) Pickup frequency for underfrequency (40.00-65.00 Hz) 0.01 55.00
Under TD Time delay for underfrequency (0.00-600.00 sec) 0.01 2.00
Over PU(Hz) Pickup frequency for overfrequency (50.00-65.00 Hz) 0.01 65.00
Over TD Time delay for overfrequency (0.00-600.00 sec) 0.01 6.00
Min. V(xVT) Minimum voltage (0.00-1.25 x VT 2nd norminal volt) 0.01 0.10
Min. I(xCT) Minimum current (0.01-3.20 x CT Phase ratio) 0.01 0.01
NFCL Func’ Nomal frequency CLOSE function (OFF,ON) OFF

ENHANCED TECHNOLOGY 15
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (11/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
NFCL TD Nomal frequency CLOSE time delay (0.0-6000.0sec) 0.1 60.0
21.OTHER ELEMENT
Seq’ Coordi’ Sequence coordination function (OFF,ON) OFF
L.O Priority Lockout priority (GROUND,PHASE) GND
F/I Reset Fault indicator reset method (AUTO,MANUAL) AUTO
D/T M-Close Manual close Time delay (0.00-600.00 sec) 0.01 0.00
22.USER CURVE SET
1.USER CURVE 1
Factor a User define curve 1 factor a (0.0000-150.9999) 0.0001 59.5000
Factor b User define curve 1 factor b (0.0200-150.9999) 0.0001 2.0000
Factor r User define curve 1 factor r (0.0000-150.9999) 0.0001 1.8000
Factor rt User define curve 1 factor rt (0.0000-150.9999) 0.0001 59.5000
2.USER CURVE 2
Factor a User define curve 2 factor a (0.0000-150.9999) 0.0001 39.8500
Factor b User define curve 2 factor b (0.0200-150.9999) 0.0001 2.0000
Factor r User define curve 2 factor r (0.0000-150.9999) 0.0001 0.9500
Factor rt User define curve 2 factor rt (0.0000-150.9999) 0.0001 39.8500
3.USER CURVE 3
Factor a User define curve 3 factor a (0.0000-150.9999) 0.0001 59.1000
Factor b User define curve 3 factor b (0.0200-150.9999) 0.0001 2.0000
Factor r User define curve 3 factor r (0.0000-150.9999) 0.0001 0.3450
Factor rt User define curve 3 factor rt (0.0000-150.9999) 0.0001 59.1000
4.USER CURVE 4
Factor a User define curve 4 factor a (0.0000-150.9999) 0.0001 5.6700
Factor b User define curve 4 factor b (0.0200-150.9999) 0.0001 2.0000
Factor r User define curve 4 factor r (0.0000-150.9999) 0.0001 0.0352
Factor rt User define curve 4 factor rt (0.0000-150.9999) 0.0001 5.6700

4.MONITORING
1.DEMAND
Function Monitoring demand function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Type Demand method (THERMAL,ROLLING) THM
Time
Time interval (5,10,15,20,30,60 minute) 5
Constant(m)
PHA PU(xCT) Current demand pickup-phase (0.00(OFF),0.04-3.20xCT phase ratio) 0.01 0.60
Current demand pickup-ground
GND PU(xCT) 0.01 0.30
(0.00(OFF),0.020-3.20xCTground ratio)
NEQ PU(xCT) Current demand pickup-NEQ (0.00(OFF),0.04-3.20 xCT phase ratio) 0.01 0.60

16 ENHANCED TECHNOLOGY
APPENDIX http://www.entecene.co.kr

Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (12/12)


FACTORY
MANU NAME DESCRIPTION STEP
DEFAULT
2.SYNCHROCHECK
Function Synchrocheck function (OFF,ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
D.V.Max(xVT) Dead line maximum voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.50
L.V.Min(xVT) Live line minimum voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.85
M.V.D(V) Maximum voltage difference (0.00-1.25 xVT 2nd norminal volt) 0.01 0.10
M.A.D(Deg) Maximum angle difference (0-100 deg) 1 15
M.F.D(Hz) Maximum frequency difference (0.00-5.00 Hz) 0.01 2.00
Sync Phase Synchrocheck phase (R(AB), S(CB) ,T phase) R(AB)
3.TRIP COUNTER
Function Monitoring trip counter function (OFF,ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Limit Counter for ALARM (1-20000) 1 10000
Counter set Trip counter set when clearing mode (0-10000) 1 0
4.RECLOSER WEAR
Function Recloser wear monitor function (OFF,ALARM) ALARM
Pickup(%) Pickup wear level (0.0-50.0 %) 0.1 20.0
Rated Volt(kV) Recloser rated voltage (15,27,38 kV) *NOTE (1
Interrupt Interrupt rating (5.0-50.0 kA) 0.1 12.5
No. Max I Number of operation under Maximum interrupt rating (1-999) 1 100
A Wear Set Recloser Wear set - A phase when clearing mode (0.00-100.00 %) 0.01 100.00
B Wear Set Recloser Wear set - B phase when clearing mode (0.00-100.00 %) 0.01 100.00
C Wear Set Recloser Wear set - C phase when clearing mode (0.00-100.00 %) 0.01 100.00
5.BATTERY TEST
BT Time(day) Self battery test interval (0FF,1-7 day) 1 OFF
6.FAULT LOCATOR
Function Fault Locator (OFF,ON) OFF
Length(km) Length of Feeder (0.1-99.9 km) 0.1 50.0
Z1(RES) Real impedance of the feeder positive sequence (0.1-6000.0 ohms) 0.1 10.0
Imaginary impedance of the feeder positive sequence
Z1(IND) 0.1 10.0
(0.1-6000.0 ohms)
Z0(RES) Real impedance of the feeder zero sequence (0.1-6000.0 ohms) 0.1 10.0
Z0(IND) Imaginary impedance of the feeder zero sequence (0.1-6000.0 ohms) 0.1 10.0
NOTE

1) The rated voltage determines the Recloser type.

ENHANCED TECHNOLOGY 17
APPENDIX http://www.entecene.co.kr

Appendix F. Ordering Guide


Choose from the following options.
E V R C 2 A - M 2 - -

Example Model E V R C 2 A - M 2 - 2 2 0 C 2 7 5 - D 1 2 X X L X P

220Vac** 2 2 0
Control Power 110Vac 1 1 0
Other Voltage X X X
CVD (Capacitor Voltage Divider)** C
Voltage Sensing Device
VT (Voltage Transformer) V
15kV 1 5
Line Voltage Class 27kV 2 7
38kV 3 8
50Hz 5
Line Frequency
60Hz 6
Without** X
Modbus M
DNP D
Communication Protocol Unit DNP & Modbus C
DNP & Modbus & IEC60870-5-101 1
DNP & Modbus & IEC60870-5-103 3
DNP & Modbus & IEC60870-5-104 4
12Vdc** 1 2
User Available DC Power 13Vdc 1 3
Output 15Vdc 1 5
24Vdc 2 4
Without** X
125Vdc** S
12Vdc A
SCADA Input/Output
Input Voltage 24Vdc B
48Vdc C
250Vdc D
Without** X
Loop Automation Scheme
Available L
LCD (Liquid Crystal Display)** L
User Interface Panel Display
VFD (Vacuum Fluorescent Display) V
Without** X
Cubicle Heater
Available H
Without** X
Mount Accessory Plate
Available P

NOTES
1. The directional controls element is available as an ordering VT (Voltage Transformer)
2. Operaing Temperature : LCD (-20℃~+70℃), VFD (-40℃~+85℃)
3. ** : EVRC2A Standard Type

18 ENHANCED TECHNOLOGY