Power Monitoring
Table of Contents
Powermonitor Products
• Specifications
• Ordering Information
• Product Specification Page 7-2
Our Powermonitor products meet the needs of producers and Power Monitoring Product and Features See Page
consumers of electric power. These products provide monitoring Powermonitor 3000 (1404 series)
and control information for substation and distribution centers, y Compact size
electrical control panels, and many utility, commercial, and industrial y Oscillography, harmonic analysis, and transient detection
applications including motor control centers. y Multiple communication options
this page
y Various update rates
The following power management application definitions help y Configurable logs up to 45000 parameters deep
explain the advantages of using power quality and automation y Time stamp data logging of system measurements and
products. events
Demand management is a control system designed to minimize Portable Powermonitor 3000 Products (1803 PPM)
y Monitor power anywhere in a facility
electrical demand penalties that can represent up to 30% of a
y Diagnose power quality problems, harmonic, transient, and
typical industrial utility bill. voltage sags, swells, and imbalance
Activity-based cost accounting is a control system that lets a y Capture and save waveforms and harmonics data
this page
customer allocate energy costs based on actual usage, which is y Options for communications to a PC or PLC include Ethernet
and RS-485
based on sub-metering rather than other measurements such as y Portable unit in a rugged carrying case
square footage allocation. y Easy to install and use, with all the components you need in
Power control is a control system where electricity is the process a single package
output. There is usually on-site generation, emergency load Starter Kit (1803-SKCT)
shedding, or systems where a high-quality and stable electric power y Provides customers with the CT’s, fuses, and shorting
source is critical to the process. terminal blocks necessary to install power monitoring 7-3
devices.
Our Line Synchronization Module’s design reduces the complexity
of conventional technology, increases generator control Powermonitor II Products (1403 series)
performance, and provides an easily integrated automation platform y 28…90 ms Selectable update rates
for both retrofit and new power facilities. y Simultaneous multi-channel oscillograph recordings
7-3
y Time-stamped data logging of system measurements and
Power quality is a control system that monitors power quality events
events or conditions that could cause a production shutdown like y High accuracy
voltage sags, brownouts, transients, and high harmonic distortion. Powermonitor Products (1400 series)
y Analysis and capture
Load profiling is a stand-alone application or networked control
y Archival 7-3
system where electrical loads are monitored or profiled. These load y Control of outputs and communication
profiles let the user prepare for utility deregulation and make fact- y Monitoring capabilities for energy cost allocation
based decisions on future demand-side management control Mini Powermonitor (1405)
systems. y Basic functionality
y Lower cost
y Digital 3-phase panel meter 7-3
y Real time volts and amps
y Display included
y OEM panels
Line Synchronization Module (1402-LS51)
y Synchronization
y Anti-motoring 7-3
y Load Sharing
y Power monitoring
Ethernet Energy Module (1803-EEM)
y Packaged processor that gathers pulse and analog data
from energy meters (gas, electric, water, etc.) and presents 7-3
that information to RSEnergymetrix or another software
package over Ethernet
Power Monitoring Software
y RSEnergyMetrix 7-4
y RSPower32
Typical Configuration
Inputs
0…5 A rms Cont.,
Current
200 A rms 1 s
Frequency 47…63 Hz (steady-state)
Dielectric Withstand Voltage 2500V rms
Burden 0.0025V A
Voltage 120V rms (339 Vpk-pk) maximum peak
Input Impedance/Burden 728 kΩ/0.02V A
Synchronization Window Independent Upper and Lower Thresholds
Voltage 0.05% steps
Frequency 0.01 Hz steps
Phase 1 degree steps
Isolated Load Sharing Input/Output
Max. Common Mode Voltage 240V AC
Continuous Voltage 2…4V DC
Input Impedance 45 kΩ
Backplane Current Load 1.1 A @ 5V DC
Environmental Conditions
Operating Temperature 0…60 °C (32…140 °F)
Storage Temperature –40…100 °C (–40…212 °F)
Humidity 5…95% (without condensation)
Update Rate
Synchronizing Bus Error Parameters 100 ms
200 ms (synchronization inactive)
Load Share and Monitor Parameters
1 s (synchronization active)
Accuracy @ 25 °C (77 °F)
Full Scale = 1.75 x CT Primary x PT Primary
Current Measurement ±0.2% of full scale (full scale = 1.4 x CT primary)
Voltage Measurement ±0.2% of full scale (full scale = 1.25 x PT primary)
Frequency and Slip Frequency Measurement ±0.05 Hz (within the 47…63 range)
Power, Power Factor, VA ±0.4% of full scale power consumption
Weight 2.72 kg (6.0 lbs)
These specifications apply to the Powermonitor 3000 Base Module (1404 Series)
Input and Output Ratings
Control Power 1404-Mx05A-xxx 120V/240V AC 50/60Hz or 125V/250V DC
0…399V L-N
Voltage Inputs
0…691V L-L
Current Inputs 0…10.6 A
Status Inputs Contact closure (internal 24V DC)
Terminal Blocks
#12 AWG (4 mm2) max.
1404-Mx Power Supply and Voltage Input Terminals Screw torque: 1.02 Nm (9 lb•in)
75 °C Copper wire only
#14 AWG (2.5 mm2) max
1404-Mx Relay, KYZ Outputs, Current Input
Screw torque: 1.18 Nm (10.4 lb•in)
Terminals
75 °C Copper wire only
1404-Mx Status Inputs, RS-485, remote I/O, #14 AWG (2.5 mm2)
DeviceNet Screw torque: 0.56 Nm (5 lb•in)
General Specifications
Control Power (1404-Mx) 2000V
Voltage Inputs 2000V
Dielectric Withstand Current Inputs 2000V
Status Inputs 750V
Control Relays 1600V
Operating Temperature –20…60 °C (–4…140 °F)
Storage Temperature –40…85 °C (–40…185 °F)
Humidity 5…95% (without condensation)
10…500 Hz
Vibration operational: 1 g (±0.006 in.)
non-operational: 2.5 g (+0.015 in.)
These specifications apply to the Powermonitor II Master and Display Modules (1403 Series).
These specifications apply to the Powermonitor II Communication Cards (1403-NENET, 1403-NDNET, 1403-NSC).
✶
Bulletin 1803-PPM
Description Cat. No.
Portable Powermonitor 3000 M8 with Ethernet
1803-PPM8E
Communication Card (Includes Display Module)
Portable Powermonitor 3000 Display Module 1803-PDM
Powermonitor II Products
Powermonitor II Master Module (Full Metering)
Measured Current
A Full Scale Measured Voltage Power Supply Cat. No.
5 120/240V AC 50/60 Hz or 125/250V DC 1403-MM05A
5 120…347VL-N 24V AC 50/60 Hz or 24/48V DC 1403-MM05B
1 (208…600Vc) 120/240V AC 50/60 Hz or 125/250V DC 1403-MM01A
1 24V AC 50/60 Hz or 24/48V DC 1403-MM01B
120/240V AC 50/60 Hz or
5 120…600V 1403-MM05A
125/250V DC
12/24V AC 50/60 Hz
or 1403-DMB
12/240/48V DC
Powermonitor II Display Module
Cat. No. 1403-DM
Accessories
Powermonitor II
Description Cat. No.
Smart Communication Card 1403-NSC
2 x 25 cm F Link 1403-CF000
2 x 1 m F Link 1403-CF001
2 x 3 m F Link 1403-CF003
2 x 5 m F Link 1403-CF005
10 m F Link 1403-CF010
20 m F Link 1403-CF020
50 m F Link 1403-CF050
1803-PPM
Description Cat. No.
Current Transformer with 3000/2000/100:5 ratio, 4 in x 3/4 in window size 1803-CT3000M
Current Transformer with 1000/500/250.5:5 ratio, 2 in diameter window size 1803-CT1000M
Current Transformer with 600/300/150.5:5 ratio, 2 in diameter window size 1803-CT600M
Current Transformer with 400/200/100.5:5 ratio, 2 in diameter window size 1803-CT400M