You are on page 1of 12

Table_of_Contents.

qxd 14/01/2004 10:18 Page 7-1

Power Monitoring
Table of Contents

Powermonitor Products
• Specifications
• Ordering Information
• Product Specification Page 7-2

Visit our website: www.ab.com/catalogs 7-1


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 10:58 Page 7-2

Bulletin Engineered Systems and Application Products


Power Monitoring

Our Powermonitor products meet the needs of producers and Power Monitoring Product and Features See Page
consumers of electric power. These products provide monitoring Powermonitor 3000 (1404 series)
and control information for substation and distribution centers, y Compact size
electrical control panels, and many utility, commercial, and industrial y Oscillography, harmonic analysis, and transient detection
applications including motor control centers. y Multiple communication options
this page
y Various update rates
The following power management application definitions help y Configurable logs up to 45000 parameters deep
explain the advantages of using power quality and automation y Time stamp data logging of system measurements and
products. events
Demand management is a control system designed to minimize Portable Powermonitor 3000 Products (1803 PPM)
y Monitor power anywhere in a facility
electrical demand penalties that can represent up to 30% of a
y Diagnose power quality problems, harmonic, transient, and
typical industrial utility bill. voltage sags, swells, and imbalance
Activity-based cost accounting is a control system that lets a y Capture and save waveforms and harmonics data
this page
customer allocate energy costs based on actual usage, which is y Options for communications to a PC or PLC include Ethernet
and RS-485
based on sub-metering rather than other measurements such as y Portable unit in a rugged carrying case
square footage allocation. y Easy to install and use, with all the components you need in
Power control is a control system where electricity is the process a single package
output. There is usually on-site generation, emergency load Starter Kit (1803-SKCT)
shedding, or systems where a high-quality and stable electric power y Provides customers with the CT’s, fuses, and shorting
source is critical to the process. terminal blocks necessary to install power monitoring 7-3
devices.
Our Line Synchronization Module’s design reduces the complexity
of conventional technology, increases generator control Powermonitor II Products (1403 series)
performance, and provides an easily integrated automation platform y 28…90 ms Selectable update rates
for both retrofit and new power facilities. y Simultaneous multi-channel oscillograph recordings
7-3
y Time-stamped data logging of system measurements and
Power quality is a control system that monitors power quality events
events or conditions that could cause a production shutdown like y High accuracy
voltage sags, brownouts, transients, and high harmonic distortion. Powermonitor Products (1400 series)
y Analysis and capture
Load profiling is a stand-alone application or networked control
y Archival 7-3
system where electrical loads are monitored or profiled. These load y Control of outputs and communication
profiles let the user prepare for utility deregulation and make fact- y Monitoring capabilities for energy cost allocation
based decisions on future demand-side management control Mini Powermonitor (1405)
systems. y Basic functionality
y Lower cost
y Digital 3-phase panel meter 7-3
y Real time volts and amps
y Display included
y OEM panels
Line Synchronization Module (1402-LS51)
y Synchronization
y Anti-motoring 7-3
y Load Sharing
y Power monitoring
Ethernet Energy Module (1803-EEM)
y Packaged processor that gathers pulse and analog data
from energy meters (gas, electric, water, etc.) and presents 7-3
that information to RSEnergymetrix or another software
package over Ethernet
Power Monitoring Software
y RSEnergyMetrix 7-4
y RSPower32

Powermonitor 3000™ Products (1404) Portable Powermonitor 3000


The Powermonitor 3000 has four versions, the M4, M5, M6, and the The Portable Powermonitor 3000 permits you to monitor power
M8. The M4 unit provides basic metering including frequency, anywhere in your facility, with a unit that offers superior functionality
voltage, current, and power. It also provides calculated information and accuracy. The rugged unit is self contained including all cables
such as energy consumption, power factor, and total harmonic and manuals. The local display provides access to all real time and
distortion. The unit also has onboard logging capability that can accumulated power parameters, power quality measurements
store data, record the min and max of each parameter, and keep an including harmonics up to the 63rd, set-point status and
event log. configuration, and device status and configuration. Options for
communications to a PC or PLC include Ethernet and RS-485.
The M5 offers M4 functionality with flash upgrade capabilities to
higher levels. The M6 unit contains all of this functionality in addition
to power quality features such as, extensive waveform capture and
storage and spectral analysis up to the 41st harmonic. The M8 adds
more sophisticated power quality tools, greater speeds, accuracy
and captures sub-cycle transients as well as harmonic analysis up
to the 63rd harmonic.
For more information, see product profiles: 1404-PP001B-US-P,
1404-PP004A-EN-P, and 1404-PP002B-EN-P

7-2 Visit our website: www.ab.com/catalogs


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 10:59 Page 7-3

Bulletin Engineered Systems and Application Products


Power Monitoring
Product Overview

Starter Kit (1803-SKCT) MiniPowermonitor (1405)


The new Powermonitoring Starter Kit (1803-SKCTXX) provides The MiniPowermonitor has 2 versions, the M610 and the M620.
customers with the CT’s, Fuses, and shorting terminal blocks The M610 is a 3-phase AC monitor. The M610 measures and
necessary to install power monitoring devices. displays line-neutral and line-line voltages. The instantaneous, 15
The kit includes: minute averaged and peak values of the measured phase currents
y Three-Split-core CT’s (400:5, 1200:5, and 2000:5 CT’s ratio are displayed sequentially. Typically in 3-phase AC power systems
options are available) four analog measuring instruments are used; three for phase
y One 8-point shorting terminal block currents and one for voltage through a phase selector switch. The
y One 3-pole fuse holder with 10 A fuses M610 combines these measurements functions into a single
compact instrument, which cyclically displays currents and voltages
of all 3 phases simultaneously.
Powermonitor II Products
The Powermonitor II Master Module (Cat. No. 1403 series) is an M610 Features and Benefits:
alternative to traditional electro-mechanical metering devices. One y Three-line digital display simultaneously shows measurements of
Powermonitor II module can replace many individual transducers all 3 phases
and meters within a single package. Communication cards for the y Displays 15-minute averaged measurements
Powermonitor II Master Module include: y Peak value storage and display
y Ethernet Smart Communication Card (Cat. No. 1403-NENET) y Automatic sequencing of displayed parameters
lets the Powermonitor II Master Module communicate directly with y User selectable standard current transformer ratios
a personal computer, Allen-Bradley PLC-5 Ethernet processors, y Non volatile memory
and SLC 5/05 Ethernet processors. The card has a communication
rate of 10 M bit/s. and supports both 10BaseT and 10Base5 The M620 measures voltages and RMS currents of 3-phase power
Ethernet ports. The RS-232 port is for local configuration. The card lines. It also measures the power factor and the active power and
features built-in HTML web pages for internet read access of totalizes energy transferred for each phase and for all phases
critical Powermonitor II data. This card is compatible with combined.
RSEnergyMetrix™, RSView32™, RSPower32™, and RSLinx™
software. M620 Features and Benefits:
y DeviceNet Communication Card (Cat. No. 1403-NDNET) y Measures all 3-phases of power parameters and has a 3-line
provides the Powermonitor II Master Module with a DeviceNet display
communication port to communicate directly with PLC-5 y Voltage measurement with limit detection (for low or medium
processors and ControlLogix processors. voltage power systems)
y Smart Communication Card (Cat. No. 1403-NSC) provides both y Current measurement with selectable current transformer ratios
Remote I/O and RS-232/RS-485 communication capabilities for y Average and peak current measurements
the Powermonitor II Master Module. It’s compatible with PLC-5 y Effective and apparent power measurement
and SLC 500 processors via the Remote I/O link. y Energy measurement with unit pulse output
For communication card specifications, see page 7-8. y Menu assisted instrument set-up via front panel key switches
The Powermonitor II Display Module is an optional input/output y Optional 4-20 mA outputs (6) or RS485 ASCII interface
device that helps you set up and configure the Master Module. It
has four tactile operator buttons and an LCD display. Up to three Line Synchronization Module
Display Modules can be connected to a single Master Module
For an integrated power-generation control solution, we offer the
providing up to three sets with two lines of data each. All
Line Synchronization module (Cat. No. 1402-LS51). This module is
communication between the Powermonitor II Master module and
designed to meet the needs of manufacturers, system integrators,
Display module occur over a fiber-optic link. For specifications, see
and sophisticated users of industrial and commercial alternators and
page 7-8. For ordering information, see page 7-9.
cogeneration systems that require two 3-phase systems to be
For typical configuration, see page 7-5.
synchronized with each other. This module provides a means for
For more information, see Publication 1403-2.0.
synchronization, load sharing, and high-speed power system
monitoring. For specifications, see page 7-6.
Powermonitor Products
Powermonitor products (Cat. No. 1400 series) provide many built-in Ethernet Energy Module (1803-EEM)
monitoring, archival, and control features. The Powermonitor Display
The Ethernet Energy Module (EEM) is a programmable logic
Module (Cat. No. 1400-PDxxx) is an alternative to an installed panel
controller-based solution for gathering and logging data from third
of traditional analog electro-mechanical metering devices. One
party energy meters into an RSEnergyMetrix server. The EEM ships
Powermonitor can replace many individual transducers and meters
with embedded logic for incorporation into demand management;
within a single package. The Display Module is designed for greater
cost allocation, energy/power monitoring and load management
than 1 kW per phase or for motors that are 2 Hp or larger. It can be
systems.
used as a stand-alone power monitoring instrument or it can be
integrated into a system using the 1400-DCU plug-in y Customers wire the meter outputs and 120V AC power to the
communication card for Remote I/O, RS-232, and RS-485 terminal blocks in the enclosure and reads the data out of the
communication. appropriate data table
For a typical configuration, see page 7-5. For specifications, see y All enclosures are NEMA 12 rated and include a 24V DC power
page 7-6. supply
For ordering information, see page 7-9.
For more information, see product data 1400-2.0. The EEM includes:
y 1- SLC-5/05 Ethernet processor w/ 16k memory
y 1- SLC Rack power supply
y Discrete 16pt. 24V DC sinking input module(s)✶
y Analog 8 point input module(s)†
For more information, see product profile: 1803-PP005A-EN-P
✶ Miscellaneous hardware consisting of circuit breakers, fuse holders, ground
and external convenience terminal blocks.
† Quantities and types of input modules and hardware will depend on the
configuration chosen for a particular set of installation requirements.

Visit our website: www.ab.com/catalogs 7-3


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 10:59 Page 7-4

Bulletin Engineered Systems and Application Products


Power Monitoring
Product Overview, Continued

Power Monitoring Software Monitoring and Analysis — RSEnergyMetrix is a powerful load


There are two types of power monitoring software: profiling, cost allocation and billing analysis tool.
y RSEnergyMetrix Software offers complete energy management for y Log usage, cost and power quality data
all utilities on a wide area network y View any parameter in real time
y RSPower32 Software offers simple integration of power monitoring y Create historical trend reports and charts
information into an existing human machine interface y View historical trending of individual meters and groups and save
tabular data for further processing and analysis
RSEnergyMetrix (9307-EM) y Establish consumption baseline and user defined time of use
periods
RSEnergyMetrix is a sophisticated web-enabled, energy
management software that puts critical energy information at your y Create custom rate plans using the rate plan menu and line item
desktop. scripting
y Assign rate plans to meters or groups of meters
The RSEnergyMetrix Software Suite combines data communication, y Import and export rate schedules in XML format
client-server applications, and Microsoft’s advanced .NET™ web y Create and print daily or monthly cost and billing reports by:
technology to provide you with a complete energy-management − Meter
solution. − Business group
With RSEnergyMetrix, you can capture, analyze, store, and share − Department
energy data across your entire enterprise via a LAN or WAN using a − Site
simple web browser. This makes it a snap to distribute the y Create energy budgets and forecasts
knowledge you need to optimize energy consumption, which can y Compare and contrast alternative utility rates; do “what-if” for
help improve productivity while lowering energy costs. other rate structures
y Print and store all reports and charts
Features and Benefits:
Scalable — Has the scalability to add components while Software and Hardware Requirements for a Midrange
maintaining your original investments.
Server:
y RSEnergyMetrix Manager
y Windows 2000 Server or Advanced Server
y RSEnergyMetrix RT
y SQL Server 2000 Standard or Enterprise
y RSEnergyMetrix 3PX
y 2 or 4 CPU 800+ MHz Pentium III or better
y RSEnergyMetrix ReportsPlus
y 1 GB RAM
y RSEnergyMetrix ChartsPlus
y 30 GB hard disk (separate disk(s) for operating system/log files
and then RAID 5 for main database files preferred)
Connectivity — Connect to metering points right from your desktop
PC. For more information, see technical data: ENEMTX-TD001A-EN-P
y Connectivity through RSLinx: RS-232, RS-485, Ethernet,
DeviceNet, RIO passthru, optical, and modem (RSLinx Lite is RSPower32
included with the manager package) Rockwell Automation’s RSPower32 is a stand-alone application and
y Third part connectivity – OPC also contains an ActiveX component for a user to configure and
display information from Allen-Bradley power monitoring products.
Configuration — RSEnergyMetrix provides easy and flexible RSPower32 has simple screens for configuring and viewing data
configuration. from power monitors. When combined with RSView32, RSPower32
adds these features directly to the RSView32 Project Manager
y Configure electricity, gas, water, and steam meters or any energy interface and provides data for tags, alarming, data logging and
or production related inputs trending.
y Configure Manual Meters as placeholders in the database for
manual data entry Utilizing the exposed object model, RSView32 or other applications✶
y Configure user defined data sources such as standard PLC-5 or such as Visual Basic can use RSPower32’s data server to read and
SLC hardware types or Generic OPC write data to power monitors and perform standard operations like
y Flexible configuration allows you to: setting the time, saving logs to disk, or capturing a waveform.
− Name your devices ✶ Consult your local Allen-Bradley Distributor for software compatibility.
− Name your groups
− Create sub-groups
− Put meters in multiple groupings for cost allocation
− Set and change meter configuration values remotely
− Set multi-level password protection and privileges

7-4 Visit our website: www.ab.com/catalogs


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 10:59 Page 7-5

Bulletin Engineered Systems and Application Products


Power Monitoring
Product Overview, Continued

Typical Configuration

Visit our website: www.ab.com/catalogs 7-5


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 11:00 Page 7-6

Bulletin Engineered Systems and Application Products


Power Monitoring
Specifications

These specifications apply to the Line Synchronization Module (1402-LS51).

Class I Div. 2 Hazardous

Inputs
0…5 A rms Cont.,
Current
200 A rms 1 s
Frequency 47…63 Hz (steady-state)
Dielectric Withstand Voltage 2500V rms
Burden 0.0025V A
Voltage 120V rms (339 Vpk-pk) maximum peak
Input Impedance/Burden 728 kΩ/0.02V A
Synchronization Window Independent Upper and Lower Thresholds
Voltage 0.05% steps
Frequency 0.01 Hz steps
Phase 1 degree steps
Isolated Load Sharing Input/Output
Max. Common Mode Voltage 240V AC
Continuous Voltage 2…4V DC
Input Impedance 45 kΩ
Backplane Current Load 1.1 A @ 5V DC
Environmental Conditions
Operating Temperature 0…60 °C (32…140 °F)
Storage Temperature –40…100 °C (–40…212 °F)
Humidity 5…95% (without condensation)
Update Rate
Synchronizing Bus Error Parameters 100 ms
200 ms (synchronization inactive)
Load Share and Monitor Parameters
1 s (synchronization active)
Accuracy @ 25 °C (77 °F)
Full Scale = 1.75 x CT Primary x PT Primary
Current Measurement ±0.2% of full scale (full scale = 1.4 x CT primary)
Voltage Measurement ±0.2% of full scale (full scale = 1.25 x PT primary)
Frequency and Slip Frequency Measurement ±0.05 Hz (within the 47…63 range)
Power, Power Factor, VA ±0.4% of full scale power consumption
Weight 2.72 kg (6.0 lbs)

These specifications apply to the Powermonitor 3000 Base Module (1404 Series)
Input and Output Ratings
Control Power 1404-Mx05A-xxx 120V/240V AC 50/60Hz or 125V/250V DC
0…399V L-N
Voltage Inputs
0…691V L-L
Current Inputs 0…10.6 A
Status Inputs Contact closure (internal 24V DC)
Terminal Blocks
#12 AWG (4 mm2) max.
1404-Mx Power Supply and Voltage Input Terminals Screw torque: 1.02 Nm (9 lb•in)
75 °C Copper wire only
#14 AWG (2.5 mm2) max
1404-Mx Relay, KYZ Outputs, Current Input
Screw torque: 1.18 Nm (10.4 lb•in)
Terminals
75 °C Copper wire only
1404-Mx Status Inputs, RS-485, remote I/O, #14 AWG (2.5 mm2)
DeviceNet Screw torque: 0.56 Nm (5 lb•in)
General Specifications
Control Power (1404-Mx) 2000V
Voltage Inputs 2000V
Dielectric Withstand Current Inputs 2000V
Status Inputs 750V
Control Relays 1600V
Operating Temperature –20…60 °C (–4…140 °F)
Storage Temperature –40…85 °C (–40…185 °F)
Humidity 5…95% (without condensation)
10…500 Hz
Vibration operational: 1 g (±0.006 in.)
non-operational: 2.5 g (+0.015 in.)

7-6 Visit our website: www.ab.com/catalogs


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 11:00 Page 7-7

Bulletin Engineered Systems and Application Products


Power Monitoring
Specifications, Continued

These specifications apply to the Powermonitor II Master and Display Modules (1403 Series).

Input and Output Ratings


120V/240V AC 50/60 Hz or 125/250V DC
1403-xMxxA
(0.2 A maximum loading)
24V AC 50/60 Hz or 24/48V DC (1 A maximum
1403-xMxxB
loading)
Control Power
120V/240V AC 50/60 Hz or 125/250V DC
1403-DMA
(0.05 A maximum loading)
12/24V AC 50/60 Hz or 12/24/48V DC
1403-DMB
(0.15 A maximum loading)
0…1 A (1403-xM01x)
Nominal Full Scale Input
0…5 A (1403-xM05x)
15 A continuous
Current Inputs Overload Withstand
300 A for 1 s
Burden 0.05V A
Impedance 0.002 Ω
Voltage Inputs Nominal Full Scale Input: 120…347V L-N (208…600V L-L) Input Impedance: 1 MΩ minimum
Status Inputs Contact closure (internal 24V DC)
Nominal Input: 1.0V AC/±1.4V DC
Analog Input
Overload withstand: 120V for one minute
General Specifications
Cat. No. 1403-xMxxA, -DMA: 1600V
Control Power
Cat. No. 1403-xMxxB, -DMB: 1000V
Voltage Inputs 2200V
Dielectric Withstand:
Current Inputs 4160V
Status Inputs 1000V
Control Relays 1600V
#10 AWG (6 mm2) max.
1403-xM Voltage and Current Terminals
Screw torque: 1.81 Nm (16 lb•in)
1403-xM Power, Status, Analog, Relay, and Ground #12 AWG (4 mm2) max.
Terminal Block 75 °C (167 °F) CU wire only
terminals Screw torque: 0.90 Nm (8 lb•in)
#14 AWG (2.5 mm2) max.
1403-DM Terminals
Screw torque: 0.56 Nm (5 lb•in)
1403-MM, -LM: –40…60 °C (–40…140 °F)
Operating Temperature
1403-DM: –20…60 °C (–4…140 °F)
Storage Temperature –40…85 °C (–40…185 °F)
Humidity 5…95% (without condensation)
10…500 Hz
Vibration operational: 1 g (±0.006 in)
non-operational: 2.5 g (+0.015 in)
operational: 15 g 1/2 sine pulse, (11 ms duration)
Shock
non-operational: 30 g 1/2 sine pulse, (11 ms duration)
UL Type Rating The Display Module is rated UL Type 4X (indoor only) IP65

These specifications apply to the Powermonitor II Communication Cards (1403-NENET, 1403-NDNET, 1403-NSC).

–40…60 °C (–40…140 °F)


Operating Temperature
DeviceNet Card: –40…55 °C (–40…131 °F)
Storage Temperature –40…85 °C (–40…185 °F)
Humidity 5…95% (without condensation)
operational: 0.006 in. DA/1.0 g sine, 10…500 Hz, 3 orthogonal axes
Vibration
non-operational: 0.015 in. DA/2.5 g sine, 10…500 Hz, 3 orthogonal axes
operational: 15 g 1/2 sine, 11 ms duration, 3 orthogonal axes, 3 (+) and 3 (-) pulse axes, 18 pulses total
Shock non-operational: 30 g 1/2 sine, 11 ms duration, 3 orthogonal axes, 3 (+) and 3 (-) pulse axes, 18 pulses
total
✶ The 1403-NDNET card is not CE approved.

Visit our website: www.ab.com/catalogs 7-7


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 11:07 Page 7-8

Bulletin Engineered Systems and Application Products


Power Monitoring
Specifications, Continued

These specifications apply to the Powermonitor Display module (1400-PDxxx).


Input and Output Ratings
120VL-N/208VL-L
Nominal full-scale input (+15%, –75%)
Voltage Inputs 277VL-N/480L-L Overload withstand: 2500V AC for 1 second
347L-N/600VL-L Input impedance: 2 MΩ

5A AC only nominal full-scale input,


Current Inputs Overload withstand: 15 A continuous, 300 A for 1 second
1A Input impedance: 0.002 Ω, Burden 0.05 VA
20V AC/DC = active, 6V AC/DC = inactive, minimum pulse width: 40 ms
Status Inputs
Input Impedance: 49.2 KΩ, 277V AC/DC maximum
Resistive 10 A, 277V AC/30V DC
Control Relays Contact Ratings (SPDT)
Inductive 240V AC, 3400 VA inrush, 360 VA sealed
AC/DC 85…264V AC/0.2 A /47…440 Hz or 110…300V DC/0.2 A
Power Supply
DC (optional) 20…60V DC @ 10 W
Auxiliary Voltage Input 1.0V AC/DC nominal full scale input (1.25V AC/DC maximum)
(VAUX) Overload withstand: 120V continuous, 1000V for 1 second Input Impedance: 10 kΩ
Auxiliary Current Output
0…20 mA output into 250 Ω maximum load
(,OUT)
Terminal Strip 1.35 Nm (12 lb•in) screw torque
Maximum Wire 4 mm2 (#12 AWG), 75 °C (167 °F) CU wire only
Operating Temperature 0…50 °C (32…122 °F)
Storage Temperature –30…70 °C (–22…158 °F)
Humidity 5…95% (without condensation)
Weight 3.2 kg (7.1 lb)

These specifications apply to the Powermonitor 1400-DCU communication card.

Input and Output Ratings


Screw Torque 0.56 Nm (5 lb•in)
Terminal Strip
Maximum Wire #14 AWG, 2.5 mm2, 75 °C (167 °F) CU wire only
Operating Temperature 0…50 °C (32…122 °F)
Storage Temperature –30…70 °C (–22…158 °F)
Humidity 5…95% (without condensation)
Isolation 500V rms
RS-232/RS-485 Communication Rate 300…19200 bit/s
y 57.6 k bit/s
Remote I/O Communication Rate y 115.2 k bit/s
y 230.4 k bit/s
Energy Class Class 2 Energy Limited
Weight 0.18 kg (0.4 lb)

7-8 Visit our website: www.ab.com/catalogs


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 11:07 Page 7-9

Bulletin Engineered Systems and Application Products


Power Monitoring
Product Selection

Powermonitor 3000 (1404 Series)


(1404-M4, M5, M6, and M8) — 120/240 Volt Power Supply (1404) — 120/240 Volt Power Supply Option✶
Option
Description Cat. No.
Description Cat. No. RS-485 (DF-1) 1404-M405A-000-02
Powermonitor 3000 Display Module 1404-DM RS-485 and RS-232 (DF-1) 1404-M405A-232-02
RS-485 (DF-1) 1404-M405A-000 RS-485 (DF-1) and DeviceNet 1404-M405A-DNT-02
RS-485 and RS-232 (DF-1) 1404-M405A-232 RS-485 (DF-1) and Remote I/O 1404-M405A-RIO-02
RS-485 (DF-1) and DeviceNet 1404-M405A-DNT RS-485 (DF-1) and Ethernet 1404-M405A-ENT-02
RS-485 (DF-1) and Remote I/O 1404-M405A-RIO RS-485 (DF-1) 1404-M505A-000-02
RS-485 (DF-1) and Ethernet 1404-M405A-ENT RS-485 and RS-232 (DF-1) 1404-M505A-232-02
RS-485 (DF-1) 1404-M505A-000 RS-485 (DF-1) and DeviceNet 1404-M505A-DNT-02
RS-485 and RS-232 (DF-1) 1404-M505A-232 RS-485 (DF-1) and Remote I/O 1404-M505A-RIO-02
RS-485 (DF-1) and DeviceNet 1404-M505A-DNT RS-485 (DF-1) and Ethernet 1404-M505A-ENT-02
RS-485 (DF-1) and Remote I/O 1404-M505A-RIO RS-485 (DF-1) 1404-M605A-000-02
RS-485 (DF-1) and Ethernet 1404-M505A-ENT RS-485 and RS-232 (DF-1) 1404-M605A-232-02
RS-485 (DF-1) 1404-M605A-000 RS-485 (DF-1) and DeviceNet 1404-M605A-DNT-02
RS-485 and RS-232 (DF-1) 1404-M605A-232 RS-485 (DF-1) and Remote I/O 1404-M605A-RIO-02
RS-485 (DF-1) and DeviceNet 1404-M605A-DNT RS-485 (DF-1) and Ethernet 1404-M605A-ENT-02
RS-485 (DF-1) and Remote I/O 1404-M605A-RIO RS-485 (DF-1) 1404-M805A-000-02
RS-485 (DF-1) and Ethernet 1404-M605A-ENT RS-485 and RS-232 (DF-1) 1404-M805A-232-02
RS-485 (DF-1) 1404-M805A-000 RS-485 (DF-1) and DeviceNet 1404-M805A-DNT-02
RS-485 and RS-232 (DF-1) 1404-M805A-232 RS-485 (DF-1) and Remote I/O 1404-M805A-RIO-02
RS-485 (DF-1) and DeviceNet 1404-M805A-DNT RS-485 (DF-1) and Ethernet 1404-M805A-ENT-02
RS-485 (DF-1) and Remote I/O 1404-M805A-RIO
RS-485 (DF-1) and Ethernet 1404-M805A-ENT
(1404) — 24 Volt Power Supply Option✶
Description Cat. No.
(1404-M4, M5, M6, and M8) — 24 Volt Power Supply
RS-485 (DF-1) 1404-M405B-000-02
Option
RS-485 and RS-232 (DF-1) 1404-M405B-232-02
Description Cat. No. RS-485 (DF-1) and DeviceNet 1404-M405B-DNT-02
Powermonitor 3000 Display Module 1404-DM RS-485 (DF-1) and Remote I/O 1404-M405B-RIO-02
RS-485 (DF-1) 1404-M405B-000 RS-485 (DF-1) and Ethernet 1404-M405B-ENT-02
RS-485 and RS-232 (DF-1) 1404-M405B-232 RS-485 (DF-1) 1404-M505B-000-02
RS-485 (DF-1) and DeviceNet 1404-M405B-DNT RS-485 and RS-232 (DF-1) 1404-M505B-232-02
RS-485 (DF-1) and Remote I/O 1404-M405B-RIO RS-485 (DF-1) and DeviceNet 1404-M505B-DNT-02
RS-485 (DF-1) and Ethernet 1404-M405B-ENT RS-485 (DF-1) and Remote I/O 1404-M505B-RIO-02
RS-485 (DF-1) 1404-M505B-000 RS-485 (DF-1) and Ethernet 1404-M505B-ENT-02
RS-485 and RS-232 (DF-1) 1404-M505B-232 RS-485 (DF-1) 1404-M605B-000-02
RS-485 (DF-1) and DeviceNet 1404-M505B-DNT RS-485 and RS-232 (DF-1) 1404-M605B-232-02
RS-485 (DF-1) and Remote I/O 1404-M505B-RIO RS-485 (DF-1) and DeviceNet 1404-M605B-DNT-02
RS-485 (DF-1) and Ethernet 1404-M505B-ENT RS-485 (DF-1) and Remote I/O 1404-M605B-RIO-02
RS-485 (DF-1) 1404-M605B-000 RS-485 (DF-1) and Ethernet 1404-M605B-ENT-02
RS-485 and RS-232 (DF-1) 1404-M605B-232 RS-485 (DF-1) 1404-M805B-000-02
RS-485 (DF-1) and DeviceNet 1404-M605B-DNT RS-485 and RS-232 (DF-1) 1404-M805B-232-02
RS-485 (DF-1) and Remote I/O 1404-M605B-RIO RS-485 (DF-1) and DeviceNet 1404-M805B-DNT-02
RS-485 (DF-1) and Ethernet 1404-M605B-ENT RS-485 (DF-1) and Remote I/O 1404-M805B-RIO-02
RS-485 (DF-1) 1404-M805B-000 RS-485 (DF-1) and Ethernet 1404-M805B-ENT-02
RS-485 and RS-232 (DF-1) 1404-M805B-232 ✶ Revenue metering compliance to ANSI C12.20 and EN 60687 Class 0.2
RS-485 (DF-1) and DeviceNet 1404-M805B-DNT Accuracy
RS-485 (DF-1) and Remote I/O 1404-M805B-RIO
RS-485 (DF-1) and Ethernet 1404-M805B-ENT Field Upgrade Kits†
Description Cat. No.
M5 to M6 Field Upgrade 40863-600-51
M6 to M8 Field Upgrade 40863-600-52
M5 to M8 Field Upgrade 40863-600-53
† When a device model is upgraded to an M6 or M8, the device will support
the new model functionality but retains the accuracy class of the original
manufactured device.

Visit our website: www.ab.com/catalogs 7-9


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 11:08 Page 7-10

Bulletin Engineered Systems and Application Products


Power Monitoring
Product Selection, Continued

Powermonitor Display Module


Description
Measured Measured
Current Voltage
A Full Scale L-N L-L Power Supply Cat. No.
85…240V AC or 110…300V DC 1400-PD11A
120V 208V
20…60V DC 1400-PD11B
85…240V AC or 110…300V DC 1400-PD12A
1 277V 480V
20…60V DC 1400-PD12B
85…240V AC or 110…300V DC 1400-PD13A
347V 600V
20…60V DC 1400-PD13B
85…240V AC or 110…300V DC 1400-PD51A
120V 208V
20…60V DC 1400-PD51B
85…240V AC or 110…300V DC 1400-PD52A
5 277V 480V
20…60V DC 1400-PD52B
85…240V AC or 110…300V DC 1400-PD53A
347V 600V
20…60V DC 1400-PD53B

Bulletin 1803-PPM
Description Cat. No.
Portable Powermonitor 3000 M8 with Ethernet
1803-PPM8E
Communication Card (Includes Display Module)
Portable Powermonitor 3000 Display Module 1803-PDM

Starter Kit (1803-SKCT)


Description Cat. No.
PEMS starter kit, 400:5 CT’s:
3 - 400:5 Split-core CT’s
1 - 8 pt. Shorting Terminal Block 1803-SKCT4
1 - 3-pole Fuse Holder w/10 A Fuses

PEMS starter kit, 1200:5 CT’s:


3 - 1200:5 Split-core CT’s
1 - 8 pt. Shorting Terminal Block 1803-SKCT12
1 - 3-pole Fuse Holder w/10 A Fuses

PEMS starter kit, 2000:5 CT’s:


3 - 2000:5 Split-core CT’s
1 - 8 pt. Shorting Terminal Block 1803-SKCT20
1 - 3-pole Fuse Holder w/10 A Fuses

7-10 Visit our website: www.ab.com/catalogs


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 11:08 Page 7-11

Bulletin Engineered Systems and Application Products


Power Monitoring
Product Selection, Continued

Powermonitor II Products
Powermonitor II Master Module (Full Metering)
Measured Current
A Full Scale Measured Voltage Power Supply Cat. No.
5 120/240V AC 50/60 Hz or 125/250V DC 1403-MM05A
5 120…347VL-N 24V AC 50/60 Hz or 24/48V DC 1403-MM05B
1 (208…600Vc) 120/240V AC 50/60 Hz or 125/250V DC 1403-MM01A
1 24V AC 50/60 Hz or 24/48V DC 1403-MM01B

Powermonitor II Master Module (Limited Metering)


Measured Current
A Full Scale Measured Voltage Power Supply Cat. No.
5 120/240V AC 50/60 Hz or 125/250V DC 1403-LM05A
5 120…347VL-N 24V AC 50/60 Hz or 24/48V DC 1403-LM05B
1 (208…600Vc) 120/240V AC 50/60 Hz or 125/250V DC 1403-LM01A
1 24V AC 50/60 Hz or 24/48V DC 1403-LM01B

Powermonitor II Display Module


Description Cat. No.
120/240V AC 50/60 Hz or 125/250V DC 1403-DMA
12/24V AC 50/60 Hz or 12/240/48V DC 1403-DMA

Powermonitor II Communication Cards


Description Cat. No.
Smart Communication Card 1403-NSC
Ethernet Communication Card 1403-NENET
DeviceNet Communication Card 1403-NDNET

MiniPowermonitor M610 and M620


Description Cat. No.
MiniPowermonitor M610 1405-M610
MiniPowermonitor M620 1405-M620

Ethernet Energy Module (1803-EEM)


Description Description Cat. No.
10 16 Pulses, 24V DC sinking 1803-EEM10E12
20 32 Pulses, 24V DC sinking 1803-EEM20E12
30 48 Pulses, 24V DC sinking 1803-EEM30E12
1 8 Analog, 4…30 mA 1803-EEM01E12
2 16 Analog, 4…30 mA 1803-EEM02E12
3 24 Analog, 4…30 mA 1803-EEM03E12
11 16 Pulses, 24V DC Sinking and 8 Analog, 4…20 mA 1803-EEM11E12
12 16 Pulses, 24V DC Sinking and 16 Analog, 4…20 mA 1803-EEM12E12
21 32 Pulses, 24V DC Sinking and 8 Analog, 4…20 mA 1803-EEM21E12

Bulletin 9307 RSEnergyMetrix


Description Cat. No.
RSEnergyMetrix Manager (0…8 meters) 9307-EM8MGRENE
RSEnergyMetrix Manager (9…64 meters) 9307-EM64MGRENE
RSEnergyMetrix Manager (65…10 000 meters) 9307-EM10KMGRENE
RSEnergyMetrix Real Time 9307-EMRTENE
RSEnergyMetrix 3rd Part OPC Client Connectivity (0…8 meters) 9307-EM83PXENE
RSEnergyMetrix 3rd Part OPC Client Connectivity (9…64 meters) 9307-EM643PXENE
RSEnergyMetrix 3rd Part OPC Client Connectivity (65…10 000 meters) 9307-EM10K3PXENE
RSEnergyMetrix ReportsPlus 9307-EMRPTENE
RSEnergyMetrix ChartsPlus 9307-EMCHTENE

Visit our website: www.ab.com/catalogs 7-11


Bulletin_Engineered_Systems_and_Application_Products.qxd 14/01/2004 11:08 Page 7-12

Bulletin Engineered Systems and Application Products


Power Monitoring
Product Selection, Continued/Accessories

Powermonitor II Master Module


Description
Measured Current
Type of Device A Full Scale Measured Voltage Power Supply Cat. No.
120/240V AC 50/60 Hz or
1 120…600V 1403-MM01A
125/250V DC
24V AC 50/60 Hz or
1 120…600V 1403-MM01B
24V/48V DC

120/240V AC 50/60 Hz or
5 120…600V 1403-MM05A
125/250V DC

Powermonitor II Master Module 24V AC 50/60 Hz or


5 120…600V 1403-MM05B
Cat. No. 1403-MM05A 24V/48V DC

Powermonitor II Display Module


Description Cat. No.
120/240V AC 50/60 Hz
or 1403-DMA
125/250V DC

12/24V AC 50/60 Hz
or 1403-DMB
12/240/48V DC
Powermonitor II Display Module
Cat. No. 1403-DM

Accessories
Powermonitor II
Description Cat. No.
Smart Communication Card 1403-NSC
2 x 25 cm F Link 1403-CF000
2 x 1 m F Link 1403-CF001
2 x 3 m F Link 1403-CF003
2 x 5 m F Link 1403-CF005
10 m F Link 1403-CF010
20 m F Link 1403-CF020
50 m F Link 1403-CF050

1803-PPM
Description Cat. No.
Current Transformer with 3000/2000/100:5 ratio, 4 in x 3/4 in window size 1803-CT3000M
Current Transformer with 1000/500/250.5:5 ratio, 2 in diameter window size 1803-CT1000M
Current Transformer with 600/300/150.5:5 ratio, 2 in diameter window size 1803-CT600M
Current Transformer with 400/200/100.5:5 ratio, 2 in diameter window size 1803-CT400M

7-12 Visit our website: www.ab.com/catalogs