Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
• MachineAlert Relays Page 3-2
Bulletin 1409
Arcing Ground Fault Detection System
• Adjustable Trip from 1…6 A Page 3-13
Bulletin 1410
Motor Winding Heater
• Automatic Operation
• Solid-State Design Page 3-16
Phase Monitors
Bulletin 813S
• Line Voltage and Current Monitor Relays Web/CD
NOTE: Information for this product line is available on the Industrial
Controls Catalog CD-ROM (pub. no. A115-CA002A-EN-C) or on the
Industrial Controls Catalog web site www.ab.com/catalogs.
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Product Overview
Προδυχτ Οϖερϖιεω
Description
Electronic Design Easy to Use
y Microprocessor technology provides highly accurate and y Compact size saves valuable panel space
repeatable protection y LCD / keypad programming takes the guesswork out of device
y Built-in LCD and keypad afford a precise, digital setting set-up
y Wide adjustment ranges allow for application flexibility y DIN rail mounting makes installation a snap
y Password protection hinders unauthorized programming access y Terminals provide IP20 finger safety protection and are clearly
y Compact 22.5 mm and 45 mm packaging marked
y Global application with CE and cULus approvals y LCD display provides relay status indication
Enhanced Protection
y Current monitors that provide the added benefits of under- and
overcurrent detection
y Phase monitors that guard against the damaging effects of phase
loss, under- and overvoltage, phase imbalance, and phase reversal
y Thermistor monitors that protect equipment from overtemperature
conditions
y Motor rotation monitors that signal motor rotational status
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Product Family Overview/Product Selection
Current Transformers
Use only with Cat Nos. 809S-E1, 809S-E3.
Trip Current Range Maximum Current
Continuous AC Amperes (A)
(5 A Secondary Winding) Continuous Inrush Cat. No.
4.2…50 75 350 809S-CT1
17…200 300 1400 809S-CT2
42…500 750 3500 809S-CT3
100…1200 1800 8400 809S-CT4
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Specifications
Specifications
Programmable Settings Bulletin 817 PTC Sensor Characteristics
Recommended Type of control unit Mark A
Setting Adjustment Range Sensor Characteristic per IEC 34-11-2
809S-E1 Maximum number of sensors 6
Actuation Value, Current 0.5…5.0 A Maximum cold resistance of PTC
1500 Ω
Release Value, Current 0.5…5.0 A sensor chain
Actuation Value, Voltage 1.0…24.9V/10…249V Trip resistance 3600 Ω (±300 Ω)
Release Value, Voltage 1.0…24.9V/10…249V Reset resistance 1580 Ω (±60 Ω)
Delay 0.0…24.9 s Short circuit trip resistance <20 Ω (–5 Ω, +0 Ω)
809S-E2 Short circuit reset resistance 24 Ω (–0 Ω, +6 Ω)
Actuation Value 2.0…15.0 A Open circuit resistance >18000 Ω
Release Value 2.0…15.0 A Bulletin 817 Power/Trip Idendification
Delay, Relay Energize 0.0…24.9 s Power on Green
Delay, Relay De-energize 0.0…24.9 s Trip Overtemperature Red
809S-E3 Trip open circuit (Sensor) Red 2 Hz
% Imbalance Level 5…25% Trip short circuit (sensor) Red “flashes”
Delay, Relay Energize 0.0…24.9 s Bulletin 817 Measuring and Reset Lines
Delay, Relay De-energize 0.0…24.9 s Up to 200 parallel or twisted;
813S-E2 Measuring Line >200 m shielded,
Overvoltage Level (E2B/E2C) 150…500V AC/250…700V AC shield connected with T1
Minimum Cross Section (mm2) 0.5 0.75 1 1.5
Undervoltage Level (E2B/E2C) 150…500V AC/250…700V AC
Maximum Line length (m) 200 300 400 600
% Imbalance Level 5…19%
Delay, Relay Energize 0.0…24.9 s Max 600 m;
Up to 200 parallel or twisted;
Delay, Relay De-energize 0.0…24.9 s Remote reset
>200 m shielded,
819-E1 shield connected with r1
Actuation Value, Voltage 1.0…24.9V AC
Release Value, Voltage 1.0…24.9V AC
Bulletin 817 Relay Configuration
Actuation Value, Frequency 10…249 Hz
817-E1 817-E2
Release Value, Frequency 10…249 Hz
Delay 0.0…24.9 s
819-E2
Actuation Value, Voltage 1.0…24.9V AC
Release Value, Voltage 1.0…24.9V AC
Delay, Relay Energize 0.0…24.9 s
Delay, Relay De-energize 0.0…24.9 s
Normal
Tripped
Power Off
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Specifications, Continued
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Specifications, Continued
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Approximate Dimensions
Αππροξιµατε ∆ιµενσιονσ
Dimensions shown are in millimeters (inches) Dimensions are not intended for manufacturing purposes.
809S-E1, 819-E1
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Approximate Dimensions, Continued
Dimensions shown are in millimeters (inches) Dimensions are not intended for manufacturing purposes.
817-E1, 817-E2
Current Transformers
A
Cat. No. Min. B C D E F
809S-CT1 32 102 117 95.5 32 6.4
809S-CT2 (1-1/4) (4) (4-5/8) (3-3/4) (1-1/4) (1/4)
57 149 181 127 38 7.1
809S-CT3
(2-1/4) (5-7/8) (7-1/8) (5) (1-1/2) (9/32)
95.5 171 198 165 41.5 7.1
809S-CT4
(3-3/4) (6-3/4) (7-25/32) (6-1/2) (1-5/8) (9/32)
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams
Φυνχτιον ανδ Ωιρινγ ∆ιαγραµσ
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams
Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams
Bulletin 1409
Arcing Ground Fault Detection System
Overview/Product Selection
Your order must include the cat. no. of the arching ground fault relays and sensor selected.
Low-level (arcing) ground faults are below the fuse or circuit breaker rating and therefore go undetected until a much larger problem develops.
The Allen-Bradley Arcing Ground Fault Detection System is designed to sense these low-level faults and either drop out the motor controller
or operate a shunt-trip circuit breaker to clear the fault.
Product Selection
Arcing Ground Fault Relays — Class II with High Current Inhibit Feature
Maximum Maximum High Current Inhibit (A)
NEMA Starter Size Voltage (V) AC Hp Full Load Current (A) Min. Max. Cat. No.
200…230 7.5 27 114 144 1409-BOAD
1 460 10 14 63 79 1409-BOBD
575 10 11 50 62 1409-BOCD
200…230 15 45 189 239 1409-COAD
2 460 25 34 153 193 1409-COBD
575 25 27 122 153 1409-COCD
200…230 30 90 360 456 1409-DOAD
3 460 50 65 293 370 1409-DOBD
575 50 52 234 296 1409-DOCD
200…230 50 135 585 741 1409-EOAD
4 460 100 124 558 706 1409-EOBD
575 100 99 446 564 1409-EOCD
200…230 100 270 1116 1413 1409-FOAD
5 460 200 240 1080 1368 1409-FOBD
575 200 192 864 1094 1409-FOCD
200…230 200 540 2160 2736 1409-GOAD
6 460 400 465 2147 2718 1409-GOBD
575 400 372 1719 2177 1409-GOCD
Arcing Ground Fault Relays — Class I without High Current Inhibit Feature
Application Max. Line Voltage (V) Cat. No.
Shunt-Trip Circuit Breaker 600
1409-MV
Medium Voltage Controller 7200
Note: Interrupting capacity is determined by starter or circuit breaker selection.
Bulletin 1409
Arcing Ground Fault Detection System
Specifications/Typical Wiring Diagrams
Specifications
Response Time 50 ms nominal plus the controller drop-out time
Supply Voltage 120V AC, 60 Hz
Power Input 3VA
Temperature Range The operating ambient temperature range for the sensor is –40…+85 °C (–40…+184 °F) and for the relay is 0…+65 °C (32…149 °F)
Output Contact Rating Make 30 A; Break 3 A; Continuous carrying current 5 A at 120V
Bulletin 1409
Arcing Ground Fault Detection System
Approximate Dimensions
Αππροξιµατε ∆ιµενσιονσ
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Cat. No. A B C D E F G H J K
92.6 88.9 104 74 67.3 56.4 92.9 39.6
1409-N1 — —
(3-21/32) (3-1/2) (4-3/32) (2-15/16) (2-21/32) (2-7/32) (3-21/32) (1-9/16)
91.4 115.8 131.8 77 88.9 88.9 120.6 63.5 69.8 54.9
1409-N2
(3-19/32) (4-9/16) (5-3/16) (3-1/32) (3-1/2) (3-1/2) (4-3/4) (2-1/2) (2-3/4) (2-5/32)
73.2 144 157.2 54.9 96.8 119.4 146.1 82.6
1409-N3 — —
(2-7/8) (5-11/16) (6-3/16) (2-5/32) (3-13/16) (4-23/32) (5-3/4) (3-1/4)
77.2 169.9 182.6 59.5 123.7 138.2 171.5 108
1409-N4 — —
(3-1/32) (6-11/16) (7-3/16) (2-11/32) (4-7/8) (5-7/16) (6-3/4) (4-1/4)
Bulletin 1410
Motor Winding Heater
Overview/Product Selection/Connection Diagram/Specifications
Your order must include the cat. no. of the motor winding heater selected.
Product Selection✶ Specifications
3-Phase Motor Voltage, Voltage applied to motor winding will vary
+10%, -5%, 60 Hz 3-Phase Hp Rating Cat. No. Output Voltage Regulation ±5% maximum for line voltage variations of
230 15…50 1410-EOA47 +10%, –15%.
460 25…100 1410-EOB50 Ambient Operating 0…50 °C (32…122 °F)
575 25…100 1410-EOC50 Temperature Range Storage –25…+85 °C (–13…+184 °F)
230 50…100 1410-FOA50 Metal oxide varistor protects against
Additional SCR Protection voltage surges. RC snubber circuit limits
460 100…200 1410-FOB54
rate of change of circuit voltage.
575 100…200 1410-FOC54
True RMS Output Current Approximately 15% of full load current.
230 100…200 1410-GOA54
Power Delivered to the Motor Approximately 1 to 3 W/Hp.
460 200…400 1410-GOB59
575 200…400 1410-GOC59
Approximate Dimensions
230 200…300 1410-HOA57
Dimensions are shown in millimeters (inches). Dimensions are not
460 400…600 1410-HOB62 intended to be used for manufacturing purposes
575 400…600 1410-HOC62
✶ For applications requiring different horsepower, kilowatt, and voltage ranges
from those listed, consult your local Allen-Bradley distributor.
Connection Diagram
See Applicable Codes and Laws.
Cat. No. A B C
1410-EOA47
146.1 88.9 114.3
1410-EOB50
(5-3/4) (3-1/2) (4-1/2)
1410-EOC50
1410-FOA50
204.8 108 177.8
1410-FOB54
(8-1/16) (4-1/4) (7)
1410-FOC54
1410-GOA54
238.1 146.1 206.4
1410-GOB59
(9-3/8) (5-3/4) (8-1/8)
1410-GOC59
1410-HOA57
279.4 244.5 207.2
1410-HOB62
(11) (9-5/8) (8-5/32)
1410-HOC62