You are on page 1of 16

Table_of_Contents_Tab03.

qxd 28/01/2004 11:41 Page 3-1

Supplemental Motor Protection Devices


Section Overview

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
• MachineAlert Relays Page 3-2

Bulletin 1409
Arcing Ground Fault Detection System
• Adjustable Trip from 1…6 A Page 3-13

Bulletin 1410
Motor Winding Heater
• Automatic Operation
• Solid-State Design Page 3-16

Phase Monitors
Bulletin 813S
• Line Voltage and Current Monitor Relays Web/CD
NOTE: Information for this product line is available on the Industrial
Controls Catalog CD-ROM (pub. no. A115-CA002A-EN-C) or on the
Industrial Controls Catalog web site www.ab.com/catalogs.

Thermistor Protection Relay


Bulletin 817
• For Critical Applications
• Automatic, Manual, and Remote Reset Web/CD
NOTE: Information for this product line is available on the Industrial
Controls Catalog CD-ROM (pub. no. A115-CA002A-EN-C) or on the
Industrial Controls Catalog web site www.ab.com/catalogs.

SMM™ Smart Motor Manager


Bulletin 825
• 0.5…2000 A Current Range Web/CD

NOTE: Information for this product line is available on the Industrial


Controls Catalog CD-ROM (pub. no. A115-CA002A-EN-C) or on the
Industrial Controls Catalog web site www.ab.com/catalogs.

Visit our website: www.ab.com/catalogs 3-1


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-2

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Product Overview

MachineAlert Relays Table of Contents


The MachineAlert Relays family of dedicated function electronic motor
protection relays offers state-of-the-art supplementary protective Product Overview . . . this page
functions that are easily added and applied to motor control circuits. Product Selection . . . 3-3
MachineAlert Relays are an economical choice for protecting Specifications . . . . . . . 3-4
equipment investments and minimizing production downtime. To meet Approximate
specific application requirements, a full range of products allows Dimensions . . . . . . . . . 3-7
selective addition of protective enhancing functions for both motors
and equipment. Standards Compliance
y Current Monitors IEC EN 60255-6
y Phase Monitors CSA 22.2 No.14
y Thermistor Monitors UL 508
y Rotation Monitors
Approvals
CE
cULus Listed

Προδυχτ Οϖερϖιεω

Description
Electronic Design Easy to Use
y Microprocessor technology provides highly accurate and y Compact size saves valuable panel space
repeatable protection y LCD / keypad programming takes the guesswork out of device
y Built-in LCD and keypad afford a precise, digital setting set-up
y Wide adjustment ranges allow for application flexibility y DIN rail mounting makes installation a snap
y Password protection hinders unauthorized programming access y Terminals provide IP20 finger safety protection and are clearly
y Compact 22.5 mm and 45 mm packaging marked
y Global application with CE and cULus approvals y LCD display provides relay status indication

Enhanced Protection
y Current monitors that provide the added benefits of under- and
overcurrent detection
y Phase monitors that guard against the damaging effects of phase
loss, under- and overvoltage, phase imbalance, and phase reversal
y Thermistor monitors that protect equipment from overtemperature
conditions
y Motor rotation monitors that signal motor rotational status

Features Typical Applications


y Three versions available
Bulletin 809S
y Programmable relay trip and reset level settings y Conveyors
Current Monitors
y Programmable relay trip and reset delay settings y Cutting and drilling machines
y undercurrent, overcurrent, current
y Automatic reset y Pumps
imbalance, phase loss, phase
y Three-phase version includes current imbalance and phase loss and phase y Mixers
sequence
sequence monitoring
y Independent programmable trip settings for undervoltage, overvoltage, and
phase imbalance
Bulletin 813S y Pumps
y Programmable relay trip and reset delay settings
Phase Monitors y Fans
y RMS voltage monitoring up-to 690V AC
y phase loss, under/overvoltage, y Blowers
y Pre-start as well as running protection
phase imbalance, phase sequence y Compressors
y Automatic reset
y (1) N.O. and (1) changeover contact
y Two versions available
y Connection of up-to six PTC thermistors in series y VFD Controlled Motors
Bulletin 817
y Open and short circuit detection y Transformers
Thermistor Monitors
y Short circuit protected signal input y Bearings
y overtemperature
y Automatic, manual and remote reset options available y Heating systems
y Status indication LEDs
y Zero speed monitoring through evaluation of the feedback voltage of a
decelerating motor
y Conveyors
Bulletin 819 y Standstill monitoring by means of a pulse generator, tachometer, etc.
y Centrifuges
Motor Rotation Monitors y Frequency monitoring for signals of any curve form in the range of
y Band saws
y zero speed detection 16…100Vp-p
y Grinders
y Programmable relay trip and reset settings
y Programmable time delay settings

3-2 Visit our website: www.ab.com/catalogs


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-3

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Product Family Overview/Product Selection

Product Family Overview


Bulletin 813S
Bulletin 809S Phase Bulletin 817 Bulletin 819
Current Monitors Monitors Thermistor Monitors Motor Rotation Monitors
Features✶ E1 E2 E3 E2 E1 E2 E1 E2
Under- and overcurrent
S S — — — — — —
protection
Under- and overvoltage
S — — S — — — —
protection
Phase imbalance and phase current voltage
— — — — — —
loss protection based based
Phase sequence protection — — S S — — — —
Overtemperature protection — — — — S S — —
Speed detection via frequency
— — — — — — S
input
Speed detection evaluation of
— — — — — — S S
motor feedback voltage
0.5…5 A 0.5…5 A IEC 400V AC IEC 690V AC
500V AC
Operating Range 1.0…24.9V 2.0…15.0 A (3-phase) — — CSA/UL 300V CSA/UL 600V
or 690V AC
10…249V (AC only) AC AC
Case size (mm) 22.5 45 45 45 22.5 22.5 22.5 45
LCD / keypad S S S S — — S S
LED Status Indicator — — — — S S — —
Automatic reset S S S S S O S S
Manual reset — — — — — O — —
Remote reset — — — — — O — —
Changeover contacts (SPDT) 1 1 1 1 — — — 1
2 2
N.O. contacts — 1 1 1 2 1
(independent) (independent)
No setting required — — — — S S — —
Programmable trip level, reset
S S S S — — S S
level and time delay settings
Trip cause identification — — — S S S — —
Measuring Circuit Monitoring
— — — — S S S S
(open, short)
✶ S= Standard
O= Option
Product Selection
Motor Protection Relay Type Description Cat. No.
0.5…5 A AC/DC (1-phase), 2.0…24.9V or 20…249V AC/DC 50/60 Hz 809S-E1⊗
Bulletin 809S Current Monitors 2.0…15 A AC/DC (1-phase) 809S-E2⊗✪
0.5…5 A AC (3-phase) 809S-E3⊗✪
Monitoring Range 150…500V AC 813S-E2B⊗✪
Bulletin 813S Phase Monitors
Monitoring Range 250…690V AC 813S-E2C⊗✪
Automatic Reset ✶ 817-E1
Bulletin 817 Thermistor Monitors
Automatic, manual or remote reset ✶ 817-E2
Max. Monitored Voltage 400V AC max (IEC), 300V AC max (CSA/UL) 819-E1⊗
Bulletin 819 Motor Speed Monitors
Max. Monitored Voltage 690V AC max (IEC), 600V AC max (CSA/UL) 819-E2⊗
✶ Rated supply voltage of 24…240 V AC/DC.

⊗ Supply Voltage Suffix Code ✪ Frequency Code


The Cat. No. as listed is incomplete. Select a Supply Voltage Suffix The Cat. No. as listed is incomplete. Select a Frequency Code from
Code from the table below to complete the Cat. No. the table below to complete the Cat. No.
Example: Cat. No. 809S-E1⊗ becomes 809S-E1D. Example: Cat. No. 813S-E2BD✪ becomes 813S-E2BD60.
Voltage Rating 24V DC 115V AC 230V AC Frequency Rating 50 Hz 60 Hz
ZJ D A 50 60

Current Transformers
Use only with Cat Nos. 809S-E1, 809S-E3.
Trip Current Range Maximum Current
Continuous AC Amperes (A)
(5 A Secondary Winding) Continuous Inrush Cat. No.
4.2…50 75 350 809S-CT1
17…200 300 1400 809S-CT2
42…500 750 3500 809S-CT3
100…1200 1800 8400 809S-CT4

Visit our website: www.ab.com/catalogs 3-3


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-4

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Specifications

Specifications
Programmable Settings Bulletin 817 PTC Sensor Characteristics
Recommended Type of control unit Mark A
Setting Adjustment Range Sensor Characteristic per IEC 34-11-2
809S-E1 Maximum number of sensors 6
Actuation Value, Current 0.5…5.0 A Maximum cold resistance of PTC
1500 Ω
Release Value, Current 0.5…5.0 A sensor chain
Actuation Value, Voltage 1.0…24.9V/10…249V Trip resistance 3600 Ω (±300 Ω)
Release Value, Voltage 1.0…24.9V/10…249V Reset resistance 1580 Ω (±60 Ω)
Delay 0.0…24.9 s Short circuit trip resistance <20 Ω (–5 Ω, +0 Ω)
809S-E2 Short circuit reset resistance 24 Ω (–0 Ω, +6 Ω)
Actuation Value 2.0…15.0 A Open circuit resistance >18000 Ω
Release Value 2.0…15.0 A Bulletin 817 Power/Trip Idendification
Delay, Relay Energize 0.0…24.9 s Power on Green
Delay, Relay De-energize 0.0…24.9 s Trip Overtemperature Red
809S-E3 Trip open circuit (Sensor) Red 2 Hz
% Imbalance Level 5…25% Trip short circuit (sensor) Red “flashes”
Delay, Relay Energize 0.0…24.9 s Bulletin 817 Measuring and Reset Lines
Delay, Relay De-energize 0.0…24.9 s Up to 200 parallel or twisted;
813S-E2 Measuring Line >200 m shielded,
Overvoltage Level (E2B/E2C) 150…500V AC/250…700V AC shield connected with T1
Minimum Cross Section (mm2) 0.5 0.75 1 1.5
Undervoltage Level (E2B/E2C) 150…500V AC/250…700V AC
Maximum Line length (m) 200 300 400 600
% Imbalance Level 5…19%
Delay, Relay Energize 0.0…24.9 s Max 600 m;
Up to 200 parallel or twisted;
Delay, Relay De-energize 0.0…24.9 s Remote reset
>200 m shielded,
819-E1 shield connected with r1
Actuation Value, Voltage 1.0…24.9V AC
Release Value, Voltage 1.0…24.9V AC
Bulletin 817 Relay Configuration
Actuation Value, Frequency 10…249 Hz
817-E1 817-E2
Release Value, Frequency 10…249 Hz
Delay 0.0…24.9 s
819-E2
Actuation Value, Voltage 1.0…24.9V AC
Release Value, Voltage 1.0…24.9V AC
Delay, Relay Energize 0.0…24.9 s
Delay, Relay De-energize 0.0…24.9 s
Normal

Tripped

Power Off

3-4 Visit our website: www.ab.com/catalogs


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-5

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Specifications, Continued

Dedicated Function Relays, 809S-E1 to 813S-E2


Dedicated Function Relays
809S-E1 809S-E2 809S-E3 813S-E2
ELECTRICAL
Main
Rated Insulation Voltage (Ui) 250V AC 690V AC 690V AC 690V AC
IEC: 250V AC IEC: 690V AC IEC: 690V AC IEC: 690V AC
Rated Operating Voltage (Ue)
CSA/UL: 250V AC CSA/UL: 600V AC CSA/UL: 600V AC CSA/UL: 600V AC
0.5...5 A AC/DC
E2B: 500V
Measurement Range 1…24.9V 1...15 A AC/DC 0.5...5 A AC
E2C: 690V
10...249V AC/DC
Accuracy ±5% ±5% ±5% ±5%
Number of Phases 1 1 3 3
Supply
24V DC 24V DC 24V DC 24V DC
Rated Supply Voltage (Us) 115V AC, 115V AC, 115V AC, 115V AC,
230V AC 230V AC 230V AC 230V AC
AC: 0.8…1.1 Us AC: 0.8…1.1 Us AC: 0.8…1.1 Us AC: 0.8…1.1 Us
Operating Range
DC: 0.85…1.1 Us DC: 0.85…1.1 Us DC: 0.85…1.1 Us DC: 0.85…1.1 Us
Maximum Power Consumption 1 VA 2 VA 2 VA 2 VA
Output Relay
(1) Form A (1) Form A (1) Form A
Type of Contacts (1) Form C
(1) Form C (1) Form C (1) Form C
5 A @ 250V AC 5 A @ 250V AC 5 A @ 250V AC 5 A @ 250V AC
Rated Operating Current
4 A @ 24V DC 4 A @ 24V DC 4 A @ 24V DC 4 A @ 24V DC
Utilization Category AC1, DC1 AC1, DC1 AC1, DC1 AC1, DC1
MECHANICAL
Environmental
(storage) –20C…+80 °C –20C…+80 °C –20C…+80 °C –20C…+80 °C
Ambient Temperature
(operating) –5C…+60 °C –5C…+60 °C –5C…+60 °C –5C…+60 °C
5…95% 5…95% 5…95% 5…95%
Humidity
non-condensing non-condensing non-condensing non-condensing
Maximum Altitude 2000 m 2000 m 2000 m 2000 m
Pollution Environment Pollution Degree 2 Pollution Degree 2 Pollution Degree 2 Pollution Degree 2
Degree of Protection IP20 IP20 IP20 IP20
Terminal Cross-Sections
Terminal Screws M3 M3 M3 M3
0.2…2.5 mm2 0.2…2.5 mm2 0.2…2.5 mm2 0.2…2.5 mm2
Conductor Size
26…14 AWG 22…12 AWG 22…12 AWG 22…12 AWG

Visit our website: www.ab.com/catalogs 3-5


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-6

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Specifications, Continued

Dedicated Function Relays, 817-E1 to 819-E2


Dedicated Function Relays
817-E1 817-E2 819-E1 819-E2
ELECTRICAL
Main
Rated Insulation Voltage (Ui) 250V AC 250V AC 400V AC 690V AC
IEC: 250V AC IEC: 250V AC IEC: 400V AC IEC: 690V AC
Rated Operating Voltage (Ue)
CSA/UL: 250V AC CSA/UL: 250V AC CSA/UL: 300V AC CSA/UL: 600V AC
Freq: 10…249 Hz
Measurement Range — — (16…100Vpp) Back-EMF: 1.0…24.9V
Back-EMF: 1.0…24.9V
Accuracy — — ±5% ±5%
Number of Phases — — 1 1
Supply
Rated Supply Voltage (Us) 4A 4A 4A 5A
AC: 0.8…1.1 Us AC: 0.8…1.1 Us
Operating Range 0.8…1.1 Us 0.8…1.1 Us
DC: 0.85…1.1 Us DC: 0.85…1.1 Us
Maximum Power Consumption 1.5 VA 1.5 VA 1 VA 2 VA
Output Relay
(2) Form A (2) Form A (2) Form A (1) Form A
Type of Contacts
dependent independent independent (1) Form C
3 A @ 120V AC 3 A @ 120V AC 5 A @ 250V AC 5 A @ 250V AC
Rated Operating Current
1.5 A @ 240V AC 1.5 A @ 240V AC 4 A @ 24V DC 4 A @ 24V DC
Utilization Category AC15, DC13 AC15, DC13 AC1, DC1 AC1, DC1
MECHANICAL
Environmental
(storage) –40…+80 °C –40…+80 °C –20…+80 °C –20…+80 °C
Ambient Temperature
(operating) –25…+60 °C –25…+60 °C –5…+60 °C –5…+60 °C
5…95% 5…95% 5…95% 5…95%
Humidity
non-condensing non-condensing non-condensing non-condensing
Maximum Altitude 2000 m 2000 m 2000 m 2000 m
Pollution Environment Pollution Degree 2 Pollution Degree 2 Pollution Degree 2 Pollution Degree 2
Degree of Protection IP20 IP20 IP20 IP20
Terminal Cross-Sections
Terminal Screws M3 M3
0.5…2.5 mm2 0.5…2.5 mm2 0.2…2.5 mm2 0.2…2.5 mm2
Conductor Size
20…12 AWG 20…12 AWG 26…14 AWG 22…12 AWG

3-6 Visit our website: www.ab.com/catalogs


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-7

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Approximate Dimensions
Αππροξιµατε ∆ιµενσιονσ

Dimensions shown are in millimeters (inches) Dimensions are not intended for manufacturing purposes.

809S-E1, 819-E1

809S-E2, 809S-E3, 813S-E2, 819-E2

Visit our website: www.ab.com/catalogs 3-7


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-8

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Approximate Dimensions, Continued

Dimensions shown are in millimeters (inches) Dimensions are not intended for manufacturing purposes.

817-E1, 817-E2

Current Transformers

A
Cat. No. Min. B C D E F
809S-CT1 32 102 117 95.5 32 6.4
809S-CT2 (1-1/4) (4) (4-5/8) (3-3/4) (1-1/4) (1/4)
57 149 181 127 38 7.1
809S-CT3
(2-1/4) (5-7/8) (7-1/8) (5) (1-1/2) (9/32)
95.5 171 198 165 41.5 7.1
809S-CT4
(3-3/4) (6-3/4) (7-25/32) (6-1/2) (1-5/8) (9/32)

3-8 Visit our website: www.ab.com/catalogs


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-9

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams
Φυνχτιον ανδ Ωιρινγ ∆ιαγραµσ

809S-E1 Wiring Diagram 809S-E1 Function Diagram

819-E1 Wiring Diagram 819-E1 Function Diagram

Visit our website: www.ab.com/catalogs 3-9


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-10

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams

809S-E2 Wiring Diagram 809S-E2 Function Diagram

819-E2 Wiring Diagram 819-E2 Function Diagram

3-10 Visit our website: www.ab.com/catalogs


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:54 Page 3-11

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams

813S-E2 Wiring Diagram

813S-E2 Function Diagram

Visit our website: www.ab.com/catalogs 3-11


Bulletin_809S_813S_817_819.qxd 28/01/2004 11:55 Page 3-12

Bulletin 809S/813S/817/819
Dedicated Function Motor Protection Relays
Function and Wiring Diagrams

809S-E3 Wiring Diagram

809S-E3 Function Diagram

3-12 Visit our website: www.ab.com/catalogs


Bulletin_1409.qxd 28/01/2004 12:14 Page 3-13

Bulletin 1409
Arcing Ground Fault Detection System
Overview/Product Selection

Bulletin 1409 — Arcing Ground Fault Detection System Table of Contents


y Adjustable Trip from 1…6 A for Maximum Sensitivity without
Nuisance Tripping Specifications . . . . . . . 3-14
y Output Form C Contact (Single-Pole Double-Throw) for Application Typical Wiring
Flexibility Diagrams . . . . . . . . . . . 3-14
y Time Delay of 50 ms Nominal to Minimize Nuisance Tripping and Approximate
Allow Time for High Current Inhibit Dimensions . . . . . . . . . 3-15
Arcing Ground Fault Relay y Test Circuit is Built In to Test System for Proper Operation Approvals
Cat. No. 1409-DOBD The Bulletin 1409 Arcing Ground Fault Detection Systems are intended for equipment protection CSA Certified
only. These systems are not Ground-Fault Circuit-Interrupters for personnel protection as
defined in Article 100 of the U.S. National Electric Code. UL Listed (File E53935, Guide
Bulletin 1409 is available in two designs, Class I and Class II. The Class I systems are intended KDAX)
for use with shunt-trip circuit breakers or medium voltage controllers. These Class I systems do
not contain a high-current inhibit circuit.
The Class II Systems are designed for use with motor starters or contactors to interrupt low-level
ground faults. They incorporate a high-current inhibit circuit that guards against the controller
opening when the fault current exceeds the controller interrupting capacity. Ground fault currents
exceeding the interrupting rating of the controllers are designed to be cleared by the short circuit
protection device (fuse or circuit breaker).
Both Class I and Class II Systems consist of two parts — a relay and a sensor. The relay contains
Arcing Ground Fault Sensor all the detection, adjustment and output circuitry. The sensor is a special two-winding current
Cat. No. 1409-N2 transformer. Operation of the ground fault detection system is indicated by the relay toggle.

Your order must include the cat. no. of the arching ground fault relays and sensor selected.
Low-level (arcing) ground faults are below the fuse or circuit breaker rating and therefore go undetected until a much larger problem develops.
The Allen-Bradley Arcing Ground Fault Detection System is designed to sense these low-level faults and either drop out the motor controller
or operate a shunt-trip circuit breaker to clear the fault.
Product Selection
Arcing Ground Fault Relays — Class II with High Current Inhibit Feature
Maximum Maximum High Current Inhibit (A)
NEMA Starter Size Voltage (V) AC Hp Full Load Current (A) Min. Max. Cat. No.
200…230 7.5 27 114 144 1409-BOAD
1 460 10 14 63 79 1409-BOBD
575 10 11 50 62 1409-BOCD
200…230 15 45 189 239 1409-COAD
2 460 25 34 153 193 1409-COBD
575 25 27 122 153 1409-COCD
200…230 30 90 360 456 1409-DOAD
3 460 50 65 293 370 1409-DOBD
575 50 52 234 296 1409-DOCD
200…230 50 135 585 741 1409-EOAD
4 460 100 124 558 706 1409-EOBD
575 100 99 446 564 1409-EOCD
200…230 100 270 1116 1413 1409-FOAD
5 460 200 240 1080 1368 1409-FOBD
575 200 192 864 1094 1409-FOCD
200…230 200 540 2160 2736 1409-GOAD
6 460 400 465 2147 2718 1409-GOBD
575 400 372 1719 2177 1409-GOCD

Arcing Ground Fault Sensors


Max. Recommended Cable SizeMaximum Recommended
NEMA Starter Size Cable Size✶ Window Diameter Cat. No.
1…2 2 AWG @ 600V AC 1-9/16 in. 1409-N1
250 MCM @ 600V AC
3…4 4/0 @ 5000V AC 2-1/2 in. 1409-N2
4/0 @ 8000V AC†
500 MCM @ 600V AC
5 350 MCM @ 5000V AC 3-1/4 in. 1409-N3
350 MCM @ 8000V AC†
2-500 MCM @ 600V AC
6 500 MCM @ 5000V AC 4-1/4 in. 1409-N4
500 MCM @ 8000V AC†
✶ For a 3-phase system with one cable per phase except as indicated.
† 8000V cable — select sensor to have a window diameter greater than 2.5 times the cable diameter.

Arcing Ground Fault Relays — Class I without High Current Inhibit Feature
Application Max. Line Voltage (V) Cat. No.
Shunt-Trip Circuit Breaker 600
1409-MV
Medium Voltage Controller 7200
Note: Interrupting capacity is determined by starter or circuit breaker selection.

Visit our website: www.ab.com/catalogs 3-13


Bulletin_1409.qxd 28/01/2004 12:15 Page 3-14

Bulletin 1409
Arcing Ground Fault Detection System
Specifications/Typical Wiring Diagrams

Specifications
Response Time 50 ms nominal plus the controller drop-out time
Supply Voltage 120V AC, 60 Hz
Power Input 3VA
Temperature Range The operating ambient temperature range for the sensor is –40…+85 °C (–40…+184 °F) and for the relay is 0…+65 °C (32…149 °F)
Output Contact Rating Make 30 A; Break 3 A; Continuous carrying current 5 A at 120V

Typical Wiring Diagrams


See Applicable Codes and Laws.

Class II with High Current Inhibit Circuit✶

Class I without High Current Inhibit Circuit✶

✶ Wiring diagrams are shown in the tripped condition.

3-14 Visit our website: www.ab.com/catalogs


Bulletin_1409.qxd 28/01/2004 12:15 Page 3-15

Bulletin 1409
Arcing Ground Fault Detection System
Approximate Dimensions
Αππροξιµατε ∆ιµενσιονσ

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Arcing Ground Fault Relay

Arcing Ground Fault Sensors

Cat. No. 1409-N1: 12.7 (1/2) x 7.1 dia. (9/32)


Cat. No. 1409-N2: 12.7 (1/2) x 11.1 dia. (7/16)

Cat. No. 1409-N3


Cat. No. 1409-N4

Cat. No. A B C D E F G H J K
92.6 88.9 104 74 67.3 56.4 92.9 39.6
1409-N1 — —
(3-21/32) (3-1/2) (4-3/32) (2-15/16) (2-21/32) (2-7/32) (3-21/32) (1-9/16)
91.4 115.8 131.8 77 88.9 88.9 120.6 63.5 69.8 54.9
1409-N2
(3-19/32) (4-9/16) (5-3/16) (3-1/32) (3-1/2) (3-1/2) (4-3/4) (2-1/2) (2-3/4) (2-5/32)
73.2 144 157.2 54.9 96.8 119.4 146.1 82.6
1409-N3 — —
(2-7/8) (5-11/16) (6-3/16) (2-5/32) (3-13/16) (4-23/32) (5-3/4) (3-1/4)
77.2 169.9 182.6 59.5 123.7 138.2 171.5 108
1409-N4 — —
(3-1/32) (6-11/16) (7-3/16) (2-11/32) (4-7/8) (5-7/16) (6-3/4) (4-1/4)

Visit our website: www.ab.com/catalogs 3-15


Bulletin_1410.qxd 28/01/2004 12:23 Page 3-16

Bulletin 1410
Motor Winding Heater
Overview/Product Selection/Connection Diagram/Specifications

Bulletin 1410 — Motor Winding Heater Approvals


y Solid-State Design CSA Certified
y Automatic Operation UL Listed (File E56639, Guide
y No Adjustments Required NMTR)
Bulletin 1410 Motor Winding Heater is intended for use with 3-phase
AC motors to guard against damage caused by condensation build-up
on motor windings, which can occur in high-humidity environments
during motor off times. This device is not intended to be used to
dry out damp motors.
Bulletin 1410 Motor Winding Heater is designed for used with 3-phase
AC squirrel-cage motors controlled by automatic full-voltage starters.
For applications involving reduced-voltage starters, multi-speed
starters, synchronous motors, or the used of power factor correction
capacitors, consult your local Allen-Bradley Distributor or Sales Office.
Motor Winding Heater

Your order must include the cat. no. of the motor winding heater selected.
Product Selection✶ Specifications
3-Phase Motor Voltage, Voltage applied to motor winding will vary
+10%, -5%, 60 Hz 3-Phase Hp Rating Cat. No. Output Voltage Regulation ±5% maximum for line voltage variations of
230 15…50 1410-EOA47 +10%, –15%.
460 25…100 1410-EOB50 Ambient Operating 0…50 °C (32…122 °F)
575 25…100 1410-EOC50 Temperature Range Storage –25…+85 °C (–13…+184 °F)
230 50…100 1410-FOA50 Metal oxide varistor protects against
Additional SCR Protection voltage surges. RC snubber circuit limits
460 100…200 1410-FOB54
rate of change of circuit voltage.
575 100…200 1410-FOC54
True RMS Output Current Approximately 15% of full load current.
230 100…200 1410-GOA54
Power Delivered to the Motor Approximately 1 to 3 W/Hp.
460 200…400 1410-GOB59
575 200…400 1410-GOC59
Approximate Dimensions
230 200…300 1410-HOA57
Dimensions are shown in millimeters (inches). Dimensions are not
460 400…600 1410-HOB62 intended to be used for manufacturing purposes
575 400…600 1410-HOC62
✶ For applications requiring different horsepower, kilowatt, and voltage ranges
from those listed, consult your local Allen-Bradley distributor.

Connection Diagram
See Applicable Codes and Laws.

Cat. No. A B C
1410-EOA47
146.1 88.9 114.3
1410-EOB50
(5-3/4) (3-1/2) (4-1/2)
1410-EOC50
1410-FOA50
204.8 108 177.8
1410-FOB54
(8-1/16) (4-1/4) (7)
1410-FOC54
1410-GOA54
238.1 146.1 206.4
1410-GOB59
(9-3/8) (5-3/4) (8-1/8)
1410-GOC59
1410-HOA57
279.4 244.5 207.2
1410-HOB62
(11) (9-5/8) (8-5/32)
1410-HOC62

3-16 Visit our website: www.ab.com/catalogs

You might also like