You are on page 1of 66

FX NET & INTELLIA

Product Catalog
Fire detection products and equipments

Schneider Fire Detection

Fire Safety systems are a critical part of any business.


Schneider Electric Buildings Business offer intelligent,
innovative fire detection products that are user-
friendly, modular, flexible, scalable and highly reliable.

Schneider Electric invests heavily in product


development. In fire protection the focus is on the
development of intelligent technologies which ensures
uninterrupted operation of your business and safety
of personnel and buildings.
FX NET - Advanced fire protection 5
FX NET panels 6
Protocol repeater 14
ZLPX Zone LED Panel 15
ZLPX Option Boards 16
Cabinets and Frames 18
Control unit 22
Controllers and adapters 23
Power supplies 26
Display Boards 27
CODINET Modem Adapter 28
Communication Modems 29
FX NET & INTELLIA features 30
Intellia Address setting 32
Detectors 33
Intrinsically Safe Fire Products 42
Remote indicators 43
Call points and sounders 44
Beacon 46
Bases 47
Base sounders 50
Input/Output modules 53
Integration 64
04

Products and Equipments for


Fire Detection
Schneider Electric
knowhow is recognised
You are looking at our new FX NET & INTELLIA around the world; fire
product catalog 2011. detection systems
certified in accordance
with standard EN 54 are
The catalogue presents all FX NET and Intellia products
used in 20 European
with pictures. Overviews of all the relevant product data are countries.
provided in the technical information tables. At the bottom
of the table you can find the product order code.

We hope that you find this catalogue helpful. Schneider Electric is a


member of Euralarm,
an association of
European manufacturers
and installers of fire
and security systems,
and participates
also in international
standardisation work.

FX NET
05
3

FX NET
Advanced fire protection
FX Net Fire Detection System from Schneider is a reliable
tool to protect people and assets due to fire and offers
many advantages over other fire alarm systems, such as
user-friendliness and adaptability.

Modular and Scalable


The FX NET intelligent fire detection and alarm system and panels have
a modular construction and provide smart features for efficient and
reliable fire safety. The modular structure of FX NET and use of multipro-
cessor technology facilitates also to easy and cost-effective expansion
options. The user can activate only those parts of the system they really
need and expand it as the needs change. On the other hand, multipro-
cessor technology combined with a networked system structure offers
distributed functions, fast deduction capabilities and reliability.

Unique ease-of-use
The Fire Detection System supplied by Schneider can be easily installed
in accordance with the fire safety needs of buildings and customers
alike. Furthermore, FX NET Fire Detection System is also simple to oper-
ate. The user interface offers clear instructions according to the situa-
tion. In an FX NET control panel, conventional buttons are replaced with
a control wheel which makes function selection quick and easy.

A range of Security Solutions


Schneider’s Fire Detection system can be used independently or
as part of an integrated security system in which fire detection,
intruder- and access control and video monitoring are combined
in a single system,thereby improving in a cost-effective way the
fire safety and premises security.

FX NET
Control Panels of the FX NET Fire Detection System

The FX NET intelligent fire detection and alarm system and panels have a modular
construction and provide smart features for efficient and reliable fire safety.
The control panels are FX NET, FXL NET, FXM NET and FXS. The full range of
Schneider’s intelligent, as well as conventional detectors can be connected to the system.

FXS

Modern slim panel with networking interface that


befits any building entrance

FX NET fire detection


system
- 32 fire alarm panels
- 255 adressable loops
FXM - 8.000 fire zones
- Max. 16.000 addresses

A powerful panel that can be standalone


or used as part of a networked system

FX FXL

Medium to large sites For large demanding installations


or be part of a network solution that require complicated controls

FX NET
Esgraf
Some additional features
- Integration
- Graphical user
interface
- Logical controller
- Repeater panel

FMPX

A user friendly graphical interface giving


easy access to safety and security
information

A fully functional fireman’s panel

MCOX

OPC-server

A powerful unit for programming of


logical functions

For easy integration to third


party systems

FX NET
08

FX NET
Intelligent Fire Detection Panel

The System FX intelligent fire detection and alarm


panels from Schneider have a modular construction
and provide new features for efficient and reliable
fire safety.
Panel construction
The base unit consists of
-1 Master Controller board (FX-MC)
-1 Power Supply board (FX-PS) and transformer
-1 User Interface board (FX-UI)
For adding serial communication
-1 Serial Adapter (FX-SAA, FX-SAB or FX-SAC)
For adding detection circuits
-1 – 4 Addressable Loop Controllers (FX-ALCA or FX-
ALCB) or Conventional Loop Controllers (FX-CLC)
For adding I/O circuits
-1 – 4 Input/Output Controllers (FX-IOC)
Batteries as needed
-2, 4, 6 or 8 pcs 12V/17Ah connected in series and
parallel for 24V/17, 34, 51 or 68 Ah
Space for 2x17 Ah batteries
Applied standard EN54-2, -4
Dimensions (h x w x d) 575 x 425 x 130
Weight excl. batteries 11 kg
Colour bluish gray
Ingress Protection class IP 30
Storage ambient temperature+ 0 … + 50°C
Operating ambient temp. + 5 … + 40°C
Max. relative humidity 95%
Operating voltage range 21 … 30Vdc
Max. standby current (@24V) 1.0 A
Max. alarm current (@24V) 4.0 A
Mains supply voltage 230Vac
Max. mains power 160 VA

Product order code 00703612xx

FX NET
09

FXL NET
Intelligent Fire Detection Panel

The System FX intelligent fire detection and alarm


panels from Schneider have a modular construc-
tion and provide new features for efficient and
reliable fire safety.

Panel construction
The base unit consists of
- 1 Master Controller board (FX-MC)
- 1 Power Supply board (FX-PS) and transformer
- 1 User Interface board (FX-UI)
For adding serial communication
- 1 Serial Adapter (FX-SAA, FX-SAB or FX-SAC)
For adding detection circuits
- 1 - 4 Addressable Loop Controllers (FX-ALCA or FX-
ALCB)
or Conventional Loop Controllers (FX-CLC)
For adding I/O circuits
- 1 - 4 Input/Output Controllers (FX-IOC)
Batteries as needed
- 2, 4, 6 or 8 pcs 12V/17Ah connected in series
and parallel for 24V/17, 34, 51 or 68 Ah
No space for batteries
Applied standard EN54-2, -4
Dimensions (h x w x d) 575 x 425 x 130
Weight excl. batteries 11 kg
Colour bluish gray
Ingress Protection class IP 30
Storage ambient temp. + 0 ... + 50°C
Operating ambient temp. + 5 ... + 40°C
Max. relative humidity 95%
Operating voltage range 21 ... 30Vdc
Max. standby current (@24V) 1.0 A
Max. alarm current (@24V) 4.0 A
Mains supply voltage 230Vac
Max. mains power 160 VA

Product order code 00703712xx

FX NET
10

FXM NET
Intelligent Fire Detection Panel

The System FX intelligent fire detection and alarm


panels from Schneider have a modular construc-
tion and provide new features for efficient and
reliable fire safety.

Panel construction
The base unit consists of
- 1 Master Controller board (FX-MC)
- 1 Power Supply board (FX-PS) and transformer
- 1 User Interface board (FX-UI)
For adding serial communication
- 1 Serial Adapter (FX-SAA , FX-SAB or FX-SAC)
For adding detection circuits
- 1 - 2 Addressable Loop Controllers (FX-ALCA or FX-
ALCB)or Conventional Loop Controllers (FX-CLC)
For adding I/O circuits
- 1 - 4 Input/Output Controllers (FX-IOC)
Batteries as needed
Total 2 card slots
Space for 2+ 12 Ah batteries

Applied standard EN54-2, -4


Dimensions (h x w x d) 328 x 425 x 130
Weight excl. batteries 6 kg
Colour bluish gray
Ingress Protection class IP 30
Storage ambient temp. + 0 ... + 50°C
Operating ambient temp. + 5 ... + 40°C
Max. relative humidity 95%
Operating voltage range 21 ... 30Vdc
Max. standby current (@24V) 0,5 A
Max. alarm current (@24V) 2,2 A
Mains supply voltage 230Vac
Max. mains power 80 VA

Product order code 00703822xx

FX NET
11

FXS NET
User Interface Panel

The System FX intelligent fire detection and alarm


panels from Schneider have a modular construction
and provide new features for efficient and reliable
fire safety.

Panel construction
The base unit consists of
- 1 Master Controller board (FX-MC)
- 1 User Interface board (FX-UI)
For adding serial communication
- 1 Serial Adapter (FX-SAA or FX-SAB)
For adding detection circuits
- 1 Addressable Loop Controller (FX-ALC) or
Conventional Loop Controller (FX-CLC)
or for adding I/O circuits
- 1 Input/Output Controller (FX-IOC)
Total number of FX-ALC, FX-CLC and FX-IOC is 1.
The panel needs power feed from an FX, FXL or
FXM panel.

Applied standard EN54-2, -4


Dimensions (h x w x d) 328 x 425 x 79
Weight 4,4 kg
Colour bluish gray
Ingress Protection class IP 30
Storage ambient temp. + 0 ... + 50°C
Operating ambient temp. + 5 ... + 40°C
Max. relative humidity 95%
Operating voltage range 21 ... 30Vdc
Current consumption, see note 100 ... 500 mA

Note! Current consumption depends on installed


boards and external devices. See planning guide
for details.

Product order code 00703810xx

FX NET
12

FMPX
Fireman’s Panel

The FMPX fireman’s panel is used by fire brigade as


a primary information source of the location of an
alarm in the building. The panel can function as a
pure display device or it can be used to silence and
reset the fire alarm. If there is a need to display zone/
area spefic fire alarm information only, then FMPX
panel must be configured. The FMPX can be con-
nected to the FX NET panels: FXS, FXM, FX and FXL.

Dimensions (W x H x D) 379 x 231 x 54 mm


Weight 2.3 kg
Colour Blue
(NCS S 4020-R80B)
Operating Temperature +5°C ... +40°C
Humidity max. RH 95%
Operating Voltage 19 ...30 VDC
Standby current 40 mA
Alarm state current 75 mA
Serial communication ports In: RS485 or RS232
Out: RS485
IP Rating IP30

Product order code 00703831xx

FX NET
13

DAPX
Alarm Panel

The DAPX Alarm Panel is used for handling of


delayed fire alarms. The product function has been
designed according to the Swedish standard. The main
function principle can be found on the data sheet
DO1639GB. The use of delayed alarms in a fire
detection system must be agreed always with local
fire authorities.

The DAPX panel shows "normal" fire alarms too but


does not allow any user operations except scrolling.
The delay alarm function is configured in the FX NET
panel.

Dimensions (W x H x D) 379 x 231 x 54 mm


Weight 2.3 kg
Colour Blue (NCS S 4020-R80B)
Operating Temperature +5°C ... +40°C
Humidity max. RH 95%
Operating Voltage 19 ...30 VDC
Standby current 40 mA
Alarm state current 75 mA
Serial communication ports
In: RS485 or RS232
Out: RS485
IP Rating IP30

Product order code 00703838xx

FX NET
14

Protocol Repeater
REPX
Protocol Repeater

The REPX protocol repeater duplicates the INFO serial


communication line.
in one system there can be at the most four REPX units
connected to one FX panel. REPX-OB, PCB version, can be
installed inside FX.

Dimensions (W x H x D) 379 x 231 x 54 mm


Weight 2.1 kg
Colour Blue (NCS S 4020-R80B)
Operating Temperature +5°C ... +40°C
Humidity max. RH 95%
Operating Voltage 19 ...30 VDC
Standby current 50 mA
Serial communication ports
In: RS485 or RS232
Out: RS485
IP Rating IP30

Product Order code


REPX, Panel version, wall mounting 0070 3832
REPX-OB,PCB version, card slot mounting 0070 3833

FX NET
15

Zone LED Panel


ZLPX
Zone LED Panel

The ZLPX zone LED panel is used by the fire bri-


gade as a primary information of the location of an
alarm in the building. The panel can function as a
pure display device showing zone-specific fire place.
The ZLPX can be connected to the FX NET panels:
FXS, FXM, FX and FXL.

Dimensions (W x H x D) 328 x 417 x 79 mm


Weight 5 kg
Colour Blue (NCS S 4020-R80B)
Operating Temperature +5°C ... +40°C
Humidity max. RH 95%
Operating Voltage 19 ...30 VDC
Standby current 50 mA
Alarm state current. 72 mA
Max. 50 LEDs "on" at the same time
Serial communication ports
In: RS485 or RS232
Out: RS485
IP Rating IP30

Product order code 00703840

FX NET
16

ZLPX Option Boards


There are several option boards to choose from and to build your own unique led panel.

System example: open collector LED outputs

System example: relay outputs

FX NET
17

System example: open collector LED outputs

Product Order code


ZLPX-IC,ZLPX controller 0070 3841


LB200,Led board 200 LEDs 0070 3842
OC-100L,Open collector output for 100 LEDs 0070 3843
OC-100R,Open collector output for 100 relays 0070 3844
CCLO,Connection cable for LED outputs, 3m 0070 3845
COL-10,10 LEDs cable, 1m 0070 3846
RB20,Relay board of 20 relays 0070 3847

FX NET
18

Cabinets and Frames


Cabinets and frames of the FX fire detection system

FXM-RMFW
Mounting frame

Feature FXM-RMFW
Dimensions 527 x 521 mm
Color White
Product order code 0070 2582

FX-RMFW
Mounting frame

Feature FX-RMFW
Dimension 527 x 765 mm
Weight 5,4 kg
Color White
Product code 0070 2577

FX NET
19

FXM-BAT
Battery Cabinet

Feature FXM-BAT
Dimensions 424 x 335 x 127 mm
Weight 3,7 kg
Battery space 4 x 12 Ah
Color NCS S5020-R80B

Product order code 0070 4605

AX/FX/IX-BAT
Battery Cabinet

Feature AX/FX/IX-BAT
Dimensions 424 x 578 x 127 mm
Weight 6,8 kg
Battery space 4 x 17 Ah
Color NCS S5020-R80B

Product code 0070 4600

FX NET
20

FXM-CAB
Mounting cabinet

Feature FXM-CAB
Dimensions 424 x 335 x 127 mm
Weight 3,3 kg
Color NCS S5020-R80B

Product order code 0070 4615

FX-CAB
Mounting cabinet

Feature FX-CAB
Dimensions 424 x 578 x 127 mm
Weight 6,5 kg
Color NCS S5020-R80B

Product order code 0070 4610

FX NET
21

FX-MAP
Chart cabinet

Feature FX-MAP
Dimensions 424 x 578 x 127 mm
Weight 8,9 kg
Color NCS S5020-R80B

Product order code 0070 5630

FX NET
22

Control units
MCOX
Control Unit

The MCOX control unit controls functions in the


FX NET fire detection system. The MCOX
communicates with the FX panel via the INFO serial
communication line. The logical functions of the MCOX
are configured with the MCO configuration tool. The MCOX
unit can control addressable outputs as well as control
panel outputs.

Dimensions (W x H x D) 379 x 231 x 54 mm


Weight 2.1 kg
Colour Blue (NCS S 4020-R80B)
Operating Temperature +5°C ... +40°C
Humidity max. RH 95%
Operating Voltage 19 ...30 VDC
Standby current 50 mA
Serial communication ports
In: RS485 or RS232
Out: RS485
IP Rating IP30

Product Order code


MCOPanel version, wall mounting 00703834
MCOX-OB PCB version, card slot mounting 00703835

FX NET
23

Controllers and adapters


FX-MC NET
Controller

Configurable RS-232 interface; configuration, printer


or sw update of MC, LC or ALC.
Optional add-on SAB(A) card with 3 configurable,
isolated RS-485 interfaces for INFO, MESA or
FX NET communication.

2 programmable relay outputs


2 programmable clean contact inputs
1 programmable, monitored alarm device output,
500mA, autofuse
24Vdc 500mA monitored output, autofuse
24Vdc input jumpers to set other functions

Product order code 00702551

FX-SAA, FX-SAB, FX-SAC


Serial Communication Adapters

FX-SAA has one RS485 one serial communication port


with galvanic isolation.
FX-SAB has two RS485 serial communication ports with
galvanic isolation.
FX-SAC has two RS485 serial communication ports with
galvanic isolation. Includes also an assistant proces-
sor for network communication and control of the zone
display unit (FX-LB32).

Dimensions 102x47x16 mm
Weight FX-SAA 52 g
FX-SAB 55 g
FX-SAC 59 g
Current consumption FX-SAA 18 mA
FX-SAB
FX-SAB and FX-SAC 36 mA
Panel connection MC board
Product Order code
FX-SAA 00702520
FX-SAB 00702521
FX-SAC 00702522

FX NET
24

FX-ALCA
Loop Controller

1 addressable loop for Intellia products.


126 addresses/loop.
1 x 24 Vdc 500mA monitored output.
Max. 60 ohm loop cable resistance.

Dimensions 160x135x18 mm
Weight 164 g
Current consumption 54 mA
Panel connection Bus board

Product order code 00702515

FX-ALCB
Loop Controller

2 addressable loop for Intellia products.


126 addresses/loop.
2 x 24 Vdc 500mA monitored output.
Max. 60 ohm loop cable resistance.

Dimensions 160x135x18 mm
Weight 179 g
Current consumption 78 mA
Panel connection Bus board

Product order code 00702517

FX NET
25

FX-CLC
Loop Controller

16 conventional loops.

Dimensions 160x135x33 mm
Weight 215 g
Current consumption 20 mA+
1.8 mA/line: 4k7 EOL
4.0mA/line: 2k94 EOL
15.6 mA/line:
normally closed input
Panel connection Bus board

Product order code 00702512

FX-IOC Input Output Controller


FX-OCA Output Controller

FX- IOC 4 clean contact inputs


2 clean contact outputs
4 alarm device line outputs
2x24Vdc 500mA monitored
output
FX- OCA 16 clean contact outputs.
Dimensions FX-IOC: 160x135x18 mm
FX-OCA: 160x135x33 mm
Weight FX-IOC: 174 g
FX-OCA: 232g
Current consumption FX-IOC: 20 mA
FX-OCA: 3 mA
Relays 30 Vdc 1.0A
FX- IOC Panel connection Bus board

Product Order code


FX-IOC 00702530
FX-OCA 00702531

FX NET
26

Power Supplies

FX-PSA
Power Supply

PSA is for FXM panel only.


24Vdc, max 2,2A.
Provides power to MC ,IOC, UI and LC via main bus.
2 x 24Vdc ext. output, max 2A / output, autofuse.
30Vac input from transformer; T3,15A fuse (5x20mm).
Battery connection; T6,3A fuse (5x20mm).
LEDs on 24 and 5Vdc, main bus communication
and CPU OK.
Temperature compensation.

Product order code 00702565

FX-PSB
Power Supply

PSB is for FX and FXL panels.


24Vdc, max 4,5A
Normally with max. configuration 1A to the system,
3,5A for battery charge.
Provides power to MC, IOC, UI and LC via main bus.
2 x 24Vdc ext. output, max 4A / output, autofuse.
30Vac input from transformer; T6,3A fuse (5x20mm).
Battery connection; T6,3A fuse (5x20mm).
LEDs on 24 and 5Vdc, main bus communication
and CPU OK.
Temperature compensation.

Product order code 00702560

FX NET
27

Display Boards for FX Panel

FX-LB32 and FX-LB80


Panel Display Unit

Feature FX-LB32
32 panel led indications to be used together
with FX-SAC

Product order code 00702541

Feature FX-LB80
80 zone led indications

Product code 00702542

FX NET
28

CODINET Modem Adapter

The CODINET modem adapter is used with a modem for long


distance serial communication. The distance between two local
modems can be typically 1 … 5 kilometres. The CODINET is de-
signed for the communication speed of 19200 baud and it is an
isolated adapter. The CODIS version is used for the speed of 9600
baud and is not isolated.

Dimensions (W x H x D) 75 x 100 x 30 mm
Weight 200 g
Colour White
Operating temperature +5°C … +40°C
Humidity max. 93%
Operating voltage 16...30 VDC
Current consumption 20 mA
Communication RS 485 / RS 232
Communication speed
CODINET 19200 baud
CODIS 9600 baud
IP Rating IP20

Product Order code


CODINET 00398001
CODIS 00398002

FX NET
29

Communication Modems
Communication modems are used together with the CODINET Modem Adapter
in FX fire detection and security systems. Available are both copper and fire cable models

Please check Data Sheet D01601/GB for more information.

Connection principle

FX NET
30

FX NET & INTELLIA Features

Response settings Remote test feature


Each detector in the Intellia range can operate in This feature, available on all Intellia detectors is
one of five response modes, any of which can be enabled from the FX by changing the state of a
selected with configuration software. Each mode forward command bit. On receipt of the command
corresponds to a unique response behaviour, the detector is forced by electrical means into an
which can be broadly related to sensitivity to fire. alarm condition. After a delay of approximately 10
Whatever the type of detector, Mode 1 will give a seconds due to signal processing, an analogue
higher sensitivity to fire than Mode 5. The selec- value between 54 and 120 - nominally 85 - is
tion of the most suitable mode depends on the returned, provided that the detector is functioning
application. correctly. This value is sustained until the forward
command bit is changed back to its original state,
For ionisation and optical smoke detectors, the after which a period of 40 seconds is required
modes relate to different combinations of smoke for the detector to return to its normal analogue
response threshold and response time. For value.
the heat detector, the mode relates to the fixed
temperature setting and the sensitivity to the Rejection of transient signals
rate-of-rise of temperature. For the multisensor, All Intellia detector algorithms are designed to
the mode relates to the levels of smoke and heat give low sensitivity to very rapid changes in the
sensitivity and to the way in which the responses sensor output, since these are unlikely to be
of the two sensors are combined. caused by real fire conditions. This is achieved by
digital low-pass filtering of sensor values which
The response characteristics of the detectors optimises the rejection of false alarm sources
have been carefully set so that detectors will while maintaining the response to fire. The filter
comply with the requirements of the relevant part parameters depend on the mode selected and for
of EN54 in all response modes. some modes the filtering is minimal. The filtering
has no significant effect on the response to fires
but does affect the way in which detectors re-
spond to transients and to step changes of smoke
or heat.

FX NET
31

Drift compensation Easy installation


All Intellia smoke detectors include compensation Detectors fit into the bases one way only, without
for sensor drift as part of the internal snagging, and require clockwise rotation without
signal-processing algorithm. The algorithm will push force to be plugged in.
compensate for changes in sensor output caused,
for example, by dust in the chamber, and will Universal patented address cards, are supplied
therefore hold the sensitivity at a constant level with all bases. Consult the coding guide in the
even with severe chamber contamination. This installation instructions to determine which pips
increased stability affects the detectors’s are to be removed from the card to give the cor-
sensitivity to fire. rect addresses.

For the Intellia smoke detectors, the compensa- The expert card gives the possibility to replace a
tion algorithms are designed so that the detectors detector in the system easily as the address is in
meet the requirements of the European standard the base and not in the detector. This is a highly
EN54-7:2000 in all response modes. appeciated feature.

The contamination level of any detector can be


verified from the panel at any time. FX panel will
give service warning in case detector
contamination reaches a level which can not be
compensated anymore.

FX NET
32

Intellia address setting


Address Cards

Address cards are supplied with all bases. Consult the


coding guide in the installation instructions to determine
which pips are to be removed from the card to give the
correct address.
Lay the card on a flat surface, pips down, insert a
screwdriver into the slot on the reverse of the pip to be
removed and give a firm twist.

When the card is coded insert it into the slot in the side
of the appropriate base, making sure that the card locks
itself into place. As a detector is inserted into the base,
the remaining pips operate the address buttons on the
detector and the detector electronics reads the address.

Product Order code

Single Address Card 06720019


Pre addressed Card set 1…63 06720016
Pre addressed Card set 64…126 06720017
Pre addressed Card set 0…126 06720018

FX NET
33

Detectors
EDI-20
Optical Smoke Detector

The Intellia optical smoke detector EDI-20 is suitable for slow


burning or smouldering fires and should be positioned where
these are most likely to occur. They can be set to a sensitivity
mode best suited for the application.

An infra-red light emitting scatters light from the diode within its
collimator is arranged at an obtuse angle to the photo-diode.
The photo-diode has an integral daylight-blocking filter.
The photo-diode signal is processed to provide an analogue
value for transmission when the detector is polled.

Operating voltage 17-28VDC


Optical Smoke Detector
Quiescent current 400 μA average
EDI-20
Remote output max. 5 mA
Alarm indicator 2 colourless light emitting diodes
(LEDs); illuminated red in alarm;
optional remote LED
Humidity 0 - 95% relative humidity
(no condensation or icing)
IP rating IP 43
Temperature range -20 - +60 °C
(no condensation or icing)
Storage temperature -30 - +80 °C
Dimensions (diameter) 100 mm
Height 42 mm
50 mm (height in base)
Weight 105 g
Materials
Housing White polycarbonate V-0 rated to UL94
Terminals Nickel plated stainless steel
Test EN54-7:2000

Product order code 0672 0220

FX NET
34

EDI-10
Ionisation Smoke Detector

The Intellia ionisation detector EDI-10 uses a low activity radioactive


foil to detect fires by irradiating the air in the smoke chambers and
causing a current flow. If smoke enters the chamber, the current
flow is reduced leading to an alarm. It is a good general purpose
detector that responds well to fast burning, flaming fires.
The ionisation chamber consists of a reference chamber contained
inside a smoke chamber. The outer smoke chamber has inlet
apertures fitted with insect resistant mesh.

The radioactive source holder and the smoke chamber form


positive and negative electrodes respectively. An Americium 241
radioactive source mounted within the reference chamber irradiates
Ionisation Smoke Detector
the air in both chambers, producing positive and negative ions.
EDI-10
The analogue voltage at the sensor electrode is converted to a
digital format which is processed to provide an analogue value for
transmission to the FX control panel when the device is polled.

Operating voltage 17-28VDC


Quiescent current 400 μA average
Remote output max. 5 mA
Alarm indicator 2 red light emitting diodes
(LEDs); optional remote LED
Humidity 0 - 95% relative humidity
(no condensation or icing)
IP rating IP 43
Temperature range -20 - +60 °C
(no condensation or icing)
Storage temperature -30 - +80 °C
Dimensions (diameter) 100 mm
Height 42 mm
50 mm (height in base)
Weight 105 g
Materials
Housing White polycarbonate V-0 rated to UL94
Terminals Nickel plated stainless steel
Test EN54-7:2000

Product order code 0672 0210

FX NET
35

EDI-50
Heat Detector

The Intellia heat detector EDI-50, distinguishable by the low


airflow resistant case, uses a single thermistor to sense the air
temperature around the detector. This type of detector is
particularly useful where the environment is dirty or smoky
under normal conditions. For more information on the application
of these detectors, please see the chart below.
The Intellia heat detector uses a single thermistor to sense the
air temperature at the detector position.
The design of the resistor detector, together with the processing
algorithm in the microcontroller, gives an approximately linear
characteristic from 10°C to 80°C. This linearised signal is further
processed, depending on the response mode selected.
Heat Detector
The five modes correspond to five "classes" as defined in
EDI-50
EN54-5:2000.

Operating voltage 17-28VDC


Quiescent current 500 μA average
Remote output max. 5 mA
Alarm indicator 2 light emitting diodes
(LEDs); illuminated red in alarm;
optional remote LED
Humidity 0 - 95% relative humidity
(no condensation or icing)
IP rating IP 43
Temperature range -20 - +60 °C
(no condensation or icing)
Storage temperature -30 - +80 °C
Dimensions (diameter) 100 mm
Height 42 mm
50 mm (height in base)
Weight 105 g
Materials
Housing White polycarbonate V-0 rated to UL94
Terminals Nickel plated stainless steel
Test EN54-5:2000

Product order code 0672 0250

FX NET
36

EDI-30
Multisensor Detector

The Intellia multisensor detector EDI-30 comprises optical smoke and


thermistor temperature sensors whose outputs are combined to give
the final analogue value. As a result, the multisensor is useful over a
wide range of applications and is highly immune to false alarms.
The way in which the signals from the two sensors are combined
depends on the response mode selected. The five modes provide
response behaviour which incorporates pure heat detection, pure smoke
detection and a combination of both. The multisensor is
therefore useful over the widest range of applications.
Mode 5 has no smoke sensitivity at all, but gives a pure heat detector
response. If the multisensor is used in mode 5, heat detector spacing
and coverage should be applied.
Multisensor Detector
The signals from the optical smoke sensing element and the temperature
EDI-30 sensor are independent, and represent the smoke level and the air tem-
perature respectively in the vicinity of the detector.

Operating voltage 17-28VDC


Quiescent current 500 μA average
Remote output max. 5 mA
Alarm indicator 2 colourless light emitting diodes
(LEDs); illuminated red in alarm;
optional remote LED
Humidity 0 - 95% relative humidity
(no condensation or icing)
IP rating IP 43
Temperature range -20 - +60 °C
(no condensation or icing)
Storage temperature -30 - +80 °C
Dimensions (diameter) 100 mm
Height 50 mm
58 mm (height in base)
Weight 105 g
Materials
Housing White polycarbonate V-0 rated to UL94
Terminals Nickel plated stainless steel
Test EN54-7; EN54-5:2000

Product order code 0672 0230

FX NET
37

EDI-60
Carbon Monoxide Detector

Intellia CO fire detector EDI-60 contains a long-life electrochemical


carbon monoxide sensor which is tolerant of low levels
of common vapours and household products. The sensing
technology is fast, accurate and needs only very low power.
These factors make the CO sensor suitable for fire detection
applications.

Typical applications include hotel bedrooms, halls of residence,


sheltered accommodation and hospital wards.
The Intellia series of products are all compatible with the ALC-board
of an FX-panel.

Carbon Monoxide
Detector EDI-60
Operating voltage 17-28VDC
Quiescent current 500 μA average
Remote output max. 5 mA
Alarm indicator 2 light emitting diodes
(LEDs); optional remote LED
Humidity 15 - 95% relative humidity
IP rating IP 43
Temperature range 0 - +60 °C (continuous)
(operating)
Storage temperature -10 - +50 °C (continuous)
Dimensions (diameter) 100 mm
Height 42 mm
50 mm (height in base)
Weight 105 g
Materials
Housing White polycarbonate V-0 rated to UL94
Terminals Nickel plated stainless steel

Product order code 0672 0260

FX NET
38

Dual IR, UV, UV/Dual IR and Triple


Flame Detectors
The Intellia base mounted Flame Detectors are designed to protect areas where open fires may be
expected. The Intellia series of products are all compatible with the ALC-board of an FX-panel.

Dual IR
Flame Detector

Operating voltage 17-28VDC


Quiescent current 2.2 mA
Remote LED current Limited to 2 mA
Range of view (EN54-10) 0.1 m2 n-heptan (25 m)
0.2 m2 n-heptan (35 m)
0.4 m2 n-heptan (45 m)
Field of view 90° cone
Spectral response 1.0 to 2.7μm
Sensitivity High-Class 1
Low-Class 3
IP rating IP 65
Operating temperature -10 - +55 °C
Storage temperature -20 - +65 °C
The Intellia Dual IR Flame Detector is sensitive Relative humidity 95% (no condensation)
to low-frequency, flickering infra-red radiation
Weight 1 kg
emitted by flames during combustion.
Housing material die-cast zinc alloy
Product order code 0672 5280

UV
Flame Detector
Operating voltage 17–28 VDC
Quiescent current 2,3 mA
Alarm Current 4,2mA
Max. Remote output current through 4,5kΩ 5mA
Field of view 90° Cone
Operating Range 0.1m2 n-heptane at 25m
Spectral response UV 185 to 260 nm
Sensitivity Class 1 or 3, EN54-10
IP Rating IP66
Operating temp. –40°C to +70°C (no condensing or icing)
Storage temp. –40°C to +85°C
Relative humidity (no condensation) 95 %
Dimensions 100 mm x 40 mm (Detector only)
100 mm x 48 mm (Detector and base)
The detector has a single UV sensor with a Weight Detector 150 g
narrow spectral response in order to Detector and base 210 g
discriminate between flames and most Housing material White Polycarbonate, V-0 rated to UL94
spurious sources of radiation. Sensing window 2 mm Quartz
Terminals Nickel plated stainless steel
Product order code 06725283

FX NET
39

UV/Dual IR
Flame Detector

Operating voltage 17–28 VDC


Quiescent current 2,8 mA
Alarm Current 4,2mA
Max. Remote output current through 4,5kΩ 5mA
Field of view 90° Cone
Operating Range 0.1m2 n-heptane at 25m
Spectral response UV 185 to 260 nm, IR 0,75 to 2,7 μm
Sensitivity Class 1 or 3, EN54-10
IP Rating IP66
Operating temperature –40°C to +70°C (no condensing or icing)
Storage temperature –40°C to +70°C
Relative humidity (no condensation) 95 %
Dimensions 100 mm x 40 mm (Detector only)
The detector has a UV and dual IR sensors
100 mm x 48 mm (Detector and base) responding to different wavelengths in order
Weight Detector 150 g to discriminate between flames and spurious
Detector and base 210 g sources of radiation.
Housing material White Polycarbonate, V-0 rated to UL94
Sensing window 2 mm Quartz
Terminals Nickel plated stainless steel
Product order code 06725284

Triple IR
Flame Detector

Operating voltage 17–28 VDC


Quiescent current 2,5 mA
Alarm Current 4,2mA
Max. Remote output current through 4,5kΩ 5mA
Field of view 90° Cone
Operating Range 0.1m2 n-heptane at 25m
Spectral response 0,75 to 2,7 μm
Sensitivity Class 1 or 3, EN54-10
IP Rating IP66
Operating temperature –40°C to +70°C (no condensing or icing)
Storage temperature –40°C to +70°C
Relative humidity (no condensation) 95 %
Dimensions 100 mm x 40 mm (Detector only)
The detector has three IR sensors that re-
100 mm x 48 mm (Detector and base) spond to different IR wavelengths in order to
Weight Detector 150 g discriminate between flames and spurious
Detector and base 210 g sources of radiation. .
Housing material White Polycarbonate, V-0 rated to UL94
Sensing window 2 mm Float Glass
Terminals Nickel plated stainless steel
Product order code 06725285

FX NET
40

Beam Detectors
The Auto-Aligning Beam Detector is a compact detector for detecting smoke in large open areas such as
warehouses, theatres, churches and sports centres.It comprises of a ground level Controller, a Detector
Head with an operating range of 8m-50m and a single prism.One controller can operate up to a maximum
of four separate detector heads.

Product Dimensions w*h*d Weight

Controller with base 202*230*81mm 1000g


Detector with base 135*135*135mm 500g
Universal bracket 135*135*71mm 200g
Reflector 100*100*10mm 100g

Product Order code

29600-524, Auto-Aligning Beam Detector 5-80m 0672 5273


29600-525, Additional Detector Head 8-50m 0672 5274
Auto- aligning beam detector 29600-526, Extension Kit 100m 0672 5275
and controller
29600-527, Universal Bracket 0672 5276
(for use with detector head and prism mounting plates)
29600-528, Surface Mounting Plate for prisms 0672 5277
29600-529, Prism Mounting Plate (4 prisms 50-100m) 0672 5278
29600-530, Prism Mounting Plate (1 prism 8-100m) 0672 5279

Connection of Auto-aligning Beam Detector to FX-ALC addressable loop.

FX NET
41

Duct Smoke Detectors


EBI-50
Duct Detector

The Intellia Duct Smoke Detector provides early


detection of smoke in the air moving through heat-
ing and ventilation (HVAC) ducts in commercial and
industrial premises. Its purpose is to prevent the
recirculation of smoke from an area on fire to areas
unaffected by the fire.
Duct smoke detector EBI-50 is designed to accept a
intelligent detector head.
The Intellia series of products are all compatible with
the ALC-board of an FX-pane

Dimensions 343 x 114 x 64 mm


Weight 1,13 kg
Operating temperature 0-70 °C
Humidity (no condensation) 10-80% RH
IP Rating IP20

Product Order code


EBI-50 Duct Detector Housing 0672 0050

Tubes:
53541-170APO, 150 - 750mm 0672 0051
53541-171APO, 750 - 1500mm 0672 0052
53541-172APO, 1500 – 3000 mm 0672 0053

Suitable detectors:
EDI-20 Optical Smoke detector 0672 0220

Electrical installation
The duct smoke detector is supplied as a housing with a base fitted for Intellia detectors. We recommend
to use Intellia optical smoke detector EDI-20 with EBI-50 Duct Detector Housing.

FX NET
42

Intrinsically Safe Fire Products


The Intellia I.S. range comprises addressable ionisation and optical smoke detectors, a temperature de-
tector, a detector base and a compatible manual call point. There is also a choice of two translators which
ensure integrity of communication between detectors and control equipment within the constraints of an
intrinsically safe system.

The Intellia range intrinsically safe fire detectors and call


points have been approved by BASEEFA. The approv-
als are to BS EN 60079-0:2004, BS EN 50284:1999, BS EN
50020:2002 and BS EN 60079-26:2004. All types are certi-
fied to EEx ia IIC T5 at ambient temperatures up to 40 °C,
or T4 at ambient temperatures up to 60 °C.

Product Order code

Optical Smoke Detector 55000-640 APO 0672 5227


Ionisation Smoke detector 55000-540 APO 0672 5217
Intellia I.S. Optical Smoke Detector Heat Detectors 55000-440 APO 0672 5257
Mounting Base 45681-215 APO 0672 5207
Manual Call Points 55000-940 0672 3737

Protocol Translators:
55000-855 (single channel) 0672 5201
55000-856 (dual channel) 0672 5202

Galvanic Isolator 29600-098APO 0672 5203

DIN-RAIL Modules Enclosures:


29600-239APO (standard DIN-Rail 4) 0672 7460
29600-240APO (standard DIN-Rail 10) 0672 7461

FX NET
43

Remote indicators
NLY-91200
Remote Indicator

The NLY-91200 Remote indicator is used to indicate


detector alarm state in installations where the detec-
tor is not visible.

Max Operating voltage Connectors (-1 and +4) 27V


Connectors (-1 and +3) 12V
Max current 12 mA
Dimensions (mm)
L x W x H 87 x 43 x 30
Weight 34 g
Colour White
Material Plastic
IP Rating IP20
Product order code 0043 1200

ERI-10 MiniDisc
Remote Indicator

The MiniDisc Remote indicator is a light-weight, com-


pact indicator for use in fire protection systems. The
indicator may be used in all installations as a remote
indicator to a detector. MiniDisc is connected to the
base.

Voltage, A & C 5-36V


Max current, B & C 25 mA,up to 40 °C
Operating temperature -10 °C to +60 °C

Product order code 0672 0601

FX NET
44

Call points and sounders


EPP-20
Call Point

Addressable call point EPP-20 is used in the


addressable ESMI FX fire detection system.
The Intellia series of products are all compatible with the ALCboard
of an FX-panel.
EPP-20 call point has in-built isolation and EPP
products can be either flush or surface mounted.
The address of the EPP-20 is changed easily with
DIL-switches. Call points can be tested and reset with the test key.

Manual Call Point:


Dimensions
Flush 93 x 89 x 27,5 mm
Surface 93 x 89 x 52 mm
Weight 100 g Call Point EPP-20
Colour Red, RAL 3001
Operating temperature -30 - +55 °C
Humidity 0 - 95%
Nominal Voltage 24VDC
Standby Current 300 * ’A
Alarm Current 5 mA
Enclosure Class IP24
Tested EN54-11

Product Order code


EPP-20, flexible element 0672 3732

Surface Mounting Box:


Dimensions
Flush 87 x 87 x 32 mm
Surface 93 x 89 x 52 mm
Weight 90 g
Colour Red, RAL 3001
Terminals 1 pcs. (for continuation of the cableshield)
Mounting holes 60 mm
Inlet in back side 1 pc., ¤ 20 mm
Inlet on lower side 2 pc., ¤ 6 mm
(to be pierced for cable)
Protection Class IP 24D
Product Order code
SRTT-2G 0642 4310

FX NET
45

ESI-40 and ESI-50


Loop powered sounder

The Loop-Powered 100dB Sounder is designed for use in open


areas and can be connected to the FX detection system.

The Intellia series of products are all compatible with the ALCboard
of an FX-panel.

The 100dB sounder is connected to the FX loop and powered


and controlled via the loop by the control and indicating equipment.

A nominal sound output of 100dB(A) is achieved at a current


consumption of only 5mA. The FX will be able to drive up to 20
sounders per loop on average; the maximum number of sounders
that may be connected to a particular loop should, however, be
Loop-Powered 100dB Sounder determined by a loop loading calculation.

ESI- 50
Operating voltage 17-28VDC
Current consumption at 24V
switch-on surge, <1s 1.2 mA
quiescent <1.2 mA
sounder operated 100dB(A) 5 mA
Sound output 100 dB (A)
IP rating (standard version) IP 42
IP rating (weatherproof version) IP 66
Operating temperature -20 - +60 °C
Humidity (no condensation) 0 - 95%
Dimensions
Weatherproof 100dB Sounder Standard (diameter x depth) 106 x 95 mm

ESI-40 Weatherproof (L x W x H) 110 x 110 x 113 mm


Weight
Standard 215 g
Weatherproof 340 g

Product Order code


ESI-40, weatherproof 100 dB 0672 8040
ESI-50, loop powered 100 dB 0672 8050

FX NET
46

Beacons
ESI-80
Loop powered beacon

The beacon has been developed as a supplement to sounders


in situations where there is a risk that sounders will not be
heard. This occurs, for example, where there is high background
noise e.g. in a workshop or a machine room or in a music room
at school

The Intellia series of products are all compatible with the ALCboard
of an FX-panel.

The Intellia ESI-80 Loop Powered Beacon is a local-area beacon


designed for indoor use.

Operating voltage 17-28VDC (polarity insensitive) Loop Powered Beacon


Current consumption at 24V ESI- 80
quiescent 150 μA
beacon operated 3 mA
switch-on surge 1 mA for 100 ms
Flash rate 1 Hz
Light output 1.75± 0.5 candela
IP rating IP 42
Operating temperature -20 - +60 °C
Humidity (no condensation) 0 - 95%
Dimensions (diameter x depth) 115 x 38 mm
Weight 140 g
Materials
beacon Polycarbonate
contacts Stainless steel
Fixing centres 50 - 60mm

Product order code 0672 8080

FX NET
47

Bases
EBI-10
Mounting base

All detectors in the Intellia range fit into EBI-10 mounting bases.

An earth connection is not required for either safety or correct


operation of detectors. The ground (earth) terminal is isolated and
is provided for tidy termination of grounded conductors or cable
screens and to maintain earth continuity where necessary.

Bases have a wide interior diameter for ease of access to cables


and terminals and there are two slots for fixing screws. The slots
enable two fixing screws to be located at a spacing of 51 to 69 mm.

Detectors fit into bases one way only, without snagging, and require
clockwise rotation without push force to be plugged in.
Mounting Base
EBI-10

Operating voltage 17-28VDC


IP rating IP 20
Operating temperature -20 - +60 °C
Storage temperature -30 - +80 °C
Humidity (no condensation) 0 - 95%
Dimensions (diameter x depth) 100 x 15 mm
Weight 100 g

Product order code 0672 0010

FX NET
48

EBI-11
Isolating base

The EBI-11 isolating base senses and isolates short circuit faults
on FX Fire Detection Panel loops and is intended for use with
Intellia detectors.

The base is loop-powered, polarity sensitive and accepts the


Address Card to set the associated device address.

In short-circuit conditions the integral yellow LED is illuminated.


The detector associated with the base remains active under shortcircuit
conditions. Power and signals to the affected section are
restored automatically when the fault is cleared.
Isolating Base
EBI-11

Operating voltage 17-28VDC


IP rating IP 20
Operating temperature -20 - +60 °C
Storage temperature -30 - +80 °C
Humidity (no condensation) 0 - 95%
Dimensions (diameter x depth) 100 x 24 mm
Weight 100 g

Product order code 0672 0011

FX NET
49

EBI-20
Relay base

The EBI-20 Low Power Relay Base, which is an advance version


of the standard base, incorporates a relay to control field equipment.

The EBI-20 Low Power Relay Base gives a set of voltage-free


changeover relay contacts controlled by the remote output of an
Intellia detector. By using a latching relay coupled to an efficient
drive circuit, the unit operates like a conventional relay while having
negligible current drain.

The base also retains the facility to drive a remote LED which
Relay Base mimics the detector remote output.

EBI-20

Operating voltage 17-28VDC


IP rating IP 20
Operating temperature -20 - +60 °C
Storage temperature -30 - +80 °C
Humidity (no condensation) 0 - 95%
Dimensions (diameter x depth) 100 x 24 mm
Weight 100 g

Product order code 0672 0020

FX NET
50

Base sounders
ESI-10
Ancillary Base Sounder

The Ancillary Base Sounder is a local-area sounder designed for


indoor use. It can be connected only to detection systems using
Intellia detectors and FX control panels with appropriate software.
The sounder incorporates a base into which a loop powered
beacon or an Intellia detector is fitted. It is powered by the control
panel via the loop wiring to which it is connected. Since the sounder
is switched on the remote indicator output of the associated
detector or beacon no remote indicator facility is available.
A guaranteed sound output of 85dB(A) at 1 meter is achieved at
a current consumption of only 3mA. The sounder generates very
low current noise so that up to 126 sounders may be connected
to a loop. In order to determine the exact number in a loop please
use the Loop Calculator program.

Ancillary Base Sounder


Operating voltage 17-28VDC ESI-10
Protocol pulses 5-9V
Current consumption at 24V DC
quiescent <100 μA
sounder operated 3 mA
IP rating IP 23D
Operating temperature -20 - +60 °C
Max. relative humidity (no condensation) 0 - 95%
Dimensions (diameter x depth) 115 x 38 mm
Weight 140 g
Material polycarbonate
Contacts stainless steel
Colour white
Fixing centres 50-60 mm

Product order code 0672 8010

FX NET
51

ESI-20 and ESI-30


Integrated Base Sounders

The Integrated Base Sounders offer:


- two tone ranges 55 - 75dB and 75 - 91dB
- synchronisation of ‘alert’ and ‘evacuate’ tones
- individual and group addressing
- available with or without built-in isolator
- unique acoustic self-test
- short circuit isolator (ESI-20)

The low tone range is useful in areas such as hospitals where a


fire alert is initially intended to warn staff only. The sounder is set
to the high range for general use. The acoustic self-test means
that the sounder listens to itself when it is switched on. If no sound
is detected a fault signal is transmitted when the sounder is polled.
The integrated base sounder responds to its own individual address
set with a DIL switch.

Integrated Base Sounders


Operating voltage 17-28VDC
ESI-20 and ESI-30 Protocol pulses 5-9V
Current consumption at 24V DC
quiescent <1.2 mA
sounder operated 5 mA
IP rating IP 21D
Operating temperature -20 - +60 °C
Max. relative humidity (no condensation) 0 - 95%
Dimensions (diameter x depth) 115 x 38 mm
Weight 140 g
Material polycarbonate
Contacts stainless steel
Colour white
Fixing centres 50-60 mm

Product Order code


ESI-20, short circuit isolator 0672 8020
ESI-30, no isolator 0672 8030

FX NET
52

ESI-60 and ESI-70


Integrated Sounders
Beacon Bases

The Loop-powered Sounder Beacon Base combines a sounder


with a beacon and a detector base in one unit. The beacon is
activated whenever the sounder is active and cannot be controlled
separately.

The products offer:


- two tone ranges 55 - 75dB and 75 - 91dB
- individual and group addressing
- available with or without built-in isolator
- unique acoustic self-test
- short circuit isolator (ESI-60)

The low tone range is useful in areas such as hospitals where a Integrated Sounder Beacon
fire alert is initially intended to warn staff only. The sounder is set Base ESI-60
to the high range for general use. The acoustic self-test means
that the sounder listens to itself when it is switched on. If no sound
is detected a fault signal is transmitted when the sounder is polled.

Operating voltage 17-28VDC


Protocol pulses 5-9V
Current consumption at 24V DC
quiescent <300 μA
sounder operated 8 mA
IP rating IP 21D
Operating temperature -20 - +60 °C
Max. relative humidity (no condensation) 0 - 95%
Dimensions (diameter x depth) 115 x 38 mm
Weight 140 g
Material polycarbonate
Contacts stainless steel
Colour white
Fixing centres 50-60 mm

Product Order code


ESI-60, short circuit isolator 0672 8060
ESI-70, no isolator 0672 8070

FX NET
53

Input/Output modules

EMI-310
Input Module with isolator

Fire protection systems can be engineered simply and effectively


without the need for custom-designed equipment. The Intellia Input
Modules offer several features for a variety of monitoring functions
in the FX fire detection system. The Intellia series of products are
all compatible with the ALC-board of an FX panel.

Modules are fitted with bi-directional short-circuit isolators so that


they are unaffected by a single short-circuit on either loop input
or output. Modules are designed to be surface or flush-mounted
to walls and consist of three parts: a backbox with knockouts for
cable entry, a PCB assembly and a protective front cover.

Input Module
EMI-310 Operating voltage 17-28VDC
Current consumption at 28V DC
Quiescent 1 mA
LED off, switch input closed 1.6 mA
LED on, switch input closed 4 mA
Switch input monitoring voltage 9-11V DC
IP rating IP 54
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%RH
Dimensions 150 x 90 x 48 mm
Weight 240 g

Product order code 0672 7310

FX NET
54

EMI-301
Output Module with isolator

The loop powered EMI-301 Module provides a voltage-free, single


pole, change-over relay output.

The EMI-301 module has one voltage-free change-over relay


output with double contacts.

One red LED and one yellow LED are visible through the front
cover of the enclosure. The red LED is illuminated to indicate that
the relay is set. The yellow LED is illuminated whenever the builtin
isolator has sensed a short-circuit loop fault.

Operating voltage (loop voltage) 17-28VDC Output Module with isolator


Current consumption at 28V DC EMI-301
Quiescent current 500 μA
LED off, switch input closed 1.6 mA
LED on, switch input closed 4 mA
Relay output contact rating 1A at 30V DC
IP rating IP 54
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 150 x 90 x 48 mm
Weight 240 g

Product order code 0672 7301

FX NET
55

EMI-311
Single Input - Output
Module with isolator

The EMI-311 module has one monitored switch contact input and
one voltage free change-over relay output with double contacts.
The EMI-311 module is fitted with a bi-directional short-circuit
isolator and will be unaffected by loop short-circuits on either loop
input or output.

Four LEDs, two red and two yellow, are visible through the front
cover of the enclosure. One red LED is illuminated to indicate that
the relay is set. The second red LED is illuminated to indicate that
the switch input is closed. One yellow LED is illuminated whenever
a fault condition (open or short circuit) has been detected. The
second yellow LED is illuminated whenever the built-in isolator
Single Input - Output Module has sensed a short-circuit loop fault.
with isolator EMI-311

Operating voltage (loop voltage) 17-28VDC


Current consumption at 28V DC
Quiescent current 1 mA
LED off, switch input closed 1.5 mA
LED on, switch input closed 2.5 mA
any other condition (2 LEDs on) 3 mA
Switch input monitoring voltage 19-11V DC
Relay output contact rating at 30V AV or DC 1A
(inductive or resistive)
IP rating IP 54
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 150 x 90 x 48 mm
Weight 240 g

Product order code 0672 7311

FX NET
56

EMI-311/240
Single Input - Single Mains
Switching Module with isolator

The EMI-311/240 module provides a monitored switch contact


input and a voltage-free, single pole change-over relay output.
This unit is designed to switch machinery operating at 230V, thus
obviating the need for an intermediate relay and a power supply.

Three LEDs, two red and one yellow, are visible through the front
cover of the enclosure. One red LED is illuminated to indicate that
the relay is set. The second red LED is illuminated to indicate that
the switch input is closed. The yellow LED is illuminated whenever
a fault condition (open or short circuit) has been detected. All LED
indicators can be disabled using segment 8 of the DIL switch.

Single Input
- Single Mains Switching Module
Operating voltage (loop voltage) 17-28VDC
Current consumption at 28V DC EMI-311/240
Quiescent 1.5 mA
LED on, switch input closed 5 mA
LED off, switch input closed 2 mA
any other condition (2 LEDs on) 5 mA
Rated load (resistive) 5 A at 250V AC
2 A at 48V DC
Switch input monitoring voltage 19-11V DC
IP rating IP 54
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 150 x 90 x 48 mm
Weight 240 g

Product order code 0672 7361

FX NET
57

EMI-310/CZ
Conventional Zone-Module
with isolator

Fire protection systems can be engineered simply and effectively


without the need for custom-designed equipment.

The loop powered EMI-310/CZ Conventional Zone-Module with


Isolator powers and controls the operation of a zone of conventional
detectors.

The Intellia series of products are all compatible with the ALCboard
of an FX-panel.

Operating voltage (loop voltage) 17-28VDC


Conventional Zone-Module
Current consumption at 28V DC
EMI-310/CZ
Quiescent 4.5 mA + detector load
alarm 11 mA (19mA when increased
current enabled)
short circuit 11 mA
Stabilisation time on power-up 4 seconds
IP rating IP 54
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 150 x 90 x 48 mm
Weight 230 g

Product order code 0672 7341

FX NET
58

EMI-301/S
Sounder Control Module
with isolator

Fire protection systems can be engineered simply and effectively


without the need for custom-designed equipment.

The EMI-301/S Module with Isolator is designed to control a zone


of sounders powered by an external DC supply. The sounders will
be switched to sound continuously or be pulsed, 1s on, 1s off.
Sounder Control Units at different addresses may be controlled
individually and have a facility for synchronising the outputs, when
being pulsed.

The Intellia series of products are all compatible with the ALCboard
of an FX-panel.
Sounder Control Module
EMI-301/S

Operating voltage (loop voltage) 17-28VDC


Current consumption at 28V DC
Quiescent 1.5 mA
Sounder operated 1.7 mA
Fault (yellow LED on) 3.6 mA
Sounder line short circuit 4.5 mA
Current consumption, external supply
relay off 200μA at 9 V
3mA at 32 V
sounders and red LED on 1.5mA at 9 V (+sounder load)
6.5mA at 32 V (+sounder load)
Sounder output monitoring voltage 9-11V DC
(open-circuit condition)
Maximum sounder circuit voltage 32V DC
Maximum sounder circuit current 1A at 32V DC
(inductive or resistive)
Maximum load between isolators 20 detectors
IP rating IP 54
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 150 x 90 x 48 mm
Weight 240 g

Product order code 0672 7351

FX NET
59

EMI-410
DIN-RAIL Input Module

The EMI-410 Module is designed to monitor the state of one or


more single pole, voltage-free contacts connected on a single pair
of cables and to report the status to the FX control panel.

The EMI-410 Module provides three input states to the control


equipment: ‘Normal’, ‘Fault’ and ‘Alarm’.

Two LEDs, one red and one yellow, are visible through the top
cover of the enclosure. The red LED is switched by the control
panel and can be illuminated in the event of an alarm condition
being detected. The yellow LED is illuminated whenever a fault
condition (open or short circuit) has been detected.

DIN-RAIL Input Module


EMI-410 Operating voltage (loop voltage) 17-28VDC
Current consumption at 28V DC
Quiescent 1 mA
Input short circuit 3.5 mA
Alarm LED on, switch input s/c 5.6 mA
Switch input monitoring voltage 9-11V DC
IP rating IP 20
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 110 x 107 x 20 mm
Weight 95g

Product order code 0672 7410

FX NET
60

EMI-401
Single Output Module

The EMI-401 Output Module provides a voltage-free, single pole,


change-over relay output.

One red LED is visible through the top cover of the enclosure.
This LED is illuminated to indicate that the relay is set. The LED
can be disabled, by means of the DIL switch, to reduce loop current.

Operating voltage (loop voltage) 17-28VDC


Current consumption at 28V DC
Quiescent 1 mA
Relay operated LED on 3.3 mA
Single Output Module
Relay operated LED off 1 mA
Relay output contact rating at 30V AC or DC max 1A EMI-401
Switch input monitoring voltage 9-11V DC
IP rating IP 20
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 110 x 107 x 20 mm
Weight 95g

Product order code 0672 7401

FX NET
61

EMI-411
Single Input - Single Output Module

The EMI-411 module has one monitored switch contact input and
one voltage-free change-over relay output.

Three LEDs, two red and one yellow, are visible through the top
cover of the enclosure. One red LED is illuminated to indicate that
the relay is set. The second red LED is illuminated to indicate that
the switch input is closed. The yellow LED is illuminated whenever
a fault condition (open or short circuit) has been detected. If the
indicating LEDs are not required or the extra loop current to
illuminate them is not available, they can be disabled by using the
eighth segment of the DIL switch.

Single Input
/Single Output Module
Operating voltage (loop voltage) 17-28VDC
EMI-411 Current consumption at 28V DC
Quiescent 1.2 mA
Switch input s/c max (LED on) 6mA
LEDs off 2.2mA
Any other condition (max 2 LEDs on) 4.5mA
Switch input monitoring voltage 9-11V DC
Relay output contact rating at 30V AC or DC
max 1A
Switch input monitoring voltage 9-11V DC
IP rating IP 20
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 110 x 107 x 20 mm
Weight 95g

Product order code 0672 7411

FX NET
62

EMI-410/CZ
Conventional Zone Module

Fire protection systems can be engineered simply and effectively


without the need for custom-designed equipment. The EMI-410/CZ
Conventional Zone-Module with Isolator powers and controls the
operation of a zone of conventional detectors.

The Intellia series of products are all compatible with the ALCboard
of an FX-panel. A 6.2 *end-of-line resistor is used to
monitor cables for open and short-circuit faults. The Zone Monitor
is fitted with a bi-directional short-circuit isolator and will be
unaffected by loop short-circuits on either loop input or output.
Enclosures with DIN rails are available to house the DIN rail Zone
Monitor.
Conventional Zone Module

Two LEDs are visible through the top cover of the enclosure. The EMI-410/CZ
red LED illuminates in the event of an alarm condition being
detected. The yellow LED is illuminated whenever the built in
isolator has sensed a short-circuit loop fault.

Operating voltage (loop voltage) 17-28VDC


Max current consumption at 28V DC
Quiescent 4 mA + detector load
Alarm 11 mA
Short-circuit 11mA
Max quiescent detector load 2mA
Max current through isolator 1A continuous
3A peak
Isolating voltage 14 V
Stabilisation time on power-up 4 seconds
IP rating IP 20
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 110 x 107 x 20 mm
Weight 95g

Product order code 0672 7441

FX NET
63

EMI-401/S
Sounder Control Module

The EMI-401/S Module is designed to control a zone of sounders


powered by an external DC supply. The sounders will be switched
to sound continuously or be pulsed, 1s on, 1s off. Sounder Control
Units at different addresses may be controlled individually and
have a facility for synchronising the outputs, when being pulsed.

The Intellia series of products are compatible with the FX-ALC


loop controller. A polarising diode is required with each alarm
device, as sounders are operated by voltage reversal, provided
by a double-pole change-over relay. The EMI-401/S DIN-rail Sounder
Control Module responds to its own individual address set with a
7-segment DIL switch.
Sounder Control Module
EMI-401/S
Two LEDs are visible through the top cover of the enclosure. The
red LED pulses or is illuminated continuously to indicate that the sounders
are, respectively, pulsed or switched on continuously. The yellow LED is
illuminated whenever a fault condition has been detected.

If the fault LED is not required or the extra loop current to illuminate
it is not available, it can be disabled by using the eighth segment
of the DIL switch. The red LED is powered from the external supply
and is always enabled.

Operating voltage 17-28 VDC


Current consumption at 24V DC 1.9 mA
Current consumption, external supply
relay off 1 mA at 12 V
3 mA at 35 V
alarm 35 mA at 12V + sounder load
45 mA at 35V + sounder load
Sounder output monitoring voltage (open circuit condition) 10-12 V DC
Max sounder circuit voltage 35 V DC
Max sounder circuit current 5A at 35 V DC
IP rating IP 20
Operating temperature -20°C - +70°C
Humidity (no condensation) 0 - 95%
Dimensions 110 x 107 x 20 mm
Weight 95 g

Product order code 0672 7451

FX NET
64

INTEGRATION
Esgraf graphical user interface

Esgraf is a graphical user interface by Schneider Electrics access control, intruder control,
video and fire alarms systems.

Daily use of Esgraf security system is easy

With the help of Esgraf, the location of alarms generated by a subsystem is


immediately displayed on the site plan. At the same time, if desired, alarm-
specific instructions and a video image of the location causing the alarm
can also be obtained. A printout of the alarming layout view is also gener-
ated automatically. Furthermore Esgraf is able to forward alarm details by
e-mail or SMS. Thus details of alarms quickly reach persons needing them.

The Esgraf interface provides especially good value in control rooms and
reception areas where personnel turnover is often high. With Esgraf, the
entire security system and related daily control activities can be managed
from a single userfriendly interface.

CCTV camera Manual call point

The call point helps


The camera helps verifying
to create the alarm
the alarm
manually

Beacon Smoke detector


When there is a fire The smoke detector
the beacon or beacon- gives automatic alarm in
sounder informs about case of fire
the alarm

FX NET
65

Esgraf connectivity

Esgraf
camera control panel

Esgraf connects to 64 systems

Esgraf shows
Cameras have control windows that look
detector contamination like a normal camera control panel. Pan, tilt
and zoom can be controlled with a mouse or
Windows joystick directly from Esgraf. A fixed
camera can have a software zoom feature.
Pre-positions and route programs can be
activated. Alarms coming from the systems
are displayed on the event list.

Esgraf 4.1 brings fire detectors’ contamina-


tion information to our graphical user inter-
face. Contamination information from fire OPC for external
detectors can be read or saved on database systems
server e.g. once a day, from where Esgraf can
read and show it graphically

FX NET fire alarm panel


A Windows program supporting FX NET
The panel handles info protocol. Reads fire events and delivers
all information from information to other systems like Vista can be
and to the field activated. Alarms coming from the systems
equipment are displayed on the event list.

FX NET
© 2011 Schneider Electric. All rights reserved.

Schneider Electric I Building Business


Pelco Finland Oy
P.O.Box 415, Kalkkipellontie 45
FIN-02601 ESPOO FINLAND
www.schneider-electric.com

Document Number FXINBR0001EN 08 2011

You might also like