Professional Documents
Culture Documents
T R A N S FO R M E R CO M P O N E N T S
—
Transformers are critical parts
in the power grid. To secure reliable
and safe service conditions,
ABB COMEM Operating unit
provides a comprehensive range
of measurement and safety devices,
including the new generation
of smart devices and cost-effective
complete solutions that monitor
transformer health and improve
safety, reliability and efficiency,
while minimizing environmental
impact.
TR ANSFORMER COMPONENTS 3
—
Table of contents
4 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Buchholz relays
Gas accumulation and oil flow monitoring
A Buchholz relay is a fundamental device for transformers, it keeps internal gas
accumulation and oil flow monitored and under control.
—
01
B U C H H O L Z R E L AY S 5
TECHNICAL DATA
Switches Up to 4
Min. switching current 10 mA/24 V dc (for lower current the golden contact is available)
Rated insulation voltage 2.5 kV ac 1 min between contacts and earth, 1.0 kV ac 1 min between open contacts
IP65
Degree of protection
IP66 upon request
4M4 Class
Mechanical test (vibration class)
4M6 Class upon request
—
For more details
please download
our data sheet
6 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Buchholz relay Comem eBR
with analog and digital output
—
02
B U C H H O L Z R E L AY S 7
TECHNICAL DATA
Switches Up to 4
Min. switching current 10 mA/24 V dc (for lower current are available the golden contact)
Rated insulation voltage 2.5 kV ac 1 min between contacts and earth, 1.0 kV ac 1 min between open contacts
IP65
Degree of protection
IP66 upon request
Modbus RTU
Digital output
Data logger
—
For more details
please download
our data sheet
8 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Dehydrating breathers
designed to absorb moisture
Moisture is a leading cause of transformer aging. Avoiding moisture ingress
into the transformer is paramount to avoiding outage and maximizing
the lifetime of the equipment.
—
03
D E H Y D R AT I N G B R E AT H E R S 9
TECHNICAL DATA
Standard EN 50216-5/A2
Material All the external part are resistant to transformer oils, salt fog and UV rays
Adding flange for fixing Standard in the lower part for the types 7 and 8
Colored, non-poisonous silica gel; amount according application table above (The color change from orange to
Desiccant
green absorbing humidity)
Protection Stainless steel pipe protection against accidental blows, with opening that allow visual inspection on the salt
SELECTION MATRIX
Features (available for standard version) Options
Corrosion protection: C4
Silica gel Volume (dm3)
Polycarbonate tube
Medium (Offshore)
Mechanical closing
Female connection
Flange connection
Moderate salinity
Hydraulic closing
(ISO 12944)
Glass tube
Type
6 20÷60 19 15.2 ■ ■ ■ ■ ■ ■ ● ●
7 >60 32 25.6 ■ ■ - ■ ■ - ● ●
8 >60 58 46.3 ■ ■ - ■ ■ - ● ●
(a) The oil quantities assigned to size classes are oriented on normal European ambient condition as given in EN50216-1, Table 1.
The values are intended to give guidance to the user: The proper choice must take into consideration the real environmental conditions, the thermal cycles due to the service
conditions of the transformer and the maintenance cycle.
—
For more details
please download
our data sheet
10 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Self-dehydrating breathers Comem eSDB
with analog and digital output
Moisture is a leading cause of transformer aging. Avoiding moisture ingress
into the transformer is of paramount importance to avoid outages
and maximize the lifetime of the asset.
—
04
D E H Y D R AT I N G B R E AT H E R S 11
TECHNICAL DATA
Material All the external part are resistant to transformer oils, salt fog and UV rays (1)
Degree of protection IP45 in accordance with EN60529 (except terminal box which is IP66)
Vibration damping Standard anti-vibration supports can be anchored to the transformer (Fig.3/D,4/D)
4 mm2, AWG 24-10 flexible cables with or without terminals (screws are used to fasten
Wires the cables to the terminal board on the terminal box). For digital/analog output advised 4x1mm2 (4x0.00155”2) /
2x1mm2 (2x0.0155”2) shielded twisted pair cable.
Rated voltage Power Supply 115 / 230V ac/dc ±10% 50 / 60 Hz (max/min supply voltage 90 / 270V ac/dc)
SELECTION MATRIX
OLTC Petersen coil Traction Network phase Network phase Network phase HVDC Furnace GSU
shifting shifting shifting cavern
Shunt reactors Shunt reactors Shunt reactors
Step up Step up
Power All < 40 MVA 40 ≤ MVA < 200 200 ≤ MVA < 350 MVA ≥ 350
Comem eSDB 10
•
Comem eSDB 10C
Comem eSDB 15 •
Comem eSDB 30 •
Comem eSDB 40 • • •
—
For more details
please download
our data sheet
12 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Liquid level indicators Comem OLI
clear and visible liquid level indication
Unexpected or accidental liquid leakages may occur randomly along transformer’s
lifetime. Clear and visible indication of oil or liquid level from any direction
has to be guaranteed through dedicated dials.
— The float movement associated with the liquid Benefits and features:
05
Comem OLI level is transmitted to the dial through a magnetic • Customizable mounting flange suitable for
coupling system; floats are available with either all transformers designs
axial or radial movement, dial can be installed • Adjustable value settings for switches
with a certain inclination. • No printings neither stickers on the view glass:
temperature indication is directly marked on
Liquid level indicator Comem OLI is compatible the plate behind the view glass
with all transformers’ design because it is prone • Easy accessibility to wiring box
to be customized to end user preferences • Field-proven reliability
through an adjustable fixing flange and dial • Robust design
marking. • Easy installation
• Compliant with IEC 60076-22-1
ABB’s liquid level indicators give off an alarm
if the fluid reaches the minimum or maximum
preset values.
Application:
• Liquid-filled power transformers with
or without conservator
• Conservator with rubber bag
• On-load tap-changer (OLTC) applications
—
05
L I Q U I D L E V E L I N D I C ATO R S 13
TECHNICAL DATA
Standard IEC 60076-22-1
Housing Alluminum alloy
Flange design Comem L140 Comem OLI22, L220 Comem OLI Comem L340
1;M25x1.5
Cable gland
3;M25x1.5 for Comem OLI, Comem OLI22, Comem eOLi and Comem eOLI22)
—
For more details
please download
our data sheet
14 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Liquid level indicators Comem eOLI
with analog and digital output
Liquid level indicator Comem eOLI, with digital and analog output offers reliable,
accurate and continuous monitoring of the liquid level inside the conservator,
enabling effective maintenance and enhancing reliability of the transformer.
— The float movement associated with the liquid Benefits and features:
06
Comem eOL level is transmitted to the dial through a magnetic • Customizable mounting flange suitable for all
with Comem eVIEWER coupling system; floats are available with either transformers designs
axial or radial movement, dial can be installed with • Adjustable value settings for switches
a certain inclination. Comem eOLI is compatible • No printings neither stickers on the view glass:
with all transformers’ design because it is prone to temperature indication is directly marked on
be customized to end user preferences through an the plate behind the view glass
adjustable fixing flange and dial marking. • Easy accessibility to wiring box
Furthermore Comem eOLI enables an additional • Continuous liquid level monitoring
visualization at eye height by means of a • Analog output 4-20mA
dedicated dial installed on the transformer’s wall. • Digital output Modbus RTU
• Customizable mounting flange suitable with all
Comem eViewer enables a visualization of the transformer’s designs
values at men height by means of a dedicated dial • Radial and axial float movement, suitable for rub-
installed on the transformer’s wall. ber bag
• Up to four adjustable switches
• Accurate indication of liquid level at men height
Application: with Comem eViewer
• Liquid-filled power transformers with or • Maintenance free
without conservator • Magnetic coupling
• Conservator with rubber bag • IP66
• Compatible with all Comem eDevices and
CoreSense+
• Compliant with IEC 60076-22-1
—
06
L I Q U I D L E V E L I N D I C ATO R S 15
TECHNICAL DATA
Modbus RTU
Digital output
Data logger
Dial at men height, Upon request
Comem eViewer Power supply 24 V dc
—
For more details
please download
our data sheet
16 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Contactless Ultrasonic liquid level indicator
Comem CU eOLI
with digital and analog output
A new contactless ultrasonic sensor based liquid level indicator with digital and analog
output enables continuous high accuracy measurement of liquid level in
transformer conservator or transformer tank.
—
07
L I Q U I D L E V E L I N D I C ATO R S 17
TECHNICAL DATA
Accuracy 0.5% FS
Repeatibility 0.5% FS
—
For more details
please download
our data sheet
18 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Winding and liquid temperature indicators
Comem OTI/Comem WTI
reliable temperature monitoring
Accurate and stable measurement of winding and liquid temperature inside the
transformer provides insight into the overall performance of the asset, while
avoiding thermal degradation and ensuring a longer operating life.
—
08
W I N D I N G A N D L I Q U I D T E M P E R AT U R E I N D I C ATO R S 19
TECHNICAL DATA
Housing All the external parts are resistant to oils, salt fog and UV rays
Capillary tube protection Copper tube Flexible AISI 304 stainless steel armouring or Rilsan
Micro switches Up to 4
—
For more details
please download
our data sheet
20 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Winding and liquid temperature indicators
Comem eWTI/eOTI
with analog and digital output
ABB’s maintenance-free winding and liquid temperature indicators enable
effective maintenance and enhance the reliability of the transformer by
continuously monitoring the liquid and winding temperature.
—
09
W I N D I N G A N D L I Q U I D T E M P E R AT U R E I N D I C ATO R S 21
TECHNICAL DATA
Housing All the external parts are resistant to oils, salt fog and UV rays
Capillary tube protection Copper tube Flexible AISI 304 stainless steel armouring or Rilsan
Micro switches Up to 4
Modbus RTU
Digital output
Data logger
—
For more details
please download
our data sheet
22 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Pressure Relief Devices Comem PRD
limiting the tank overpressure
Pressure is a very important parameter to determine signs of decreased performance
or upcoming failure. Moreover, in case of a high pressure situation, it is fundamental
to limit and contain the effect of hot oil evacuation in the surrounding environment.
—
10
PRESSURE RELIEF DE VICES 23
TECHNICAL DATA
Three types of installation Indoor/outdoor Corrosion class: C4- Medium Ral 7032
environment Tropical proof Corrosion class: C5- Medium Geomet coating
—
For more details
please download
our data sheet
24 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Pressure Relief Devices Comem ePRD
with analog and digital output
Continuous control and monitoring of the pressure inside the transformer tank
significantly improves transformer reliability and safety.
—
11
PRESSURE RELIEF DE VICES 25
TECHNICAL DATA
Three types of installation Indoor/outdoor Corrosion class: C4- Medium RAL 7032
environment Tropical proof Corrosion class: C5- Medium Geomet coating
From -40°C to +80°C
Ambient temperature
Lower temperature version available upon request
Indoors and outdoors, tropical proof
Installation To prevent the formation of condensation
Off shore protection available upon demand
Oil-directed cover Seawater resistant cast aluminum, powder coated
Visual indicator Seawater resistant aluminum, red color and stainless steel stem
Switches Up to 3, ChangeOver
—
For more details
please download
our data sheet
26 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Hydrogen and moisture sensor CoreSense™
Single gas sensing to flag incipient
transformer faults
Hydrogen in transformer oil, above all other gases, is a key indicator of potential
problems, resulting in interrupted operations and unplanned expenditures.
Monitoring hydrogen levels with CoreSense™ is the most cost-effective, condition-
based maintenance approach to mitigate these risks, and to ensure reliable
transformer performance and optimized maintenance planning.
—
12
M O N I TO R I N G S Y S T E M S 27
TECHNICAL DATA
Hydrogen
Hydrogen measurement range 0 to 5,000 ppm (µl/l) with a detection limit of 25 ppm (µl/l )
Moisture
Moisture range in ppm 0 to 60 ppm @ 25°C (77°F) or 0 to 180 ppm @ 55°C (131°F)
Electrical specifications
Mechanical specifications
Communications specifications
Ultrabright easy-to-read LED Three color code LED system indicates status of hydrogen and moisture levels
Field display option Field mount display for hydrogen and moisture readout at transformer
Digital output RS485 serial port
2 RJ45 100 base-T Ethernet ports
100 base-FX fiber optic Ethernet port
Protocols Modbus RTU over RS485 and Modbus IP over Ethernet
Modbus Master on RS485 for reading local sensors (CoreSense™ Hub)
DNP3 over RS485 and Ethernet
IEC61850 over Ethernet
Analog output 3 dry-contact relays for alarms
3 analog 4-20 mA outputs for publishing values
3 analog 4-20 mA inputs for reading external sensors
Environmental specifications
Operating ambient temperature and humidity From –50 °C to 55 °C (–58 °F to 131 °F) with 5 to 95% RH, non-condensing
—
For more details
please download
our brochure
28 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Multi-gas sensing CoreSense™ M10
for optimal transformer operation
Gases in transformer oil serve as chemical indicators of potential problems that can
result in interrupted operations and unplanned expenditures. Monitoring dissolved gas
levels with CoreSense™ M10 is the most effective condition-based maintenance tool
to mitigate these risks. It ensures reliable transformer operation and optimized
maintenance planning.
—
13
Continuous online monitoring Reliable design
CoreSenseTM M10 CoreSense™ M10 provides real-time, continuous, CoreSense™ M10 is designed for at least 10 years
online monitoring of gas and moisture levels in of maintenance-free operation with no
transformer oil. It measures nine gases: hydrogen, consumables. Thanks to its innovative Fourier
methane, acetylene, ethylene, ethane, carbon Transform Infrared spectrometer (FTIR) and
monoxide, carbon dioxide, propane and propene. industrial grade design, the CoreSense™ M10:
Dissolved gas readings can be used to provide • will not drift over time and does not require
early identification and warnings for most any carrier or calibration gases
transformer faults, whereas moisture monitoring • reduces risks of oil leaks with a simple pump-
can prevent premature aging of a unit. Early less oilcircuit limited to the measuring head
identification and detection of such incipient • has reduced maintenance with built-in redun-
faults thereby allow you to take preemptive dancies
measures, when needed. • can survive in harsh and corrosive outdoor
conditions, withstand vacuum and operate
Easy installation under one meter (3 feet) of water
With a thermal element that induces convection
currents, CoreSense™ M10 can be connected to Simple interface
new or existing transformers of all types and • Whether looking at the LED alarms on the de-
brands, at most locations, including the drain vice, the built-in touch screen display or the
valve. CoreSense™ M10 shares the same intuitive web interface, the message will be
transformer interface as a CoreSense™ single-gas concise and simple to read
sensor. This enables easy interchangeability • WARNING and ALARM settings are user-
between the two devices, which is useful to configurable for all gases and moisture levels
optimize the operation of a sick transformer by • Collected data is available for download in .csv
replacing a CoreSense™ with a CoreSense™ M10. format
• AssetHealth DGA PC software provides data
analytics, including Duval triangles
—
13
M O N I TO R I N G S Y S T E M S 29
TECHNICAL DATA
Gases
25 to 5,000 ppm (µl/l) ±25 ppm or ±20% (whichever is higher)
Hydrogen (H2)
5 to 5,000 ppm high performance version available as an option
Carbon monoxide (CO) 2 to 5,000 ppm (µl/l) ±2 ppm or ±5% (whichever is higher)
Carbon dioxide (CO2) 5 to 20,000 ppm (µl/l) ±5 ppm or ±5% (whichever is higher)
Acetylene (C2H2) 0.5 to 10,000 ppm (µl/l) ±0.5 ppm or ±5% (whichever is higher)
Propene (C3H6) 20 to 10,000 ppm (µl/l) ±20 ppm or ±5% (whichever is higher)
Propane (C3H8) 10 to 10,000 ppm (µl/l) ±10 ppm or ±5% (whichever is higher)
Moisture
Moisture range in ppm 0 to 60 ppm @ 25°C (77°F) or 0 to 180 ppm @ 55°C (131°F)
Mechanical specifications
Sensor head Dimensions, weight 392 x 264 x 158 mm (14.43 x 10.39 x 6.2 in), 8 kg (17.6 lbs)
Operating ambient temperature and humidity From –50 °C to 55 °C (from –58 °F to 131 °F) with 5 to 95% RH, non-condensing
—
For more details
please download
our leaflet
30 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Integrated safety detector Comem RIS2
bunch of accessories in one single device
Comem RIS2 integrates the functions performed by different transformer
accessories into a single, compact and reliable device that keeps constant control
of the transformer’s pressure, temperature, oil level and gassing.
—
14
I N T E G R AT E D S A F E T Y D E T E C TO R 31
TECHNICAL DATA
Standard IEC 60076-22-1
IP66
Degree of protection (CEI-EN 60529)
IP67 upon request
Degree of shock tightness (EN 50102) IK 07
Salt-fogtight 1,000 h
UV-Ray resistance
500 h
(UNI-ISO 4892 / UNI-ISO 4582)
Ambient temperature from -40°C to 60°C
• Gassing
Detector closes/opens a circuit when
the max. gas volume is reached (max.170 cm3) • Temperature
—
For more details please
consult our web page
32 ME A SUREMENT AND SAFET Y DEVICES TR ANSFORMER COMPONENTS
—
Temperature monitoring unit Comem DTI
Monitor and protect your dry-type transformer
Temperature monitoring unit Comem DTI / Comem eDTI is a measurement and safety
device for use in dry-type transformers, which enables you to control alarms, control
fans and continuously monitor temperature in your transformer fleet.
—
15
I N T E G R AT E D S A F E T Y D E T E C TO R 33
TECHNICAL DATA
Auxiliary power supply 24/230 V dc/ac ±15% 50-60 Hz
Maximum absorption 4 VA
Connection Extractible terminal with screws, section wires max 2.5 mm2
2500 Vrms 50 Hz per 60 s :U aux - input PT100 /
Insulation
U aux - relay outputs / inputs PT100 - relay outputs
Protection degree IP52 front panel, IP20 rear panel, as CEI-EN 60529
Flash mounting DIN 96x96 mm, depth 120 mm /
Dimensions - enclosure
Enclosure thermoplastic self-extinguishing as UL94 V0
Working environment From-10 °C to +60 °C, humidity max 95%
_
1 T1-T2-T3-T4 channel display
_
2 Temperature display
_
1 3
_
ALARM: First level of alarm
abb.com/transformercomponents
9AKK107492A2850-EN 06-2019