3- Cable sizes for apartments (4x35 +16 mm) to be replaced as per Voltage Drop Calculation.
4- Cable tray type shall be used for power and communication systems and cable trunking to be
removed from BOQ.
6- Remove all non-fusible disconnect switch 60 A for DX units and used only for Main roof.
7- All Access control in flat area shall be removed and replaced by smart magnetic locked and
adding ACS for (Communication room).
8- CCTV Cameras to be reduced in basement floor and removed from elevator cabinets.
10- Lighting fixtures layout for flats to be redesign and submitted us for approval.
12- Fire alarm system to be submitted after approved from civil defense.