You are on page 1of 5

SABBOUR 

CONSULTING OFFICE MEP LOAD ASSESSMENT CORNICHE JEDDAH WATERFRONT DEVELOPMENT

SEC INDEX

Electrical Load Electrical Load


Total
Outdoor GROUND FLOOR FIRST FLOOR Total
Electrical Load After
Air-Conditioned Area 735 VA/M2 FOR 235 V/M2 FOR Total Electrical Load After
Unit Number / Reference GROSS NLA Taking Demand 70% for
Area (Leasable Indoor Indoor Electrical Load adding 5% on load
F&B And 80% for
area) 95VA/M2 for 95VA/M2 for for future
Cinemas As per SEC
Outdoor Outdoor
Sr No Floor

Total Total
Ref Ref Sq. meters Sq. meters Sq. meters kVA kVA kVA
kVA kVA

C101 GF 153.00 52.00 117.40 117.40 123.26 86.29


1 F&B 298.00
C201 FF 145.00 39.00 37.78 37.78 39.67 27.77
C102 GF 174.00 60.00 133.59 133.59 140.27 98.19
2 F&B 313.00
C202 FF 139.00 38.00 36.28 36.28 38.09 26.66
C103 GF 174.00 60.00 133.59 133.59 140.27 98.19
3 F&B 313.00
C203 FF 139.00 38.00 36.28 36.28 38.09 26.66
C104 GF 174.00 59.00 133.50 133.50 140.17 98.12
4 F&B 320.00
C204 FF 146.00 32.00 37.35 37.35 39.22 27.45
C105 GF 175.00 60.00 134.33 134.33 141.04 98.73
5 F&B 321.00
C205 FF 146.00 31.00 37.26 37.26 39.12 27.38
C106 GF 175.00 61.00 134.42 134.42 141.14 98.80
6 F&B 321.00
C206 FF 146.00 31.00 37.26 37.26 39.12 27.38
C107 GF 109.00 60.00 85.82 85.82 90.11 63.07
7 F&B 312.00
C207 FF 203.00 38.00 51.32 51.32 53.88 37.72
C108 GF 109.00 60.00 85.82 85.82 90.11 63.07
8 F&B 267.00
C208 FF 158.00 38.00 40.74 40.74 42.78 29.94
C109 GF 109.00 60.00 85.82 85.82 90.11 63.07
9 F&B 253.00
C209 FF 144.00 38.00 37.45 37.45 39.32 27.53
C110 GF 119.00 66.00 93.74 93.74 98.42 68.90
10 F&B 273.00
C210 FF 154.00 42.00 40.18 40.18 42.19 29.53
GF 104.00 41.00 80.34 80.34 84.35 59.05
12 F&B C112 104.00
0.00 0.00 0.00 0.00
GF 94.00 33.00 72.23 72.23 75.84 53.09
13 F&B C113 94.00
0.00 0.00 0.00 0.00
GF 106.00 44.00 82.09 82.09 86.19 60.34
14 F&B C114 106.00
0.00 0.00 0.00 0.00
GF 111.00 56.00 86.91 86.91 91.25 63.88
15 F&B C115 111.00
FF 0.00 0.00 0.00 0.00
GF 221.00 221.00 88.00 170.80 170.80 179.33 125.53
16 F&B C116
FF 0.00 0.00 0.00 0.00 0.00
17 F&B C117 GF 1,264.00 1,264.00 929.04 929.04 975.49 682.84

C-1 FF 274.13 274.13 63.05 63.05 66.20 46.34


C-2 FF 243.34 243.34 55.97 55.97 58.77 41.14
C-3 FF 240.14 240.14 55.23 55.23 57.99 40.60
18 CINEMA C-4 FF 249.15 249.15 57.30 57.30 60.17 42.12
C-5 FF 244.63 244.63 56.26 56.26 59.08 41.35
C-6 FF 272.13 272.13 62.59 62.59 65.72 46.00
C-7 FF 258.35 258.35 59.42 59.42 62.39 43.67
D101 GF 1,135.00 92.00 271.63 271.63 285.21 199.65
19 ENTERTAINMENT 2,527.13
D201 FF 1,392.13 198.00 342.96 342.96 360.11 252.08

CONCESSION
20 D101A GF 0.00 0.00 0.00 0.00 0.00
STORE
D102 GF 0.00 0.00 0.00 0.00 0.00
21 F&B
0.00 0.00 0.00 0.00

D104 GF 251.00 64.00 190.57 190.57 200.09 140.07


23 F&B 491.00
D204 FF 240.00 51.00 61.25 61.25 64.31 45.02

D105 GF 272.00 272.00 104.00 209.80 209.80 220.29 154.20


24 F&B

D205 FF 215.00 215.00 54.00 55.66 55.66 58.44 40.91


D106 GF 182.00 73.00 140.71 140.71 147.74 103.42
25 F&B 305.00
D206 FF 123.00 59.00 34.51 34.51 36.24 25.36

E101 GF 179.00 72.00 138.41 138.41 145.33 101.73


29 F&B 358.00
E201 FF 179.00 56.00 47.39 47.39 49.75 34.83
E102 GF 179.00 77.00 138.88 138.88 145.82 102.08
30 F&B 359.00
E202 FF 180.00 55.00 47.53 47.53 49.90 34.93
E103 GF 179.00 73.00 138.50 138.50 145.43 101.80
31 F&B 359.00
E203 FF 180.00 55.00 47.53 47.53 49.90 34.93
E104 GF 180.00 86.00 140.47 140.47 147.49 103.25
32 F&B 360.00
E204 FF 180.00 55.00 47.53 47.53 49.90 34.93
E105 GF 179.00 78.00 138.98 138.98 145.92 102.15
33 F&B 359.00
E205 FF 180.00 55.00 47.53 47.53 49.90 34.93
E106 GF 179.00 74.00 138.60 138.60 145.52 101.87
34 F&B 358.00
E206 FF 179.00 55.00 47.29 47.29 49.65 34.76
E107 GF 179.00 80.00 139.17 139.17 146.12 102.29
35 F&B 358.00
E207 FF 179.00 57.00 47.48 47.48 49.85 34.90
E108 GF 179.00 73.00 138.50 138.50 145.43 101.80
36 F&B 359.00
E208 FF 180.00 55.00 47.53 47.53 49.90 34.93
E109 GF 179.00 92.00 140.31 140.31 147.32 103.12
37 F&B 359.00
E209 FF 180.00 55.00 47.53 47.53 49.90 34.93
E110 GF 179.00 76.00 138.79 138.79 145.72 102.01
38 F&B 358.00
E210 FF 179.00 56.00 47.39 47.39 49.75 34.83

F101 GF 190.00 75.00 146.78 146.78 154.11 107.88


39 F&B 380.00
F201 FF 190.00 59.00 50.26 50.26 52.77 36.94
F102 GF 180.00 76.00 139.52 139.52 146.50 102.55
40 F&B 360.00
F202 FF 180.00 54.00 47.43 47.43 49.80 34.86
F103 GF 115.00 74.00 91.56 91.56 96.13 67.29
41 F&B 318.00
F203 FF 203.00 55.00 52.93 52.93 55.58 38.90

MEP LOADS ASSESSMENT REV E SEP 2021 1
SABBOUR CONSULTING OFFICE MEP LOAD ASSESSMENT CORNICHE JEDDAH WATERFRONT DEVELOPMENT

SEC INDEX

Electrical Load Electrical Load


Total
Outdoor GROUND FLOOR FIRST FLOOR Total
Electrical Load After
Air-Conditioned Area 735 VA/M2 FOR 235 V/M2 FOR Total Electrical Load After
Unit Number / Reference GROSS NLA Taking Demand 70% for
Area (Leasable Indoor Indoor Electrical Load adding 5% on load
F&B And 80% for
area) 95VA/M2 for 95VA/M2 for for future
Cinemas As per SEC
Outdoor Outdoor
Sr No Floor

Total Total
Ref Ref Sq. meters Sq. meters Sq. meters kVA kVA kVA
kVA kVA

F104 GF 115.00 76.00 91.75 91.75 96.33 67.43


42 F&B 318.00
F204 FF 203.00 55.00 52.93 52.93 55.58 38.90
F105 GF 98.00 77.00 79.35 79.35 83.31 58.32
43 F&B 285.00
F205 FF 187.00 55.00 49.17 49.17 51.63 36.14
F106 GF 98.00 78.00 79.44 79.44 83.41 58.39
44 F&B 285.00
F206 FF 187.00 54.00 49.08 49.08 51.53 36.07
F107 GF 179.00 78.00 138.98 138.98 145.92 102.15
45 F&B 358.00
F207 FF 179.00 57.00 47.48 47.48 49.85 34.90

G101 GF 179.00 78.00 138.98 138.98 145.92 102.15


46 F&B 329.00
G201 FF 150.00 48.00 39.81 39.81 41.80 29.26
G102 GF 180.00 90.00 140.85 140.85 147.89 103.52
47 F&B 330.00
G202 FF 150.00 42.00 39.24 39.24 41.20 28.84
G103 GF 179.00 70.00 138.22 138.22 145.13 101.59
48 F&B 329.00
G203 FF 150.00 48.00 39.81 39.81 41.80 29.26
G104 GF 180.00 83.00 140.19 140.19 147.19 103.04
49 F&B 331.00
G204 FF 151.00 42.00 39.48 39.48 41.45 29.01
G105 GF 180.00 79.00 139.81 139.81 146.80 102.76
50 F&B 331.00
G205 FF 151.00 50.00 40.24 40.24 42.25 29.57
G106 GF 180.00 76.00 139.52 139.52 146.50 102.55
51 F&B 331.00
G206 FF 151.00 49.00 40.14 40.14 42.15 29.50
G107 GF 180.00 82.00 140.09 140.09 147.09 102.97
52 F&B 302.00
G207 FF 122.00 59.00 34.28 34.28 35.99 25.19
G108 GF 188.00 74.00 145.21 145.21 152.47 106.73
53 F&B 309.00
G208 FF 121.00 62.00 34.33 34.33 36.04 25.23
G109 GF 180.00 89.00 140.76 140.76 147.79 103.45
54 F&B 302.00
G209 FF 122.00 70.00 35.32 35.32 37.09 25.96
G110 GF 180.00 75.00 139.43 139.43 146.40 102.48
55 F&B 361.00
G210 FF 181.00 192.00 60.78 60.78 63.81 44.67
G111 GF 179.00 71.00 138.31 138.31 145.23 101.66
56 F&B 179.00
FF 0.00 0.00 0.00 0.00

H101 GF 268.00 105 206.96 206.96 217.30 152.11


57 F&B 268.00
H201 FF 134.00 152 45.93 45.93 48.23 33.76
H102 GF 180.00 80 139.90 139.90 146.90 102.83
58 F&B 305.00
H202 FF 125.00 80 36.98 36.98 38.82 27.18
H103 GF 179.00 72 138.41 138.41 145.33 101.73
59 F&B 305.00
H203 FF 126.00 72 36.45 36.45 38.27 26.79
H104 GF 180.00 79 139.81 139.81 146.80 102.76
60 F&B 306.00
H204 FF 126.00 82 37.40 37.40 39.27 27.49
H105 GF 179.00 71 138.31 138.31 145.23 101.66
61 F&B 330.00
H205 FF 151.00 53 40.52 40.52 42.55 29.78
H106 GF 180.00 75 139.43 139.43 146.40 102.48
62 F&B 332.00
H206 FF 152.00 53 40.76 40.76 42.79 29.95
H107 GF 180.00 72 139.14 139.14 146.10 102.27
63 F&B 331.00
H207 FF 151.00 53 40.52 40.52 42.55 29.78
H108 GF 180.00 81 140.00 140.00 146.99 102.90
64 F&B 331.00
H208 FF 151.00 56 40.81 40.81 42.85 29.99
H109 GF 179.00 72 138.41 138.41 145.33 101.73
65 F&B 331.00
H209 FF 152.00 46 40.09 40.09 42.09 29.47
H110 GF 180.00 76 139.52 139.52 146.50 102.55
66 F&B 333.00
H210 FF 153.00 55 41.18 41.18 43.24 30.27

K101 GF 302 116 232.99 232.99 244.64 171.25


67 F&B 645
K201 FF 343 83 88.49 88.49 92.91 65.04
K102 GF 299 159 234.87 234.87 246.61 172.63
68 F&B 630
K202 FF 331 107 87.95 87.95 92.35 64.64
K103 GF 261 98 201.15 201.15 211.20 147.84
69 F&B 637
K203 FF 376 80 95.96 95.96 100.76 70.53
K104 GF 123 37 93.92 93.92 98.62 69.03
70 F&B 123
K204 FF 0.00 0.00 0.00 0.00
K105 GF 276 95 211.89 211.89 222.48 155.74
71 F&B 794
K205 FF 518 63 127.72 127.72 134.10 93.87
K106 GF 276 97 212.08 212.08 222.68 155.88
72 F&B 840
K206 FF 564 66 138.81 138.81 145.75 102.03
K107 GF 123 37 93.92 93.92 98.62 69.03
73 F&B 123
K207 FF 0.00 0.00 0.00 0.00
K108 GF 299 84 227.75 227.75 239.13 167.39
74 F&B 661
K208 FF 362 58 90.58 90.58 95.11 66.58
K109 GF 237 94 183.13 183.13 192.28 134.60
75 F&B 540
K209 FF 303 107 81.37 81.37 85.44 59.81
K110 GF 124 91 99.79 99.79 104.77 73.34
76 F&B 124
K210 FF 0.00 0.00 0.00 0.00
K111 GF 237 87 182.46 182.46 191.58 134.11
77 F&B 540
K211 FF 303 105 81.18 81.18 85.24 59.67
K112 GF 125 82 99.67 99.67 104.65 73.25
78 F&B 125
K212 FF 0.00 0.00 0.00 0.00
K113 GF 279 88 213.43 213.43 224.10 156.87
79 F&B 685
K213 FF 406 141 108.81 108.81 114.25 79.97

MEP LOADS ASSESSMENT REV E SEP 2021 2
SABBOUR CONSULTING OFFICE MEP LOAD ASSESSMENT CORNICHE JEDDAH WATERFRONT DEVELOPMENT

SEC INDEX

Electrical Load Electrical Load


Total
Outdoor GROUND FLOOR FIRST FLOOR Total
Electrical Load After
Air-Conditioned Area 735 VA/M2 FOR 235 V/M2 FOR Total Electrical Load After
Unit Number / Reference GROSS NLA Taking Demand 70% for
Area (Leasable Indoor Indoor Electrical Load adding 5% on load
F&B And 80% for
area) 95VA/M2 for 95VA/M2 for for future
Cinemas As per SEC
Outdoor Outdoor
Sr No Floor

Total Total
Ref Ref Sq. meters Sq. meters Sq. meters kVA kVA kVA
kVA kVA

L100 GF 113 50 87.81 87.81 92.20 64.54


80 F&B 211
L200 FF 98 365 57.71 57.71 60.59 42.41
L101 GF 122 60 95.37 95.37 100.14 70.10
81 F&B 212
L201 FF 90 50 25.90 25.90 27.20 19.04
L102 GF 160 64 123.68 123.68 129.86 90.90
82 F&B 288
L202 FF 128 50 34.83 34.83 36.57 25.60
L103 GF 166 67 128.38 128.38 134.79 94.36
83 F&B 299
L203 FF 133 50 36.01 36.01 37.81 26.46
L104 GF 166 67 128.38 128.38 134.79 94.36
84 F&B 299
L204 FF 133 50 36.01 36.01 37.81 26.46
L105 GF 164 67 126.91 126.91 133.25 93.28
85 F&B 297
L205 FF 133 50 36.01 36.01 37.81 26.46
L106 GF 164 67 126.91 126.91 133.25 93.28
86 F&B 297
L206 FF 133 50 36.01 36.01 37.81 26.46
L107 GF 164 67 126.91 126.91 133.25 93.28
87 F&B 297
L207 FF 133 50 36.01 36.01 37.81 26.46
L108 GF 164 67 126.91 126.91 133.25 93.28
88 F&B 297
L208 FF 133 50 36.01 36.01 37.81 26.46
L109 GF 164 67 126.91 126.91 133.25 93.28
89 F&B 297
L209 FF 133 50 36.01 36.01 37.81 26.46
L110 GF 255 108 197.69 197.69 207.57 145.30
90 F&B 458
L210 FF 203 85 55.78 55.78 58.57 41.00
L111 GF 355 145 274.70 274.70 288.44 201.90
91 F&B 649
L211 FF 294 98 78.40 78.40 82.32 57.62
L112 GF 413 166 319.33 319.33 335.29 234.70
92 F&B 762
L212 FF 349 106 92.09 92.09 96.69 67.68
L113 GF 418 166 323.00 323.00 339.15 237.41
93 F&B 773
L213 FF 355 111 93.97 93.97 98.67 69.07
L114 GF 423 176 327.63 327.63 344.01 240.80
94 F&B 603
L214 FF 180 285 69.38 69.38 72.84 50.99
L115 GF 437 198 340.01 340.01 357.01 249.90
95 F&B 665
L215 FF 228 88 61.94 61.94 65.04 45.53
L116 GF 410 184 318.83 318.83 334.77 234.34
96 F&B 820
L216 FF 410 135 109.18 109.18 114.63 80.24
L117 GF 409 172 316.96 316.96 332.80 232.96
97 F&B 818
L217 FF 409 132 108.66 108.66 114.09 79.86
L118 GF 383 118 292.72 292.72 307.35 215.15
98 F&B 766
L218 FF 383 102 99.70 99.70 104.68 73.28
L119 GF 277 122 215.19 215.19 225.94 158.16
99 F&B 556
L219 FF 279 73 72.50 72.50 76.13 53.29
L120 GF 413 99 312.96 312.96 328.61 230.03
100 F&B 827
L220 FF 414 89 105.75 105.75 111.03 77.72

N101 GF 519 446 423.84 423.84 445.03 311.52


101 F&B 879
N201 FF 360 403 122.89 122.89 129.03 90.32
N102 GF 501 447 410.70 410.70 431.24 301.86
102 F&B 866
N202 FF 365 411 124.82 124.82 131.06 91.74
N103 GF 501 447 410.70 410.70 431.24 301.86
103 F&B 866
N203 FF 365 411 124.82 124.82 131.06 91.74
N104 GF 519 446 423.84 423.84 445.03 311.52
104 F&B 879
N204 FF 360 403 122.89 122.89 129.03 90.32
N105 GF 519 446 423.84 423.84 445.03 311.52
105 F&B 879
N205 FF 360 403 122.89 122.89 129.03 90.32
N106 GF 501 447 410.70 410.70 431.24 301.86
106 F&B 866
N206 FF 365 411 124.82 124.82 131.06 91.74
N107 GF 501 447 410.70 410.70 431.24 301.86
107 F&B 866
N207 FF 365 411 124.82 124.82 131.06 91.74
N108 GF 519 446 423.84 423.84 445.03 311.52
108 F&B 879
N208 FF 360 403 122.89 122.89 129.03 90.32

J101 GF 180 74 139.33 139.33 146.30 102.41


109 F&B 360
J201 FF 180 49 46.96 46.96 49.30 34.51
J102 GF 180 72 139.14 139.14 146.10 102.27
110 F&B 360
J202 FF 180 48 46.86 46.86 49.20 34.44
J103 GF 177 73 137.03 137.03 143.88 100.72
111 F&B 357
J203 FF 180 47 46.77 46.77 49.10 34.37
J104 GF 118 80 94.33 94.33 99.05 69.33
112 F&B 322
J204 FF 204 58 53.45 53.45 56.12 39.29
J105 GF 118 80 94.33 94.33 99.05 69.33
113 F&B 323
J205 FF 205 57 53.59 53.59 56.27 39.39
J106 GF 118 78 94.14 94.14 98.85 69.19
114 F&B 323
J206 FF 205 57 53.59 53.59 56.27 39.39
J107 GF 117 66 92.27 92.27 96.88 67.81
115 F&B 321
J207 FF 204 56 53.26 53.26 55.92 39.15
J108 GF 178 74 137.86 137.86 144.75 101.33
116 F&B 358
J208 FF 180 48 46.86 46.86 49.20 34.44
J109 GF 180 72 139.14 139.14 146.10 102.27
117 F&B 360
J209 FF 180 48 46.86 46.86 49.20 34.44

MEP LOADS ASSESSMENT REV E SEP 2021 3
SABBOUR CONSULTING OFFICE MEP LOAD ASSESSMENT CORNICHE JEDDAH WATERFRONT DEVELOPMENT

SEC INDEX

Electrical Load Electrical Load


Total
Outdoor GROUND FLOOR FIRST FLOOR Total
Electrical Load After
Air-Conditioned Area 735 VA/M2 FOR 235 V/M2 FOR Total Electrical Load After
Unit Number / Reference GROSS NLA Taking Demand 70% for
Area (Leasable Indoor Indoor Electrical Load adding 5% on load
F&B And 80% for
area) 95VA/M2 for 95VA/M2 for for future
Cinemas As per SEC
Outdoor Outdoor
Sr No Floor

Total Total
Ref Ref Sq. meters Sq. meters Sq. meters kVA kVA kVA
kVA kVA

J110 GF 282 139 220.48 220.48 231.50 162.05


118 F&B 566
J210 FF 284 117 77.86 77.86 81.75 57.22

119 F&B P101 GF 83 83 37 64.52 64.52 67.75 47.42

120 F&B P102 GF 83 83 38 61.01 61.01 64.06 44.84

121 F&B P103 GF 83 83 40 64.81 64.81 68.05 47.63

122 F&B P104 GF 86 86 37 63.21 63.21 66.37 46.46

123 F&B P105 GF 0 0 0 0.00 0.00 0.00 0.00

124 F&B P106 GF 0 0 0 0.00 0.00 0.00 0.00

125 F&B P107 GF 16 16 0 11.76 11.76 12.35 8.64

126 F&B P108 GF 16 16 0 11.76 11.76 12.35 8.64

127 F&B P109 GF 16 16 0 11.76 11.76 12.35 8.64

128 F&B P110 GF 16 16 0 11.76 11.76 12.35 8.64

129 F&B P111 GF 16 16 0 11.76 11.76 12.35 8.64

130 F&B P112 GF 71 71 28 52.19 52.19 54.79 38.36

131 F&B P113 GF 71 71 28 52.19 52.19 54.79 38.36

132 F&B P114 GF 71 71 28 52.19 52.19 54.79 38.36

133 F&B P115 GF 71 71 27 52.19 52.19 54.79 38.36

B101 GF 227 208 186.61 186.61 195.94 137.15


134 F&B 473
B201 FF 246 95 66.84 66.84 70.18 49.12
B102 GF 227 205 186.32 186.32 195.64 136.95
135 F&B 473
B202 FF 246 95 66.84 66.84 70.18 49.12

136 F&B B103 GF 116 116 85.26 85.26 89.52 62.67

137 F&B B104 GF 117 117 86.00 86.00 90.29 63.21

Estimated Electrical Loads


for Public and MEP
138 2000 1000.00 750.00
Equipment
Kva

GROSS TOTAL 52,446.00 21139

Consider 20% Spare


Loads on Gross Total 20% 4228
Connected Load kVA

Total Connected Load


25367
kVA

Demand On TR SS
based on Average 70% 7610
Coinsident Factors Sec

Gross Total After


Diversity on TR SS 17757
kVA

Demand On MVSG
0.9X0.9 81% 3374
AS per Sec

Gross Total After


Diversity on MVSG 14383
kVA

MEP LOADS ASSESSMENT REV E SEP 2021 4
SABBOUR CONSULTING OFFICE MEP LOAD ASSESSMENT CORNICHE JEDDAH WATERFRONT DEVELOPMENT

SEC INDEX

Electrical Load Electrical Load


Total
Outdoor GROUND FLOOR FIRST FLOOR Total
Electrical Load After
Air-Conditioned Area 735 VA/M2 FOR 235 V/M2 FOR Total Electrical Load After
Unit Number / Reference GROSS NLA Taking Demand 70% for
Area (Leasable Indoor Indoor Electrical Load adding 5% on load
F&B And 80% for
area) 95VA/M2 for 95VA/M2 for for future
Cinemas As per SEC
Outdoor Outdoor
Sr No Floor

Total Total
Ref Ref Sq. meters Sq. meters Sq. meters kVA kVA kVA
kVA kVA

3rd Option, but it is not advisable as the electrical HVAC loads are significat and the given figures are unde
NOTES:

1- ALL AREAS MENTIONED ABOVE HAVE BEEN TAKEN FROM THE


RECEIVED AREA SCHEDULE DATED 20TH OF SEP 2021 ( ANY UPDATE ON
THE AREA SCHEDULE WILL CAUSE CHANGING IN THE COOLING LOADS
AND ELECTRICAL POWER

* increasing the risk on the Landlord when the Demand usage considered at the LV side
2- THE COOLING INDEX ESTIMATED ABOVE WILL BE VALIDATED BY
HEAT LOAD CALCULATIONS, BUT THE ABOVE WILL BE USED FOR
SPACE PLANNING PURPOSES. SPACE PLANNING WILL BE TUNNED
DURING THE DESIGN DEVELOPMENT

3- THE COOLING INDEXES MENTIONED ABOVE CONSIDERS AT EDGE


WHICH IS IMPORTANT TO ADDRESS THE FOLLOWING:

a. THE FRONT VIEW GLASS PANEL SHALL BE SELECTED TO MEET


SCHADING COEFFICIENT 0.25 UP TO 0.32 MAXIMUM AND THE U VALUE
1.3W/M ² . K ° 
b. ROOF SHALL BE COVERED BY WEIGHT GRAVEL FOR REDUCING THE

* the electrical of HVAC loads are under-estimation


ENERGY HEAT GAIN

c. AIR CURTAIN SHALL BE FURNISHED BY TENANT AT ACCESS DOOR


FOR REDUCING THE INFILTRATION LOAD AS POSSIBLE AND ENSURE IT
SHALL NOT EXCEED 0.15ACH

3- THE BOH FOR COOKING WILL BE LIMITED TO GF ONLY; TENANT CAN

Not Advisable Option due to:


USE A PERCENATAGE 15% OF THE FIRST FLOOR NLA FOR NON
COOKING FACILITY

4- SO AS TO ACHIEVING 25MVA FOR THIS DEVELOPMENT; 80%


DIVERSITY VALUE HAS BEEN CONSIDERED IN BOTH MVSG AND ON SS.
FOR COMMERCIAL PURPOSES; SUCH

estimation
DIVERSITY SHOULD BE APPLIED BUT TO MEET THE CEILING OF SCECO
(SEC), SUCH DIVERSITY TO BE APPILED. OUR CONSIDERATION SHALL
BE DISCUSSED WITH SEC AND CONSENT

5- SAB ESTIMATED ABOUT 3MVA ELECTRICAL DEMAND FOR ALL MEP


EQUIPMENT AND PUBLIC AMINITIES INCLUDING 25KVA POP-UP
ELECTRICAL RETRACTABLE DISTRIBUTED THROUGHOUT THE
WATERFRONT PROMENADE

6- IT IS IMPORTANT TO ADDRESS THAT TO MINIMIZE ANY RISK IN


FUTURE AND ALLOW FOR CERTAIN SORT OF FLEXIBILITY TO LEASING
DEPARTMENT,

SAB MAY PROPOSE THE FOLLOWING:


a. CONVERT ADDITIONAL PERCENTAGE ABOUT 10% OF F&B UNITS TO CA

b. SMOKING FACILITY INSIDE AIR CONDITIONED SPACE TO BE


PROHABITED OR RATIONALIZED AS POSSIBLE TO AVOID MORE
ELECTRICAL DEMAND

MEP LOADS ASSESSMENT REV E SEP 2021 5