PROJECT TITLE : EPC FASILITAS PENANGANAN BATUBARA TAHAP - IV DOC.

NO : BA4-BB-CS-E-CSC-002
SUB TITLE : ELECTRICAL CALCULATION OF CABLE SIZING ISSUED DATE : 07/02/2017
PACKAGE : ELECTRICAL & INSTRUMENT REVISION :-
SUB PACKAGE : ELECTRICAL PREP. BY : ARS
LOCATION : SOUTH SUMATERA CHECK. BY : AF
CLIENT : PT. BUKIT ASAM APP. BY : DN
400V AC THREE PHASE SUPPLY RL-LP

Equipment INCOMING RLLP-1RST(1) RLLP-1RST(2) EXS-RLLP-1X RLLP-2RST(1) RLLP-2RST(2)


(Cable No)

Total Load kW 12 10.1 4.9 0.1 10.0 5.2


Voltage V 400 400 400 220 400 400
Power Factor % 0.85 0.85 0.85 0.85 0.85 0.85
Power Factor Angle Rad 0.55 0.55 0.55 0.55 0.55 0.55
Full Load Current A 20 17 8 0.37 17 9
Length of Cable m 422 735 630 8 735 665
Cable Ampacity 0
Cable Installation Air, Cable Trench Air, Cable Ladder Air, Cable Ladder Air, Cable Trench Air, Cable Ladder Air, Cable Ladder
Cable Current De-rating Factor 0.78 0.78 0.78 0.78 0.78 0.78
Cable Size mm2 35 25 16 2.5 25 16
Nominal Current A 129 102 72 26 105 79
Number of Cables No. 1 1 1 1 1 1
Circuit Current 101 80 56 20 82 62
OK OK OK OK OK OK
Cable Voltage Drop (Running) 0
Resistance ohms/km 0.627 1.200 1.910 8.866 1.200 1.910
Reactance ohm/km 0.077 0.080 0.080 0.095 0.080 0.080
Circuit Reistance ohm/km 0.627 1.200 1.910 8.866 1.200 1.910
Circuit Reactance ohm/km 0.077 0.080 0.080 0.095 0.080 0.080
Voltage Drop Volts / phase 4.93 13.39 8.73 0.05 13.26 9.78
Voltage Drop (%) % 1.23 3.35 2.18 0.02 3.31 2.45
Total Voltage Drop (%) % 1.56 4.91 3.74 4.93 4.87 4.00
OK OK OK OK OK OK
Cable Voltage Drop (Starting) 0
power factor % - - - - - -
Power Factor Angle Rad - - - - - -
Starting Current A - - - - - -
Voltage Drop Volts / phase - - - - - -
Volt Drop (%) (Must be <15% %
Overall) - - - - - -
- - - - - -
Cable Fault Level
Prospective Short Circuit i 0.642 1.1 1.1 - 1.1 1.1
Duration Of Short Circuit s 0.25 0.25 0.25 - 0.25 0.25
Temperature Rise Constant k 115 155 155 - 155 155
Minimum Cross Sectional mm2 2.79 3.55 3.55 - 3.55 3.55
OK OK OK - OK OK
OVERALL RESULT OK OK OK OK OK OK

Installation Method:
LV cable on air/trench/ladder single core trefoil maximum 9 groups, touching, derating factor = 0.85
LV cable on air/trench/ladder multicore core maximum 9 groups, touching, derating factor = 0.78
PROJECT TITLE : EPC FASILITAS PENANGANAN BATUBARA TAHAP - IV DOC. NO : BA4-BB-CS-E-CSC-002
SUB TITLE : ELECTRICAL CALCULATION OF CABLE SIZING ISSUED DATE : 07/02/2017
PACKAGE : ELECTRICAL & INSTRUMENT REVISION :-
SUB PACKAGE : ELECTRICAL PREP. BY : ARS
LOCATION : SOUTH SUMATERA CHECK. BY : AF
CLIENT : PT. BUKIT ASAM APP. BY : DN
400V AC THREE PHASE SUPPLY RL-LP

Equipment BXB-RLLP-2X
(Cable No)

Total Load kW 0.4


Voltage V 220
Power Factor % 0.85
Power Factor Angle Rad 0.55
Full Load Current A 2.14
Length of Cable m 5
Cable Ampacity
Cable Installation Air, Cable Trench
Cable Current De-rating Factor 0.78
Cable Size mm2 2.5
Nominal Current A 26
Number of Cables No. 1
Circuit Current 20
OK
Cable Voltage Drop (Running)
Resistance ohms/km 8.866
Reactance ohm/km 0.095
Circuit Reistance ohm/km 8.866
Circuit Reactance ohm/km 0.095
Voltage Drop Volts / phase 0.16
Voltage Drop (%) % 0.07
Total Voltage Drop (%) % 4.95
OK
Cable Voltage Drop (Starting)
power factor % -
Power Factor Angle Rad -
Starting Current A -
Voltage Drop Volts / phase -
Volt Drop (%) (Must be <15% %
Overall) -
-
Cable Fault Level
Prospective Short Circuit i -
Duration Of Short Circuit s -
Temperature Rise Constant k -
Minimum Cross Sectional mm2 -
-
OVERALL RESULT OK

Installation Method:
LV cable on air/trench/ladder single core trefoil maximum 9 groups, touching, derating factor = 0.85
LV cable on air/trench/ladder multicore core maximum 9 groups, touching, derating factor = 0.78