DB1-GF, LOCATION: Gnd FLOOR, FEED FROM: LT PANEL-GF From SLD: Page-07

Main Incoming Ckt. Breaker: Main Incoming Cable:


Phase Earth Size No. of Watt Per Total Phase Load in Watt Remarks
CKT No. CKT Ref. MCCB/MCB Rat/Amp. Load Type Point Reference Location
Neutral (re) Points/ Point Watt R Y B
1 R1 10 A SP MCB 2.5 BYA 2.5 BYA LIGHT L(5)+F(3) 5+3 40+100 500 400 4.69A
2 Y1 10 A SP MCB 2.5 BYA 2.5 BYA LIGHT L(5)+F(2) 5+2 40+100 400 400 3.75A
3 B1 16 A SP MCB 2.5 BYA 2.5 BYA P.SOCKET Q(1)+Q(2)+Q(3) 3 500 1500 1500 14.06A
4 R2 16 A SP MCB 2.5 BYA 2.5 BYA P.SOCKET Q(4)-Q(7) 4 500 2000 2000 18.74A
5 Y2 16 A SP MCB 2.5 BYA 2.5 BYA G-1 G-1 1 1000 1000 1000 9.37A
6 B2 20 A SP MCB 4 BYA 2.5 BYA AC SOCKET T1 1 1300 1300 1300 12.18A
7 R3 20 A SP MCB 4 BYA 2.5 BYA AC SOCKET T2 1 1300 1300 1300 12.18A
8 Y3 16 A SP MCB 2.5 BYA 2.5 BYA OTHER T4 1 1000 1000 1000 9.37A
9 B3 16 A SP MCB 2.5 BYA 2.5 BYA SPACE SPACE 1 1000 1000 1000 9.372
Electrical Load per phase 3700 2400 3800
Total Electrical Load 9900
Total Electrical Load 9.9
Total Design current, Id 17.82
Risk Factor 1.5
Final, If 26.73
Phase Balance 37%