SITE TEST REPORT

Site Test Report of M/s Adani Wind Energy Kutch One Ltd,
555MW Wind Projects, Nakhatrana, Kutchh, Gujarat.
CAPACITOR BANK-
1. Customer : M/s Adani Wind Energy Kutch one Ltd
2. Bank Ref :
3. System Voltage : 33kV
4. Bank size : 10+10+5 MVAR
5. Date :

LAY OUT AND CLEARANCE:

1. CONFORMITY WITH APPROVED DWG : OK

2. VISUAL INSPECTION OF INSULATORS : OK

BUSBARS AND CONNECTORS:

1. EXTERNAL CONDITION :OK

2. TIGHTNESS OF CONNECTIONS :OK

EARTH RESISTANCE:

1. WITH GRID : Ω

2. WITHOUT GRID : Ω

CAPACITOR BANK-1
TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

INSULATION RESISTANCE MEASUREMENT: (At 5 kV) 1min


1. A. Including Bus bar, Star connected Capacitor, Reactor: All Value in GΩ

Sr.No. Reference 5 MVAR IR Value 10 MVAR IR Value 10MVAR IR Value


1. R-E 18.3 21.4 20.8
2. Y-E 16.5 22.0 21.9
3 B-E 17.4 22.8 23.0

B. INCOMER BPI AND OUTGOING BPI 5MVAR: All Value in GΩ

Reference Incomer IR Value Outgoing IR Value Reference Phase IR


BPI BPI Value
Top-Earth R1 13.4 R1 17.1 R 20.4
Top-Earth R2 12.5 R2 16.2 Cap. Frame Y 21.4
Top-Earth Y1 14.3 Y1 15.4 to Earth B 22.4
Top-Earth Y2 12.5 Y2 13.9
Top-Earth B1 14.3 B1 14.9
Top-Earth B2 15.3 B2 15.3

C. INCOMER BPI AND OUTGOING BPI 10MVAR:

Reference Incomer IR Value Outgoing IR Value Reference Phase IR


BPI BPI Value
Top-Earth R1 15.2 R1 18.1 R 23.9
Top-Earth R2 14.8 R2 17.2 Cap. Frame Y 24.1
Top-Earth Y1 16.2 Y1 16.2 to Earth B 21.5
Top-Earth Y2 15.9 Y2 15.9
Top-Earth B1 17.1 B1 16.8
Top-Earth B2 14.9 B2 17.3
D. INCOMER BPI AND OUTGOING BPI 10MVAR: All Value in GΩ

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Reference Incomer IR Value Outgoing IR Value Reference Phase IR


BPI BPI Value
Top-Earth R1 15.3 R1 17.1 R 19.5
Top-Earth R2 16.3 R2 16.8 Cap. Frame Y 20.9
Top-Earth Y1 16.4 Y1 17.5 to Earth B 20.3
Top-Earth Y2 17.3 Y2 16.9
Top-Earth B1 18.4 B1 15.8
Top-Earth B2 19.3 B2 14.3

2. CAPACITOR NAME PLATE DETAILS:


S.NO. Ratings (5 Mvar) Ratings (10 Mvar)

Make Hitachi Energy Company Hitachi Energy Company

Capacitance (µF) 13.74 13.74

Type CHD CHD


Nominal Current (A) 48.1 48.1

Year of Manufacturing 2022 2022

Reactive Power 536.33 536.33


(KVAR)
Standard IEC 60871-1 IEC 60871-1

Nominal voltage (V) 11148 11148

Frequency (Hz) 50 50

Phase 1 1

Weight (kg) 67 67

Fuses Internal Internal

Discharge Device Internal Internal

Ins. Level,Ui kV 28/75 28/75

Temp.Cat O/C ͦC O/C ͦC

A: CAPACITANCE MEASUREMENT in Micro Farad: BANK-S1(10MVAR): All Value in GΩ

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Reference Serial No. Tolerance Capacitance R1 side R1+R2 IR


All values in Total Total Value
µF
1 AD22128-2097 +4 14.11 12.5
2 AD22128-2160 +5 14.26 11.4
R1-ph
3 AD22128-2226 +4 14.03 13.9
4 AD22128-2434 +5 14.14 14.3
1 AD22128-2358 +4 13.78 12.5
2 AD22128-2157 +5 13.93 14.4
R2-ph
3 AD22128-2465 +4 13.85 13.5
4 AD22128-2167 +5 13.96 14.8
1 AD22128-2347 +4 14.22 13.5
2 AD22128-2433 +5 13.94 14.3
Y1-ph
3 AD22128-2072 +4 13.82 16.2
4 AD22128-2497 +5 13.80 15.8
1 AD22128-2339 +5 13.78 19.2
2 AD22128-2410 +4 13.80 20.4
Y2-ph
3 AD22128-2184 +4 13.67 18.4
4 AD22128-2454 +4 13.82 19.2
1 AD22128-2215 +4 14.15 18.3
2 AD22128-2165 +5 14.26 21.4
B1-ph
3 AD22128-2423 +4 14.15 20.5
4 AD22128-2152 +5 14.19 22.3
1 AD22128-2246 +5 14.10 17.4
2 AD22128-2436 +4 14.22 16.9
B2-ph
3 AD22128-2337 +5 14.11 17.3
4 AD22128-2409 +4 14.15 18.4

B.CAPACITANCE MEASUREMENT in Micro Farad: BANK-S2(10MVAR): All Value in GΩ

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Reference Serial No. Tolerance Capacitance R1 side R1+R2 IR


All values in Total Total Value
µF
1 AD22128-2353 +4 14.01 18.9
2 AD22128-2177 +5 14.21 19.2
R1-ph
3 AD22128-2228 +4 14.05 18.4
4 AD22128-2126 +5 14.10 21.0
1 AD22128-2235 +4 14.06 17.9
2 AD22128-2169 +5 14.18 16.5
R2-ph
3 AD22128-2115 +4 13.96 18.4
4 AD22128-2318 +5 14.07 14.5
1 AD22128-2082 +4 24.09 17.2
2 AD22128-2304 +5 24.21 15.4
Y1-ph
3 AD22128-2313 +4 14.10 16.3
4 AD22128-2156 +5 14.24 17.4
1 AD22128-2206 +4 14.24 16.5
2 AD22128-2420 +5 13.96 18.4
Y2-ph
3 AD22128-2209 +4 14.06 19.2
4 AD22128-2338 +5 14.11 20.5
1 AD22128-2405 +4 14.27 20.3
2 AD22128-2312 +5 14.21 21.9
B1-ph
3 AD22128-2357 +4 14.06 19.5
4 AD22128-2180 +6 14.52 21.4
1 AD22128-2229 +4 13.15 21.8
2 AD22128-2323 +5 14.04 21.9
B2-ph
3 AD22128-2134 +4 14.03 22.8
4 AD22128-2164 +5 14.12 20.9

C: CAPACITANCE MEASUREMENT in Micro Farad: BANK-S3(5MVAR):

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Reference Serial No. Tolerance Capacitance R1 side R1+R2 IR


All values in Total Total Value
µF
1 AD22128-2305 +3 13.90 21.8
R1-ph
2 AD22128-2412 +6 14.14 19.5
1 AD22128-2320 +4 13.99 20.6
R2-ph
2 AD22128-2261 +5 14.11 20.1
1 AD22128-2301 +4 13.13 17
Y1-ph
2 AD22128-2332 +5 13.25 18.2
1 AD22128-2327 +4 13.78 19.5
Y2-ph
2 AD22128-2307 +5 13.88 20.4
1 AD22128-2493 +4 14.16 18.9
B1-ph
2 AD22128-2372 +5 14.10 19.1
1 AD22128-2190 +4 13.78 20.0
B2-ph
2 AD22128-2092 +5 23.81 17.8

3. REACTOR NAME PLATE DETAILS:

Sr.No. Ratings
5 MVAR 10 MVAR-1 10 MVAR-2
Make Shrihans Electricals Pvt. Ltd.
Impedance/Phase (Ω) 14.73 7.23 7.23
Type Dry Dry Dry
Nominal Current (A) 96.23 192.45 192.45
Year of Manufacturing 2023 2023 2022
Reactive Power (KVAR) 128.74 257.44 257.44
Standard IS 5553 Part-3 1990 IS 5553 Part-3 IS 5553 Part-3
1990 1990
Nominal voltage (V) 33000 33000 33000
Frequency (Hz) 50 50 50
Phase 1 1 1

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Type of Cooling AN AN AN
Class of Insulation F F F
B.I.L (kV/kvp) 70/170 70/170 70/170
Weight (kg) 320 480 480
S.T.C for 2 sec (kA) 1.57 3.20 3.20

A. INDUCTANCE MEASURMENT in milli Henry: 10MVAR-1


Serial No. Phase Inductance IR Value
U33578 R 22.5mH 19.5 GΩ
V33583 Y 20.9mH 15.8 GΩ
W33578 B 21.4mH 16.2 GΩ

B. INDUCTANCE MEASURMENT in milli Henry: 10MVAR-2


Serial No. Phase Inductance IR Value
U33579 R 20.5mH 17.2 GΩ
V33579 Y 22.5mH 14.5 GΩ
W33579 B 21.8mH 13.9 GΩ

C.INDUCTANCE MEASURMENT in milli Henry:5MVAR


Serial No. Phase Inductance IR Value
U33570 R 42.4mH 12.8 GΩ
V33570 Y 44.5mH 14.3 GΩ
W33572 B 43.8mH 14.9 GΩ

4. CURRENT STABILITY TEST: (10MVAR)

A. Stability test 10MVAR Bank-S1:


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

NCT
Applied Voltage Current
Secondary
R Y B
R-Y Y-B B-R
(Amps) (Amps) (Amps)

410 410 410

C: Stability test 10MVAR Bank-S2:


NCT
Applied Voltage Current
Secondary
R Y B 0.0
R-Y Y-B B-R
(Amps) (Amps) (Amps)

410 410 410 0.075 0.074 0.075

Stability test 5 MVAR Bank-S3:


NCT
Applied Voltage Current
Secondary
R Y B 0.0
R-Y Y-B B-R
(Amps) (Amps) (Amps)

410 410 410 0.031 0.032 0.031

TEST REPORT OF CURRENT TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1- MAIN CT

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG. (P) LTD, BHIVADI (RAJ.)

Rated voltage : 36 KV

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Sr. No. : R-Phase: 0C12982/1/14/23 , Y-Phase: 0C12982/1/16/23

B-Phase :0C12982/1/21/23

Year of Manufacture : R-Phase: 2023, Y-Phase: 2023, B-Phase: 2023

Core Ratio Class Protection / Metering

CORE-1 800/1 0.2S 1S1-1S2 METERING

CORE-2 800/1 5P 2S1-2S2 PROTECTION

1. INSULATION RESISTANCE MEASUREMENT :


(Value Taken at 5kV for 1 min)

Phase
Core
R- Phase Y- Phase B-Phase

Primary – Earth 23.8 17.7 33.6


Primary-core1 21.6 15.6 29.7
Primary – Core 2 30.9 18.1 31.7

(Value Taken at 500V for 1 min)

Core 1 – Core2 >1 GΩ >1 GΩ >1 GΩ


Core 2-Core3 >1 GΩ >1 GΩ >1 GΩ
Core 1 –Earth >1 GΩ >1 GΩ >1 GΩ
Core2-Earth >1 GΩ >1 GΩ >1 GΩ

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

2. WINDING RESISTANCE MEASUREMENT:

CORE R PHASE Y PHASE B PHASE

1S1-1S2 3.8 3.8 3.9


2S1-2S2 5.4 5.6 5.5

3. POLARITY TEST:

Between Phase
Core
Terminal R- Phase Y- Phase B-Phase

Core – 1 1S1 – 1S2 Forward Forward Forward

Core – 2 2S1 – 2S2 Forward Forward Forward

4. RATIO TEST:

Core CT RATIO CT
[A] CURRENT Measured CT sec. current (mA)
INJECT.(A)

CORE R Y B

CORE – 1 800/1 100 0.125 0.126 0.125

1S1 -1S2 200 0.251 0.250 0.250

300 0.375 0.374 0.375

CORE – 2 800/1 100 0.124 0.125 0.126

2S1 - 2S2 200 0.251 0.252 0.250

300 0.376 0.375 0.375

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

TEST REPORT OF VOLTAGE TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1 - MAIN PT

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG.(P) LTD,BHIVADI (RAJ)

Rated voltage : 36 KV

Sr. No. : R-Phase: 12982/4/3/25 Y-Phase: 12982/4/16/23

B-Phase: 12982/4/9/23

Year of Manufacture : R-Phase: 2023, Y-Phase: 2023, B-Phase: 2023

Core Ratio Class Protection / Metering

CORE-1 33KV√3/110√3 0.2 1a-1n METERING


1. INSULA
TIO CORE-2 33KV√3/110√3 3P 2a-2n PROTECTION N
RESISTAN
CE
MEASUREMENT :
(Value Taken at 5kV for 1 min.)

Phase
Core
R- Phase Y- Phase B-Phase

Primary – Earth 25.7 26.8 25.9

Primary-core1 22.8 21.5 23.9

Primary – Core 2 20.9 22.5 22.8

(Value Taken at 500V for 1 min.)


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Core 1 – Core2 >1 GΩ >1 GΩ >1 GΩ


Core 1 –Earth >1 GΩ >1 GΩ >1 GΩ
Core2-Earth >1 GΩ >1 GΩ >1 GΩ

2. WINDING RESISTANCE MEASUREMENT:

CORE R PHASE Y PHASE B PHASE

1a-1n 0.8 Ω 0.7 Ω 0.9 Ω

2a-2n 0.8 Ω 0.8 Ω 0.7 Ω

3. POLARITY TEST

Between Phase
Core
Terminal R- Phase Y- Phase B-Phase

1a – 1n Forward Forward Forward


Core – 1

2a – 2n Forward Forward Forward


Core – 2

4. RATIO TEST :

Core PT RATIO (V) PT VOLTAGE


Measured PT SEC. VOLTAGE
INJEC(V)

CORE R Y B

1a -1n 33KV√3/110√3

2a -2n 33KV√3/110√3

TEST REPORT OF L A

FEEDER /BAY NAME : CAPACITOR BANK 3 - LIGHTING ARESSTOR


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

MAKE : OBLUM

Rated voltage : 36 KV

Sr. No. : R- NA Y-NA B-NA

1. INSULATION RESISTANCE MEASUREMENT :


(Value Taken at 5kV for 1 min.)

Phase
PRIMARY-E
R Y B

TOP-EARTH 20.5 GΩ 19.8 GΩ 25.8 GΩ

Earthing- Check All Phase R, Y, B lighting arrester is OK

TEST REPORT OF CURRENT TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1- 10 MVAR CT-2

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG. (P) LTD, BHIVADI (RAJ)

Rated voltage : 36 KV

Sr. No. : R-Phase:,OC12982/2/57/23 Y-Phase OC12982/2/61/23


B –Phase : OC12982/2/41/23

Year of Manufacture : R-Phase: 2023, Y-Phase: 2023, B-Phase: 2023

Core Ratio Class Protection / Metering

CORE-1 300/1 0.2S 1S1-1S2 METERING


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
CORE-2
NAME: ABHISEK BEHURA 300/1 5P20 NAME: 2S1-2S2 PROTECTION
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

1. INSULATION RESISTANCE MEASUREMENT:


(Value Taken at 5kV for 1 min)

Phase
Core
R- Phase Y- Phase B-Phase

Primary – Earth 54.3 GΩ 55.5 GΩ 53.0 GΩ

Primary-core1 50.5 GΩ 49.3 GΩ 49.8 GΩ

Primary – Core 2 47.3 GΩ 48.9 GΩ 48.0 GΩ

(Value Taken at 500V for 1 min)

Core 1 – Core2 >1.0 GΩ >1.0 GΩ >1.0 GΩ

Core 1 –Earth >1.0 GΩ >1.0 GΩ >1.0 GΩ

Core2-Earth >1.0 GΩ >1.0 GΩ >1.0 GΩ

2. WINDING RESISTANCE MEASUREMENT:

CORE R PHASE Y PHASE B PHASE

1S1-1S2 3.8 3.9 3.9

2S1-2S2 7.1 7.3 7.3

3. POLARITY TEST

Between Phase
Core
Terminal R- Phase Y- Phase B-Phase

Core – 1 1S1 – 1S2 Forward Forward Forward


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA
Core – 2 2S1 – 2S2 Forward NAME:
Forward Forward
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

4. RATIO TEST :

Core CT RATIO CT CURRENT


Measured CT sec. current (mA)
[A] INJEC(A)

CORE R Y B

CORE – 1 300 100 0.383 0.334 0.333

1S1 -1S2 200 0.667 0.666 0.665

300 1.001 1.000 1.001

CORE – 2 300 100 0.334 0.333 0.335

2S1 - 2S2 200 0.667 0.666 0.665

300 1.001 1.001 1.000

TEST REPORT OF CIRCUIT BREAKER 10MVAR-2

FEEDER /BAY NAME : CAPACITOR BANK 1-10 MVAR CB

CUSTOMER : ADANI GREEN ENERGY LTD.

Sr. No. : 1VYN030123000213

NAME PLATE DETAILS:

Make : ABB

STANDARD : IEC62271-100

HIGHER SYSTEM VOLTAGE : 40.5 KV


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

SERVICE VOLTAGE : 40.5 KV

RATED CURRENT : 630 A

RATED FREQUENCY : 50Hz

BASIC INSULATION LEVEL : 70 KV/ 170 KV pk

SHORT CIRCUIT BREAKING CURRENT : 31.5 kA /3 sec.

SHORT CURCUIT MAKING CURRENT : 82 kA pk

MINIMUM CREEPAGE : 1116 mm

CONTROL VOLTAGE : 220 V DC

SPRING CHARGE MOTOR SUPPLY VOLTAGE : 230 V AC

AUXILIARY SUPPLY VOLTAGE : 230 V AC

PAINT SHADE : 631 OF IS (LIGHT GREY)

ENCLOSURE FABRICATION MATERIAL TYPE : MS- HR

ENCLOSURE FABRICATION MATERIAL THICKNESS : 2.5 MM

SUPPORT STRUCTURE TYPE : VCB MOUNTING STRUCTURE

TERMINAL CONNECTOR (REQD. IF ANY) : IN HITACHI SCOPE

1. INSULATION RESISTANCE MEASUREMENT :


(Value Taken at 5kV for 1 min)

MODE R (GΩ) Y (GΩ) B (GΩ)

OPEN

TOP TO MIDDEL 48.6GΩ 56.0 GΩ 39.5 GΩ

CLOSE

PHASE TO EARTH 45.8 GΩ 63.5 GΩ 56.4 GΩ

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

2. TIMING MEASUREMENT (Millisecond) : kit used : SCOPE timings


REFERENCE R (ms) Y (ms) B (ms)

COIL-1

CLOSE-1 80 80 80

TRIP-1 42 42 42

C-O-1 41 41 41

COIL-2

CLOSE-2 79 79 78

TRIP-2 42 43 42

C-O-2 43 44 44

3. CONTACT RESISTANCE MEASUREMENT : kit used: SCOPE CRM100C


(Temp.: - 40°C)

PHASE R – PH Y –PH B – PH

CRM(µΩ) 22.3 25.6 22.6

4. COIL RESISTANCE MEASUERMENT

CLOSING COIL 223.6Ω

TRIP COIL 1 233.6Ω

TRIP COIL 2 231.6Ω

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

TEST REPORT OF NEUTRAL CURRENT TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1 - 10 MVAR NCT

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG.(P) LTD,BHIVADI (RAJ.)

Rated voltage : 36 KV

Sr. No. : NCT: - OC12982/3/6/23

Year of Manufacture : 2023,

Core Ratio Class Protection / Metering

CORE-1 5/1 5P20 1S1-1S2 PROTECTON

1. INSULATION RESISTANCE MEASUREMENT:


(Value Taken at 5kV for 1 min)

Core
NCT

Primary – Earth 28.9

Primary-core 27.5

CORE – EARTH 500V >1 GΩ

2. WINDING RESISTANCE MEASUREMENT:


(Value Taken at 500V for 1 min)

CORE NCT PHASE

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

1S1-1S2 2.1

3. POLARITY TEST

Between
Core NCT PHASE
Terminal

Core – 1 1S1 – 1S2 FORWORD

4. RATIO TEST :

Core CT RATIO [A] CT CURRENT Measured CT sec. current (mA)


INJEC(A)

CORE

CORE - 1 5/1 1 0.201

1S1 -1S2 2 0.400

3 0.601

TEST REPORT OF CURRENT TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1- 10 MVAR CT-1

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG. (P) LTD, BHIVADI (RAJ)

Rated voltage : 36 KV

Sr. No. : R-Phase:, OC12982/2/10/23 Y-Phase: OC12982/2/13/23

B-Phase: OC12982/2/18/23

Year of Manufacture : R-Phase: 2023, Y-Phase: 2023, B-Phase: 2023

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Core Ratio Class Protection / Metering

CORE-1 300/1 0.2S 1S1-1S2 METERING

CORE-2 300/1 5P20 2S1-2S2 PROTECTION

1. INSULATION RESISTANCE MEASUREMENT:


(Value Taken at 5kV for 1 min)

Phase
Core
R- Phase Y- Phase B-Phase

Primary – Earth 66.7 68.5 71.3

Primary-core1 50.3 53.4 55.1

Primary – Core 2 48.3 47.8 48.9

(Value Taken at 500V for 1 min)

Core 1 – Core2 >1.0 GΩ >1.0 GΩ >1.0 GΩ

Core 1 –Earth >1.0 GΩ >1.0 GΩ >1.0 GΩ

Core2-Earth >1.0 GΩ >1.0 GΩ >1.0 GΩ

5. WINDING RESISTANCE MEASUREMENT:

CORE R PHASE Y PHASE B PHASE

1S1-1S2 3.8 3.9 3.9

2S1-2S2 7.4 7.4 7.6

6. POLARITY TEST

Between Phase
Core
Terminal R- Phase Y- Phase B-Phase

Core – 1 1S1 – 1S2 Forward Forward Forward


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA
Core – 2 2S1 – 2S2 Forward NAME:
Forward Forward
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

7. RATIO TEST :

Core CT RATIO CT CURRENT


Measured CT sec. current (mA)
[A] INJEC(A)

CORE R Y B

CORE – 1 300 100 0.34 0.37 0.35

1S1 -1S2 200 0.67 0.68 0.68

300 1.01 1.02 0.99

CORE – 2 300 100 0.35 0.36 0.37

2S1 - 2S2 200 0.67 0.69 0.66

300 1.02 1.01 1.02

TEST REPORT OF CIRCUIT BREAKER

FEEDER /BAY NAME : CAPACITOR BANK 1-10 MVAR CB

CUSTOMER : ADANI GREEN ENERGY LTD.

Sr. No. : 1VYN030123000208

NAME PLATE DETAILS:

Make : ABB

STANDARD : IEC62271-100

HIGHER SYSTEM VOLTAGE : 40.5 KV

SERVICE VOLTAGE : 40.5 KV


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

RATED CURRENT : 630 A

RATED FREQUENCY : 50Hz

BASIC INSULATION LEVEL : 70 KV/ 170 KV pk

SHORT CIRCUIT BREAKING CURRENT : 31.5 kA /3 sec.

SHORT CURCUIT MAKING CURRENT : 82 kA pk

MINIMUM CREEPAGE : 1116 mm

CONTROL VOLTAGE : 220 V DC

SPRING CHARGE MOTOR SUPPLY VOLTAGE : 230 V AC

AUXILIARY SUPPLY VOLTAGE : 230 V AC

PAINT SHADE : 631 OF IS (LIGHT GREY)

ENCLOSURE FABRICATION MATERIAL TYPE : MS- HR

ENCLOSURE FABRICATION MATERIAL THICKNESS : 2.5 MM

SUPPORT STRUCTURE TYPE : VCB MOUNTING STRUCTURE

TERMINAL CONNECTOR (REQD. IF ANY) : IN HITACHI SCOPE

1. INSULATION RESISTANCE MEASUREMENT :


(Value Taken at 5kV for 1 min)

MODE R (GΩ) Y (GΩ) B (GΩ)

OPEN

TOP TO MIDDEL 41.6G0Ω 56.0 GΩ 59.5 GΩ

CLOSE

PHASE TO EARTH 43.8 GΩ 53.5 GΩ 46.4 GΩ

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

2. TIMING MEASUREMENT (Millisecond) : kit used : SCOPE timings


REFERENCE R (ms) Y (ms) B (ms)

COIL-1

CLOSE-1 80 80 80

TRIP-1 41 42 41

C-O-1 41 41 41

COIL-2

CLOSE-2 79 79 78

TRIP-2 42 43 42

C-O-2 43 43 43

3. CONTACT RESISTANCE MEASUREMENT : kit used: SCOPE CRM100C


(Temp.: - 40°C)

PHASE R – PH Y –PH B – PH

CRM(µΩ) 23.3 23.6 22.6

4. COIL RESISTANCE MEASUERMENT

CLOSING COIL 213.6Ω

TRIP COIL 1 223.6Ω

TRIP COIL 2 230.6Ω

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

TEST REPORT OF NEUTRAL CURRENT TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1- 10 MVAR NCT-1

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG.(P) LTD,BHIVADI (RAJ.)

Rated voltage : 36 KV

Sr. No. : NCT: OC12982/3/2/23

Year of Manufacture : 2023,

Core Ratio Class Protection / Metering

CORE-1 5/1 5P20 1S1-1S2 PROTECTON

1. INSULATION RESISTANCE MEASUREMENT:


(Value Taken at 5kV for 1 min)

Core
NCT

Primary – Earth 42.3

Primary-core 40.0

CORE – EARTH >1.0 GΩ

3. WINDING RESISTANCE MEASUREMENT:


(Value Taken at 500V for 1 min)

CORE NCT PHASE

1S1-1S2 2.1

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

3. POLARITY TEST

Between
Core NCT PHASE
Terminal

Core – 1 1S1 – 1S2 FORWORD

4. RATIO TEST :

Core CT RATIO [A] CT CURRENT Measured CT sec. current (mA)


INJEC(A)

CORE

CORE - 1 5/1 1 0.201

1S1 -1S2 2 0.400

3 0.601

TEST REPORT OF CURRENT TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1 - 5 MVAR CT

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG. (P) LTD, BHIVADI (RAJ.)

Rated voltage : 36 KV

Sr. No. : R-Phase: OC12982/2/33/23 Y-Phase, OC12982/ 2/53/23

B-Phase OC12982/2/34/23

Year of Manufacture : R-Phase: 2023, Y-Phase: 2023, B-Phase: 2023

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Core Ratio Class Protection / Metering

CORE-1 300/1 0.2S 1S1-1S2 METERING

CORE-2 300/1 5P20 2S1-2S2 PROTECTION

1. INSULATION RESISTANCE MEASUREMENT:


(Value Taken at 5kV for 1 min)

Phase
Core
R- Phase Y- Phase B-Phase

Primary – Earth 45.6 56.2 45.8

Primary-core1 25.9 32.1 56.4

Primary – Core 2 35.7 33.4 25.6

(Value Taken at 500V for 1 min.)

Core 1 – Core2 >1.0GΩ >1.0GΩ >1.0GΩ

Core 1 –Earth >1.0GΩ >1.0GΩ >1.0GΩ

Core2-Earth >1.0GΩ >1.0GΩ >1.0GΩ

2.WINDING RESISTANCE MEASUREMENT:

CORE R PHASE Y PHASE B PHASE

1S1-1S2 3.2 Ω 3.3 Ω 3.2 Ω

2S1-2S2 6.8Ω 6.9 Ω 6.8 Ω

3. POLARITY TEST

Between Phase
Core
Terminal R- Phase Y- Phase B-Phase

Core – 1 1S1 – 1S2 Forward Forward Forward


TESTED BY AKSHAR Core – 2 2S1 – 2S2 Forward WITNESSED
ForwardBY ADANIForward
PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

4. RATIO TEST :

Core CTRATIO CT
[A] CURRENT Measured CT sec. current (mA)
INJEC(A)

CORE R Y B

CORE – 1 300/1 100 0.34 0.35 0.35

1S1 -1S2 200 0.67 0.68 0.68

300 0.99 1.03 1.02

CORE – 2 300/1 100 0.37 0.39 0.38

2S1 - 2S2 200 0.69 0.68 0.67

300 1.08 1.06 1.04

TEST REPORT OF CIRCUIT BREAKER

FEEDER /BAY NAME : CAPACITOR BANK 1 - 5 MVAR CB

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

Sr. No. 1VYN30123000214

NAME PLATE DETAILS:

Make : ABB

STANDARD : IEC62271-100

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

HIGHER SYSTEM VOLTAGE : 40.5 KV

SERVICE VOLTAGE : 40.5 KV

RATED CURRENT : 630 A

RATED FREQUENCY : 50Hz

BASIC INSULATION LEVEL : 70 KV/ 170 KV pk

SHORT CIRCUIT BREAKING CURRENT : 31.5 kA /3 sec.

SHORT CURCUIT MAKING CURRENT : 82 kA pk

MINIMUM CREEPAGE : 1116 mm

CONTROL VOLTAGE : 220 V DC

SPRING CHARGE MOTOR SUPPLY VOLTAGE : 230 V AC

AUXILIARY SUPPLY VOLTAGE : 230 V AC

PAINT SHADE : 631 OF IS (LIGHT GREY)

ENCLOSURE FABRICATION MATERIAL TYPE : MS- HR

ENCLOSURE FABRICATION MATERIAL THICKNESS : 2.5 MM

SUPPORT STRUCTURE TYPE : VCB MOUNTING STRUCTURE

TERMINAL CONNECTOR (REQD. IF ANY) : IN HITACHI SCOPE

1. INSULATION RESISTANCE MEASUREMENT :


(Value Taken at 5kV for 1 min)

MODE R (GΩ) Y (GΩ) B (GΩ)

OPEN

TOP TO MIDDEL 43.6G0Ω 58.0 GΩ 51.5 GΩ

CLOSE

PHASE TO EARTH 42.8 GΩ 56.5 GΩ 44.4 GΩ


TESTED BY AKSHAR WITNESSED BY ADANI PROJECT
NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

2. TIMING MEASUREMENT (Millisecond) : kit used : SCOPE timings


REFERENCE R (ms) Y (ms) B (ms)

COIL-1

CLOSE-1 78 78 78

TRIP-1 41 41 41

C-O-1 43 43 43

COIL-2

CLOSE-2 79 79 78

TRIP-2 42 43 42

C-O-2 43 43 43

3. CONTACT RESISTANCE MEASUREMENT : kit used: SCOPE CRM100C


(Temp.: - 40°C)

PHASE R – PH Y –PH B – PH

CRM(µΩ) 23.3 23.6 22.6

4. COIL RESISTANCE MEASUERMENT

CLOSING COIL 217.6Ω


TESTED BY AKSHAR TRIP COIL 1 WITNESSED BY ADANI PROJECT
226.6Ω
NAME: ABHISEK BEHURA NAME:
SIGN: TRIP COIL 2 SIGN: 224.6Ω
DATE: 20.06.2023 DATE:
SITE TEST REPORT

TEST REPORT OF NEUTRAL CURRENT TRANSFORMER


FEEDER /BAY NAME : CAPACITOR BANK 1 - 5MVAR

CUSTOMER : M/S ADANI GREEN ENERGY LTD.

NAME PLATE DETAILS:

Make : MEHRU ELECT & MECH. ENGG. (P) LTD, BHIVADI (RAJ)

Rated voltage : 36 KV

Sr. No. : NCT: 12982/3/3/23

Year of Manufacture : 2023,

Core Ratio Class Protection / Metering

CORE-1 5/1 5P20 1S1-1S2 PROTECTON

1. INSULATION RESISTANCE MEASUREMENT:


(Value Taken at 5kV for 1 min)

Core
NCT

Primary – Earth 63.5 GΩ

Primary-core 59.2 GΩ

CORE – EARTH >1.0 GΩ

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

2. WINDING RESISTANCE MEASUREMENT:


(Value Taken at 500V for 1 min)

CORE NCT PHASE

1S1-1S2 2.2

3. POLARITY TEST

Between
Core NCT PHASE
Terminal

Core – 1 1S1 – 1S2 FORWORD

4. RATIO TEST :

Core CT RATIO CT CURRENT Measured CT sec. current (mA)


[A] INJEC.(A)

CORE

CORE – 1 5/1 1A 0.201

1S1 -1S2 2A 0.401

3A 0.600

FIELD QUALITY RECORD - REF 620 RELAY

S.NO PARAMETER DESCRIPTION VALUE OF PARAMETER

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

1.
Make ABB

2. Model No 5BFNAANNNEA1BNC11G

3. Serial no 1VYV91548852

1a) CURRENT MEASUREMENTS

Measured Current (A)


Phase Applied Current (A)
R Y B I0

R 1.0 300.1 0 0 0

Y 1.0 0 300.0 0 0

B 1.0 0 0 300.0 0

RYB 1.0 300.1 300.0 300.1 0

N 1.0 0 0 0 5.0

1b) VOLTAGE MEASUREMENTS

Measured Voltage (kV)


Applied Voltage
Phase Ph-Ph
(V)
R Y B

R 63.51 19.052 19.053

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Y 63.51 19.053 19.051

B 63.51 19.049 19.048

RYB 63.51 32.993 33.00 33.03

2. OVER CURRENT PROTECTION

2a) Stage-1: I>1

Set current : 0.67A Curve : IEC NI

TMS : 0.05 Directional : Non.Dir

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Pickup Calculated Operating Time (Sec) Measured Operating Time (Sec)


Phas Current (A)
e 2Is 5Is 2Is 5Is
2T 5T

R 1.34 3.35 0.510 0.234

Y 1.34 3.35 0.514 0.238


0.501 0.214
B 1.34 3.35 0.521 0.214

RYB 1.34 3.35 0.513 0.215

IDMT Pickup: 1.05 x Setting, Pickup Tolerance: ± 5%

2b) Stage-2: I>2

Set current : 2.92A Curve : DT

Time : 100ms Directional : Non-Dir

Phase Pickup Current (A) Measured Op.Time (ms)

R 2.93 134mS

Y 2.93 135mS

B 2.93 159mS

RYB 2.93 140mS

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

3. EARTH FAULT PROTECTION

3a) Stage-1: IN>1

Set current : 0.2A Curve : IEC SI

TMS : 0.05 Directional : Non.Dir

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Pickup Calculated Operating Time (Sec) Measured Operating Time (Sec)


Phas Current (A)
e 2Is 5Is 2Is 5Is
2T 5T

R 0.4 1.0 0.501 0.230

Y 0.4 1.0 0.501 0.214 0.512 0.240

B 0.4 1.0 0.510 0.230

IDMT Pickup: 1.05 x Setting, Pickup Tolerance: ± 5%

3b) Stage-2: IN>2

Set current : 0.4A Curve : DT

Time : 100ms Directional : Non-Dir

Phase Pickup Current (A) Measured Op.Time (ms)

R 0.402 130.2

Y 0.402 130.3

B 0.402 129.2

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

DMT Operation Time Tolerance: ± 2% or 70ms whichever is greater (1.05 - <2) Is

± 2% or 50ms whichever is greater (2.00 - 20) Is

4. OVERVOLTAGE PROTECTION

Stage-1: V>1

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Set Voltage : 121V Mode : Ph-Ph

Set Time : 3.0Sec Curve : DT

Pickup Voltage (V)


Phase Measured Operating Time (Sec)
Ph-Ph

R 69.86 3.116ms

Y 69.86 3.141ms

B 69.86 3.110ms

RYB - -

Pickup Tolerance: Setting ± 1%

Timing Tolerance: ± 2% or 50ms whichever is greater

Stage-1: V>2

Set Voltage : 132V Mode : Ph-Ph

Set Time : 0.1Sec Curve : DT

Pickup Voltage (V)


Phase Measured Operating Time (Sec)
Ph-Ph

R 76.21 0.12 S

Y 76.21 0.13S

B 76.21 0.13S

RYB - -

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

5. UNDERVOLTAGE PROTECTION

Stage-1: V<1

Set Voltage : 93.5V Mode : 2Ph-Ph

Set Time : 3.0 Sec Curve : DT

Pickup Voltage (V) Measured Operating Time (Sec) @


Phase
Ph-Ph Vs/1.05

R 49.07 3.019ms

Y 49.07 3.029ms

B 49.07 3.019ms

RYB

Pickup Tolerance: Setting ± 5%

6. UNBALANCE PROTECTION

a) Stage-1: I>1

Set current : 0.2A Curve : DT

TMS : 1.0S Directional : Non.Dir

Phase Pickup Current (A) Measured Operating Time (Sec)

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

R 0.21 1.100S

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

BINARY INPUTS Checked as per Relay Assignment 


BINARY OUTPUTS Checked as per Relay Assignment 
LED INDICATORS Checked as per Relay Assignment 
Disturbance Recorder VERIFIED

Relay found Healthy YES

Test Kit Used:

Calibration due
Kit Name Serial No. Calibration date
date

Omicron 3Phase
Secondary Injection Kit

FIELD QUALITY RECORD - REF 620 RELAY

S.NO PARAMETER DESCRIPTION VALUE OF PARAMETER

4.
Make ABB

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

5. Model No 5BFNAANNNEA1BNC11G

6. Serial no 1VYV91548853

1a) CURRENT MEASUREMENTS

Measured Current (A)


Phase Applied Current (A)
R Y B I0

R 1.0 300.2 0 0 0

Y 1.0 0 300.0 0 0

B 1.0 0 0 300.0 0

RYB 1.0 300.2 300.1 300.1 0

N 1.0 0 0 0 5.0

1b) VOLTAGE MEASUREMENTS

Measured Voltage (kV)


Applied Voltage
Phase Ph-Ph
(V)
R Y B

R 63.51 19.050 19.052

Y 63.51 19.052 19.051

B 63.51 19.049 19.048

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

RYB 63.51 33.02 33.292 32.984

2. OVER CURRENT PROTECTION

2a) Stage-1: I>1

Set current : 0.67A Curve : IEC NI

TMS : 0.05 Directional : Non.Dir

Phas Pickup Calculated Operating Time (Sec) Measured Operating Time (Sec)
e Current (A)
2Is 5Is 2Is 5Is

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

2T 5T

R 1.34 3.35 0.536 0.234

Y 1.34 3.35 0.528 0.230


0.501 0.214
B 1.34 3.35 0.515 0.232

RYB 1.34 3.35 0.523 0.232

IDMT Pickup: 1.05 x Setting, Pickup Tolerance: ± 5%

2b) Stage-2: I>2

Set current : 2.92A Curve : DT

Time : 100ms Directional : Non-Dir

Phase Pickup Current (A) Measured Op.Time (ms)

R 2.93 149mS

Y 2.93 148mS

B 2.93 151mS

RYB 2.93 141mS

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

3. EARTH FAULT PROTECTION4

3a) Stage-1: IN>1

Set current : 0.2A Curve : IEC SI

TMS : 0.05 Directional : Non.Dir

Phas Pickup Calculated Operating Time (Sec) Measured Operating Time (Sec)

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Current (A)
e 2Is 5Is 2Is 5Is
2T 5T

R 0.4 1.0 0.503 0.231

Y 0.4 1.0 0.501 0.214 0.517 0.230

B 0.4 1.0 0.499 0.228

IDMT Pickup: 1.05 x Setting, Pickup Tolerance: ± 5%

3b) Stage-2: IN>2

Set current : 0.4A Curve : DT

Time : 100ms Directional : Non-Dir

Phase Pickup Current (A) Measured Op.Time (ms)

R 0.402 128.0

Y 0.402 130.2

B 0.402 131.0

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

DMT Operation Time Tolerance: ± 2% or 70ms whichever is greater (1.05 - <2) Is

± 2% or 50ms whichever is greater (2.00 - 20) Is

4. OVERVOLTAGE PROTECTION

Stage-1: V>1

Set Voltage : 121V Mode : Ph-Ph

Set Time : 3.0Sec Curve : DT

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Pickup Voltage (V)


Phase Measured Operating Time (Sec)
Ph-Ph

R 69.86 3.126ms

Y 69.86 3.134ms

B 69.86 3.116ms

RYB - -

Pickup Tolerance: Setting ± 1%

Timing Tolerance: ± 2% or 50ms whichever is greater

Stage-1: V>2

Set Voltage : 132V Mode : Ph-Ph

Set Time : 0.1Sec Curve : DT

Pickup Voltage (V)


Phase Measured Operating Time (Sec)
Ph-Ph

R 76.21 0.226 S

Y 76.21 0.228S

B 76.21 0.217S

RYB - -

5. UNDERVOLTAGE PROTECTION

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Stage-1: V<1

Set Voltage : 93.5V Mode : Ph-Ph

Set Time : 3.0 Sec Curve : DT

Pickup Voltage (V) Measured Operating Time (Sec) @


Phase
Ph-Ph Vs/1.05

R 49.07 3.019ms

Y 49.07 3.039ms

B 49.07 3.014ms

RYB

Pickup Tolerance: Setting ± 5%

6. UNBALANCE PROTECTION

a) Stage-1: I>1

Set current : 0.2A Curve : DT

TMS : 1.0S Directional : Non.Dir

Phase Pickup Current (A) Measured Operating Time (Sec)

R 0.21 1.1013S

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

BINARY INPUTS Checked as per Relay Assignment 


BINARY OUTPUTS Checked as per Relay Assignment 
LED INDICATORS Checked as per Relay Assignment 
Disturbance Recorder VERIFIED

Relay found Healthy YES

Test Kit Used:

Calibration due
Kit Name Serial No. Calibration date
date

Omicron 3Phase
Secondary Injection Kit

FIELD QUALITY RECORD - REF 620 RELAY

S.NO PARAMETER DESCRIPTION VALUE OF PARAMETER

7.
Make ABB

8. Model No 5BFNAANNNEA1BNC11G

9. Serial no 1VYV91548873

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

1a) CURRENT MEASUREMENTS

Measured Current (A)


Phase Applied Current (A)
R Y B I0

R 1.0 300.1 0 0 0

Y 1.0 0 300.0 0 0

B 1.0 0 0 300.0 0

RYB 1.0 300.1 300.0 300.1 0

N 1.0 0 0 0 5.0

1b) VOLTAGE MEASUREMENTS

Measured Voltage (kV)


Applied Voltage
Phase Ph-Ph
(V)
R Y B

R 63.51 19.050 19.052

Y 63.51 19.051 19.051

B 63.51 19.049 19.048

RYB 63.51 32.992 32.992 32.994

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

2. OVER CURRENT PROTECTION

2a) Stage-1: I>1

Set current : 0.33A Curve : IEC NI

TMS : 0.05 Directional : Non.Dir

Pickup Calculated Operating Time (Sec) Measured Operating Time (Sec)


Phas Current (A)
e 2Is 5Is 2Is 5Is
2T 5T

R 0.66 1.65 0.501 0.214 0.503 0.224

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Y 0.66 1.65 0.511 0.234

B 0.66 1.65 0.515 0.234

RYB 0.66 1.65 0.514 0.512

IDMT Pickup: 1.05 x Setting, Pickup Tolerance: ± 5%

2b) Stage-2: I>2

Set current : 1.46A Curve : DT

Time : 100ms Directional : Non-Dir

Phase Pickup Current (A) Measured Op.Time (ms)

R 1.47 139Ms

Y 1.47 136mS

B 1.47 138mS

RYB 1.47 130mS

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

3. EARTH FAULT PROTECTION

3a) Stage-1: IN>1

Set current : 0.2A Curve : IEC SI

TMS : 0.05 Directional : Non.Dir

Pickup Calculated Operating Time (Sec) Measured Operating Time (Sec)


Phas Current (A)
e 2Is 5Is 2Is 5Is
2T 5T

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

R 0.4 1.0 0.515 0.224

Y 0.4 1.0 0.501 0.214 0.512 0.228

B 0.4 1.0 0.510 0.231

IDMT Pickup: 1.05 x Setting, Pickup Tolerance: ± 5%

3b) Stage-2: IN>2

Set current : 0.4A Curve : DT

Time : 100ms Directional : Non-Dir

Phase Pickup Current (A) Measured Op.Time (ms)

R 0.402 115.5

Y 0.402 120.1

B 0.402 120.2

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

DMT Operation Time Tolerance: ± 2% or 70ms whichever is greater (1.05 - <2) Is

± 2% or 50ms whichever is greater (2.00 - 20) Is

4. OVERVOLTAGE PROTECTION

Stage-1: V>1

Set Voltage : 121V Mode : Ph-Ph

Set Time : 3.0Sec Curve : DT

Phase Pickup Voltage (V) Measured Operating Time (Sec)

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Ph-Ph

R 69.86 3.022ms

Y 69.86 3.032ms

B 69.86 3.022ms

RYB - -

Pickup Tolerance: Setting ± 1%

Timing Tolerance: ± 2% or 50ms whichever is greater

Stage-1: V>2

Set Voltage : 132V Mode : Ph-Ph

Set Time : 0.1Sec Curve : DT

Pickup Voltage (V)


Phase Measured Operating Time (Sec)
Ph-Ph

R 76.21 0.13 S

Y 76.21 0.13S

B 76.21 0.13S

RYB - -

5. UNDERVOLTAGE PROTECTION

Stage-1: V<1

Set Voltage : 93.5V Mode : Ph-Ph

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

Set Time : 3.0 Sec Curve : DT

Pickup Voltage (V) Measured Operating Time (Sec) @


Phase
Ph-Ph Vs/1.05

R 49.07 3.019ms

Y 49.07 3.039ms

B 49.07 3.029ms

RYB

Pickup Tolerance: Setting ± 5%

6. UNBALANCE PROTECTION

a) Stage-1: I>1

Set current : 0.2A Curve : DT

TMS : 1.0S Directional : Non.Dir

Phase Pickup Current (A) Measured Operating Time (Sec)

R 0.21 1.101 S

DMT Pickup: 1.0 x Setting, Pickup Tolerance: ± 5%

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE:
SITE TEST REPORT

BINARY INPUTS Checked as per Relay Assignment 


BINARY OUTPUTS Checked as per Relay Assignment 
LED INDICATORS Checked as per Relay Assignment 
Disturbance Recorder VERIFIED

Relay found Healthy YES

Test Kit Used:

Calibration due
Kit Name Serial No. Calibration date
date

Omicron 3Phase
Secondary Injection Kit

TESTED BY AKSHAR WITNESSED BY ADANI PROJECT


NAME: ABHISEK BEHURA NAME:
SIGN: SIGN:
DATE: 20.06.2023 DATE: