Settings groups
Gallant 25MW / 12.5 MW / 12.5 MW
SIMATIC relay-2 final/7UM622 03.02.22 18:39:25
1 Settings groups
1.2 Group O/C I> (with undervoltage seal-in); Group O/C I>
Page 1 of 11
12_5 MW relay-2 final_prn_18_39_25
Group Inverse O/C Time Protection; Group IDMT
Gallant 25MW / 12.5 MW / 12.5 MW
SIMATIC relay-2 final/7UM622 03.02.22 18:39:25
Page 2 of 11
12_5 MW relay-2 final_prn_18_39_25
Group Unbalance Load (Negative Sequence); Group Unbalance Load
Gallant 25MW / 12.5 MW / 12.5 MW
SIMATIC relay-2 final/7UM622 03.02.22 18:39:25
Page 3 of 11
12_5 MW relay-2 final_prn_18_39_25
Page 4 of 11
12_5 MW relay-2 final_prn_18_39_25
Group Reverse Power Protection; Group Reverse Power
Gallant 25MW / 12.5 MW / 12.5 MW
SIMATIC relay-2 final/7UM622 03.02.22 18:39:25
Page 5 of 11
12_5 MW relay-2 final_prn_18_39_25
Group Impedance Protection; Group Zones
Gallant 25MW / 12.5 MW / 12.5 MW
SIMATIC relay-2 final/7UM622 03.02.22 18:39:25
Page 6 of 11
12_5 MW relay-2 final_prn_18_39_25
Page 7 of 11
12_5 MW relay-2 final_prn_18_39_25
Page 8 of 11
12_5 MW relay-2 final_prn_18_39_25
Group Rate-of-frequency-change protection; Group df/dt Protect.
Gallant 25MW / 12.5 MW / 12.5 MW
SIMATIC relay-2 final/7UM622 03.02.22 18:39:25
4502 Mode of Threshold (df1/dt >/<) -df/dt< negative rate of freq. change A
4503 Pickup Value of df1/dt Stage 1.5 Hz/s A
4504 Time Delay of df1/dt Stage 2.00 sec A
4505 AND logic with pickup of stage f1 OFF A
4506 Mode of Threshold (df2/dt >/<) +df/dt> positive rate of freq. change A
4507 Pickup Value of df2/dt Stage 1.5 Hz/s A
4508 Time Delay of df2/dt Stage 2.00 sec A
4509 AND logic with pickup of stage f2 OFF A
Page 9 of 11
12_5 MW relay-2 final_prn_18_39_25
Page 10 of 11
12_5 MW relay-2 final_prn_18_39_25
Group Supervision; Group General
Gallant 25MW / 12.5 MW / 12.5 MW
SIMATIC relay-2 final/7UM622 03.02.22 18:39:25
Page 11 of 11