7SJ621 V4_6 Var_prn_11_33_44

Power System Data 1


BACKUP_SIPROTEC / P2 /
SIMATIC CJ-S641-411-CJ11 / 7SJ621 V4.6 19.10.18 11:33:45

1 Power System Data 1

1.1 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0214 Rated Frequency 60 Hz All


0209 Phase Sequence L1 L2 L3 All
0276 Unit of temperature measurement Degree Celsius All
0201 CT Starpoint towards Line All
0213 VT Connection, three-phase U1E, U2E, U3E All
0240 VT Connection, single-phase NO All
0235A Storage of th. Replicas w/o Power Supply NO All
0250A Time Overcurrent with 2 phase prot. OFF All
0613A (I) DMT Earth Overcurrent with IE (measured) All
0614A Operating Quantity for Overvolt. Prot. Uph-ph All
0615A Operating Quantity for Undervolt. Prot. U1 All

1.2 Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's


No. Settings Value Group

0204 CT Rated Primary Current 2500 A All


0205 CT Rated Secondary Current 5A All
0217 IE-CT rated primary current 200 A All
0218 IE-CT rated secondary current 5A All

1.3 Group Power System Data 1; Group VT's

Group Power System Data 1; Group VT's


No. Settings Value Group

0202 Rated Primary Voltage 13.80 kV All


0203 Rated Secondary Voltage (L-L) 115 V All
0206A Matching ratio Phase-VT To Open-Delta-VT 1.73 All

Page 1 of 6
7SJ621 V4_6 Var_prn_11_33_44

BACKUP_SIPROTEC / P2 /
SIMATIC CJ-S641-411-CJ11 / 7SJ621 V4.6 19.10.18 11:33:45

1.4 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0210A Minimum TRIP Command Duration 0.15 sec All


0211A Maximum Close Command Duration 1.00 sec All
0212 Closed Breaker Min. Current Threshold 0.20 A All

Page 2 of 6
7SJ621 V4_6 Var_prn_11_33_44
Settings groups
BACKUP_SIPROTEC / P2 /
SIMATIC CJ-S641-411-CJ11 / 7SJ621 V4.6 19.10.18 11:33:45

2 Settings groups

2.1 Group Power System Data 2; Group General

Group Power System Data 2; Group General


No. Settings Value Group

1101 Measurement: Full Scale Voltage (100%) 13.80 kV A


1102 Measurement: Full Scale Current (100%) 2500 A A
1108 P,Q operational measured values sign not reversed A

2.2 Group DMT / IDMT Phase/Earth Overcurrent; Group General

Group DMT / IDMT Phase/Earth Overcurrent; Group General


No. Settings Value Group

1201 Phase Time Overcurrent ON A


1213A Manual Close Mode I>> instantaneously A
1215A Dropout Time Delay DMT Phase 0.00 sec A
1301 Earth Time Overcurrent ON A
1313A Manual Close Mode IE>> instantaneously A
1315A Dropout Time Delay DMT Earth 0.00 sec A

2.3 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph

Group DMT / IDMT Phase/Earth Overcurrent; Group DMT Ph


No. Settings Value Group

1202 I>> Pickup 175.00 A A


1203 T I>> Time Delay 60.00 sec A
1204 I> Pickup 5.00 A A
1205 T I> Time Delay 0.52 sec A
1214A I>> active Always A

Page 3 of 6
7SJ621 V4_6 Var_prn_11_33_44
Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph
BACKUP_SIPROTEC / P2 /
SIMATIC CJ-S641-411-CJ11 / 7SJ621 V4.6 19.10.18 11:33:45

2.4 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph

Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT Ph


No. Settings Value Group

1207 Ip Pickup 5.00 A A


1209 TIME DIAL: TD 0.52 A
1210 Drop-Out Characteristic Instantaneous A
1212 ANSI Curve Very Inverse A

2.5 Group DMT / IDMT Phase/Earth Overcurrent; Group DMT E

Group DMT / IDMT Phase/Earth Overcurrent; Group DMT E


No. Settings Value Group

1302 IE>> Pickup 2.00 A A


1303 T IE>> Time Delay 60.00 sec A
1304 IE> Pickup 2.00 A A
1305 T IE> Time Delay 0.18 sec A
1314A IE>> active Always A

2.6 Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E

Group DMT / IDMT Phase/Earth Overcurrent; Group IDMT E


No. Settings Value Group

1307 IEp Pickup 0.50 A A


1309 TIME DIAL: TD 1.70 A
1310 Drop-Out Characteristic Instantaneous A
1312 ANSI Curve Definite Inverse A

2.7 Group Over / Under Voltage; Group General

Group Over / Under Voltage; Group General


No. Settings Value Group

5101 Undervoltage Protection OFF A


5001 Overvoltage Protection ON A

Page 4 of 6
7SJ621 V4_6 Var_prn_11_33_44

BACKUP_SIPROTEC / P2 /
SIMATIC CJ-S641-411-CJ11 / 7SJ621 V4.6 19.10.18 11:33:45

2.8 Group Over / Under Voltage; Group Under Voltage

Group Over / Under Voltage; Group Under Voltage


No. Settings Value Group

5102 U< Pickup 210 V A


5106 T U< Time Delay 100.00 sec A
5110 U<< Pickup 210 V A
5112 T U<< Time Delay 100.00 sec A
5113A Dropout Ratio U< 1.20 A
5114A Dropout Ratio U<< 1.20 A
5120A Current Supervision ON A

2.9 Group Over / Under Voltage; Group Over Voltage

Group Over / Under Voltage; Group Over Voltage


No. Settings Value Group

5002 U> Pickup 138 V A


5004 T U> Time Delay 3.00 sec A
5005 U>> Pickup 200 V A
5007 T U>> Time Delay 3.00 sec A
5017A Dropout Ratio U> 0.95 A
5018A Dropout Ratio U>> 0.95 A

2.10 Group Measurement Supervision; Group General

Group Measurement Supervision; Group General


No. Settings Value Group

8101 Measurement Supervision ON A


5301 Fuse Fail Monitor OFF A

Page 5 of 6
7SJ621 V4_6 Var_prn_11_33_44
Group Measurement Supervision; Group MeasSupervision
BACKUP_SIPROTEC / P2 /
SIMATIC CJ-S641-411-CJ11 / 7SJ621 V4.6 19.10.18 11:33:45

2.11 Group Measurement Supervision; Group MeasSupervision

Group Measurement Supervision; Group MeasSupervision


No. Settings Value Group

8102 Voltage Threshold for Balance Monitoring 50 V A


8103 Balance Factor for Voltage Monitor 0.75 A
8104 Current Balance Monitor 2.50 A A
8105 Balance Factor for Current Monitor 0.50 A
8106 Summated Current Monitoring Threshold 0.50 A A
8107 Summated Current Monitoring Factor 0.10 A

2.12 Group Measurement Supervision; Group Fuse Fail Mon.

Group Measurement Supervision; Group Fuse Fail Mon.


No. Settings Value Group

5302 Zero Sequence Voltage 30 V A


5303 Residual Current 0.50 A A

2.13 Group Energy; Group Measurement

Group Energy; Group Measurement


No. Settings Value Group

8315 Meter resolution Standard A