You are on page 1of 33

7SJ624 V4_9_prn_18_00_56

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

ISWP / Incomer / 7SJ624 V4.9

MLFB: 7SJ6241**B901FG4
Parameter-set version: V04.95.00
Device path: C:\Siemens\DIGSI4\D4PROJ\Iswp\P7DI\GV\SD\00000004
Author:
Creation date: 20.02.20 20:59:45
Last modified: 23.04.20 17:54:34
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Device Configuration ................................................................................................................................................ 2


2 Power System Data 1 ...........................................................................................................................................… 3
2.1 Group Power System Data 1; Group Power System ...........................................................................................… 3
2.2 Group Power System Data 1; Group CT's ...........................................................................................................… 3
2.3 Group Power System Data 1; Group VT's ............................................................................................................… 3
2.4 Group Power System Data 1; Group Breaker .......................................................................................................... 4
2.5 Group Power System Data 1; Group Prot.Op. quant. ..........................................................................................… 4
3 Settings groups ....................................................................................................................................................… 5
3.1 Group Power System Data 2; Group General ......................................................................................................… 5
3.2 Group 67 Directional Phase/Ground Overcurrent; Group General ......................................................................… 5
3.3 Group 67 Directional Phase/Ground Overcurrent; Group 67 ...............................................................................… 5
3.4 Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC ......................................................................… 6
3.5 Group 67 Directional Phase/Ground Overcurrent; Group 67N .............................................................................… 6
3.6 Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC ....................................................................… 7
3.7 Group Measurement Supervision; Group General ...............................................................................................… 7
3.8 Group Measurement Supervision; Group Fuse Fail Mon. ....................................................................................… 7
3.9 Group Measurement Supervision; Group MeasSupervision .................................................................................... 7
3.10 Group Measurement Supervision; Group VT broken wire ...................................................................................… 8
3.11 Group Energy; Group Measurement ........................................................................................................................ 8

Page 1 of 8
7SJ624 V4_9_prn_18_00_56
Device Configuration

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0104 Oscillographic Fault Records Disabled
0112 50/51 Disabled
0113 50N/51N Disabled
0115 67, 67-TOC Time Overcurrent Curve IEC
0116 67N, 67N-TOC Time Overcurrent Curve IEC
0127 50 1Ph Disabled
0117 Cold Load Pickup Disabled
0122 2nd Harmonic Inrush Restraint Disabled
0131 (sensitive) Ground fault Disabled
0130 (sens.) Ground fault dir. characteristic cos phi / sin phi measurement (standard)
0140 46 Negative Sequence Protection Disabled
0142 49 Thermal Overload Protection Disabled
0150 27, 59 Under/Overvoltage Protection Disabled
0154 81 Over/Underfrequency Protection Disabled
0155 27 / Q dir. con. Protection Disabled
0161 25 Function group 1 Disabled
0170 50BF Breaker Failure Protection Disabled
0172 52 Breaker W ear Monitoring Disabled
0182 74TC Trip Circuit Supervision Disabled
Flexible Function

Page 2 of 8
7SJ624 V4_9_prn_18_00_56
Power System Data 1

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

2 Power System Data 1

2.1 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0214 Rated Frequency 50 Hz All


0209 Phase Sequence ABC All
0276 Unit of temperature measurement Degree Celsius All
0201 CT Starpoint towards Line All
0280 Holmgreen-conn. (for fast sum-i-monit.) NO All
0251A CT Connection Ia, Ib, Ic, (IGnd) All
0213 VT Connection, three-phase Van, Vbn, Vcn, VGnd All
0240 VT Connection, single-phase NO All
0235A Storage of th. Replicas w/o Power Supply NO All
0250A 50, 51 Time Overcurrent with 2ph. prot. OFF All

2.2 Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's


No. Settings Value Group

0204 CT Rated Primary Current 800 A All


0205 CT Rated Secondary Current 1A All
0217 Ignd-CT rated primary current 800 A All
0218 Ignd-CT rated secondary current 1A All

2.3 Group Power System Data 1; Group VT's

Group Power System Data 1; Group VT's


No. Settings Value Group

0202 Rated Primary Voltage 33.00 kV All


0203 Rated Secondary Voltage (L-L) 110 V All
0206A Matching ratio Phase-VT To Open-Delta-VT 1.73 All

Page 3 of 8
7SJ624 V4_9_prn_18_00_56
Group Power System Data 1; Group Breaker

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

2.4 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0210A Minimum TRIP Command Duration 0.15 sec All


0211A Maximum Close Command Duration 1.00 sec All
0212 Closed Breaker Min. Current Threshold 0.04 A All

2.5 Group Power System Data 1; Group Prot.Op. quant.

Group Power System Data 1; Group Prot.Op. quant.


No. Settings Value Group

0613A 50N/51N/67N Ground Overcurrent with Ignd (measured) All

Page 4 of 8
7SJ624 V4_9_prn_18_00_56
Settings groups

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

3 Settings groups

3.1 Group Power System Data 2; Group General

Group Power System Data 2; Group General


No. Settings Value Group

1101 Measurem:FullScaleVoltage(Equipm.rating) 33.00 kV A


1102 Measurem:FullScaleCurrent(Equipm.rating) 800 A A
1108 P,Q operational measured values sign not reversed A
1114A Operational current measurement < 1% NO A

3.2 Group 67 Directional Phase/Ground Overcurrent; Group General

Group 67 Directional Phase/Ground Overcurrent; Group General


No. Settings Value Group

1501 67, 67-TOC Phase Time Overcurrent ON A


1513A Manual Close Mode 67-2 instantaneously A
1526 67-3 Direction Forward A
1523 67-2 Direction Forward A
1524 67-1 Direction Forward A
1525 67-TOC Direction Forward A
1518A 67 Drop-Out Time Delay 0.00 sec A
1519A Rotation Angle of Reference Voltage 45 ° A
1601 67N, 67N-TOC Ground Time Overcurrent ON A
1613A Manual Close Mode 67N-2 instantaneously A
1626 67N-3 Direction Forward A
1623 67N-2 Direction Forward A
1624 67N-1 Direction Forward A
1625 67N-TOC Direction Forward A
1617 Ground Polarization with VN and IN A
1618A 67N Drop-Out Time Delay 0.00 sec A
1619A Rotation Angle of Reference Voltage -45 ° A

3.3 Group 67 Directional Phase/Ground Overcurrent; Group 67

Group 67 Directional Phase/Ground Overcurrent; Group 67


No. Settings Value Group

1527A 67-3 measurement of Fundamental component A


1532A 67-3 active always A

Page 5 of 8
7SJ624 V4_9_prn_18_00_56

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

Group 67 Directional Phase/Ground Overcurrent; Group 67(2)


No. Settings Value Group

1528 67-3 Pickup oo A A


1529 67-3 Time Delay oo sec A
1520A 67-2 measurement of Fundamental component A
1514A 67-2 active always A
1502 67-2 Pickup oo A A
1503 67-2 Time Delay oo sec A
1521A 67-1 measurement of Fundamental component A
1504 67-1 Pickup 5.00 A A
1505 67-1Time Delay 0.45 sec A

3.4 Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC

Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC


No. Settings Value Group

1522A 67-TOC measurement of Fundamental component A


1507 67-TOC Pickup 0.77 A A
1508 67-TOC Time Dial 0.23 sec A
1510 Drop-Out Characteristic Disk Emulation A
1511 IEC Curve Normal Inverse A

3.5 Group 67 Directional Phase/Ground Overcurrent; Group 67N

Group 67 Directional Phase/Ground Overcurrent; Group 67N


No. Settings Value Group

1627A 67N-3 measurement of Fundamental component A


1632A 67N-3 active always A
1628 67N-3 Pickup oo A A
1629 67N-3 Time Delay oo sec A
1620A 67N-2 measurement of Fundamental component A
1614A 67N-2 active always A
1602 67N-2 Pickup oo A A
1603 67N-2 Time Delay oo sec A
1621A 67N-1 measurement of Fundamental component A
1604 67N-1 Pickup 1.50 A A
1605 67N-1 Time Delay 0.50 sec A

Page 6 of 8
7SJ624 V4_9_prn_18_00_56
Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

3.6 Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC

Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC


No. Settings Value Group

1622A 67N-TOC measurement of Fundamental component A


1607 67N-TOC Pickup 0.20 A A
1608 67N-TOC Time Dial 0.30 sec A
1610 Drop-Out Characteristic Disk Emulation A
1611 IEC Curve Normal Inverse A

3.7 Group Measurement Supervision; Group General

Group Measurement Supervision; Group General


No. Settings Value Group

5301 Fuse Fail Monitor OFF A


5310 Block protection by FFM YES A
8101 Measurement Supervision ON A
5201 VT broken wire supervision OFF A

3.8 Group Measurement Supervision; Group Fuse Fail Mon.

Group Measurement Supervision; Group Fuse Fail Mon.


No. Settings Value Group

5302 Zero Sequence Voltage 30 V A


5303 Residual Current 0.10 A A
5308A Differential Current Threshold (3phase) 0.10 A A

3.9 Group Measurement Supervision; Group MeasSupervision

Group Measurement Supervision; Group MeasSupervision


No. Settings Value Group

8102 Voltage Threshold for Balance Monitoring 50 V A


8103 Balance Factor for Voltage Monitor 0.75 A
8104 Current Threshold for Balance Monitoring 0.50 A A
8105 Balance Factor for Current Monitor 0.50 A
8110A T Balance Factor for Voltage Monitor 5 sec A
8111A T Current Balance Monitor 5 sec A

Page 7 of 8
7SJ624 V4_9_prn_18_00_56

SIMATIC ISWP / Incomer / 7SJ624 V4.9/7SJ624 23.04.20 18:00:57

3.10 Group Measurement Supervision; Group VT broken wire

Group Measurement Supervision; Group VT broken wire


No. Settings Value Group

5202 Threshold voltage sum 8.0 V A


5203 Maximum phase to phase voltage 16.0 V A
5204 Minimum phase to phase voltage 16.0 V A
5205 Symmetry phase to phase voltages 16.0 V A
5206 Minimum line current 0.04 A A
5208 Alarm delay time 1.25 sec A

3.11 Group Energy; Group Measurement


Group Energy; Group Measurement
No. Settings Value Group

8315 Meter resolution Standard A

Page 8 of 8
7UT613 V4_6_prn_18_17_52

ISWP / 20MVA Trafo / 7UT613


SIMATIC V4.6/7UT613 28.04.20 18:17:52

ISWP / 20MVA Trafo / 7UT613 V4.6

MLFB: 7UT6131*EB921BC1
Parameter-set version: V04.67.00
Device path: C:\Siemens\DIGSI4\D4PROJ\Iswp\P7DI\GV\SD\0000000e
Author:
Creation date: 28.04.20 17:59:58
Last modified: 28.04.20 18:00:35
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Device Configuration ................................................................................................................................................ 2


2 Power System Data 1 ...........................................................................................................................................… 3
2.1 Group Power System Data 1; Group CT-Numbers .................................................................................................. 3
2.2 Group Power System Data 1; Group CT-Assign ..................................................................................................… 3
2.3 Group Power System Data 1; Group VT-Assign ...................................................................................................... 3
2.4 Group Power System Data 1; Group Power System ...........................................................................................… 3
2.5 Group Power System Data 1; Group Transf. .......................................................................................................… 4
2.6 Group Power System Data 1; Group CT's ...........................................................................................................… 4
2.7 Group Power System Data 1; Group VT's ............................................................................................................… 4
2.8 Group Power System Data 1; Group CB ..............................................................................................................… 5
3 Oscillographic Fault Records ...............................................................................................................................… 6
3.1 Group Oscillographic Fault Records; Group Osc. Fault Rec. ...............................................................................… 6
4 Settings groups ....................................................................................................................................................… 7
4.1 Group Power System Data 2; Group Power System ...........................................................................................… 7
4.2 Group Power System Data 2; Group PoleOpen Detect .......................................................................................… 7
4.3 Group 87 Differential Protection; Group General .................................................................................................… 7
4.4 Group 87 Differential Protection; Group I-Diff ......................................................................................................… 7
4.5 Group 87 Differential Protection; Group Characteristic ............................................................................................ 8
4.6 Group 87 Differential Protection; Group Inrush 2.HM ..........................................................................................… 8
4.7 Group 87 Differential Protection; Group Restr. n.HM ...........................................................................................… 8
4.8 Group Supervision; Group General ......................................................................................................................… 9

Page 1 of 9
7UT613 V4_6_prn_18_17_52
Device Configuration
ISWP / 20MVA Trafo / 7UT613
SIMATIC V4.6/7UT613 28.04.20 18:17:52

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0105 Protection Object 3 phase Transformer
0112 87 Differential Protection Enabled
0113 87G Restricted ground fault protection Disabled
0114 87G#2 Restricted ground fault protection Disabled
0117 Cold Load Pickup Disabled
0120 50/51 Disabled
0130 50/51#2 Disabled
0132 50/51#3 Disabled
0122 50N/51N Disabled
0134 50N/51N#2 Disabled
0136 50N/51N#3 Disabled
0124 50G/51G Disabled
0138 50G/51G#2 Disabled
0127 50 1Ph Disabled
0140 46 Negative Sequence Protection Disabled
0142 49 Thermal Overload Protection Disabled
0144 49#2 Thermal Overload Protection Disabled
0143 24 Overexcit. Protection (Volt/Hertz) Disabled
0150 32R Reverse Power Protection Disabled
0151 32F Forward Power Supervision Disabled
0152 27 Undervoltage Protection Disabled
0153 59 Overvoltage Protection Disabled
0156 81 Over/Underfrequency Protection Disabled
0170 50BF Breaker Failure Protection Disabled
0171 50BF#2 Breaker Failure Protection Disabled
0180 Disconnect measurment location Disabled
0181 Measured Values Supervision Disabled
0182 74TC Trip Circuit Supervision Disabled
0186 External Trip Function 1 Disabled
0187 External Trip Function 2 Disabled

Page 2 of 9
7UT613 V4_6_prn_18_17_52
Power System Data 1
ISWP / 20MVA Trafo / 7UT613
SIMATIC V4.6/7UT613 28.04.20 18:17:52

2 Power System Data 1

2.1 Group Power System Data 1; Group CT-Numbers

Group Power System Data 1; Group CT-Numbers


No. Settings Value Group

0211 Number of connected Measuring Locations 2 All


0212 Number of assigned Measuring Locations 2 All
0213 Number of Sides 2 All

2.2 Group Power System Data 1; Group CT-Assign

Group Power System Data 1; Group CT-Assign


No. Settings Value Group

0220 Assignment at 2 assig.Meas.Loc./ 2 Sides S1:M1, S2:M2 All


0251 Auxiliary CT IX1 is used as Not connected All
0252 Auxiliary CT IX2 is used as Not connected All
0253 Auxiliary CT IX3 is used as Not connected All
0255 Type of auxiliary CT IX3 1A/5A current input All

2.3 Group Power System Data 1; Group VT-Assign

Group Power System Data 1; Group VT-Assign


No. Settings Value Group

0261 VT set Va, Vb, Vc is assigned Measuring location 1 All


0262 VT V4 is assigned Measuring location 1 All
0263 VT V4 is used as Vdelta transformer All

2.4 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0270 Rated Frequency 50 Hz All


0271 Phase Sequence ABC All
0276 Unit of temperature measurement Degree Celsius All

Page 3 of 9
7UT613 V4_6_prn_18_17_52

ISWP / 20MVA Trafo / 7UT613


SIMATIC V4.6/7UT613 28.04.20 18:17:52

2.5 Group Power System Data 1; Group Transf.

Group Power System Data 1; Group Transf.


No. Settings Value Group

0311 Rated Primary Voltage Side 1 33.0 kV All


0312 Rated Apparent Power of Transf. Side 1 20.00 MVA All
0313 Starpoint of Side 1 is Isolated All
0314 Transf. W inding Connection Side 1 D (Delta) All
0321 Rated Primary Voltage Side 2 33.0 kV All
0322 Rated Apparent Power of Transf. Side 2 20.00 MVA All
0323 Starpoint of Side 2 is Grounded All
0324 Transf. W inding Connection Side 2 Y (W ye) All
0325 Vector Group Numeral of Side 2 11 All

2.6 Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's


No. Settings Value Group

0511 CT-Strpnt. Meas. Loc.1 in Dir. of Object YES All


0512 CT Rated Primary Current Meas. Loc. 1 1000 A All
0513 CT Rated Secondary Current Meas. Loc. 1 1A All
0521 CT-Strpnt. Meas. Loc.2 in Dir. of Object YES All
0522 CT Rated Primary Current Meas. Loc. 2 1000 A All
0523 CT Rated Secondary Current Meas. Loc. 2 1A All

2.7 Group Power System Data 1; Group VT's

Group Power System Data 1; Group VT's


No. Settings Value Group

0801 VT Rated Prim. Voltage Set Va, Vb, Vc 33.0 kV All


0802 VT Rated Sec. Voltage Set Va, Vb, Vc 110 V All
0803 Angle correction VA, VB, VC - VT 0.00 ° All
0816 Matching ratio Ph-VT to Broken-Delta-VT 1.73 All

Page 4 of 9
7UT613 V4_6_prn_18_17_52
Group Power System Data 1; Group CB
ISWP / 20MVA Trafo / 7UT613
SIMATIC V4.6/7UT613 28.04.20 18:17:52

2.8 Group Power System Data 1; Group CB

Group Power System Data 1; Group CB


No. Settings Value Group

0831 Switchgear / CBaux at Side 1 Q0 All


0832 Switchgear / CBaux at Side 2 <none> All
0836 Switchgear / CBaux at Measuring Loc. M1 <none> All
0837 Switchgear / CBaux at Measuring Loc. M2 <none> All
0851A Minimum TRIP Command Duration 0.15 sec All

Page 5 of 9
7UT613 V4_6_prn_18_17_52
Oscillographic Fault Records
ISWP / 20MVA Trafo / 7UT613
SIMATIC V4.6/7UT613 28.04.20 18:17:52

3 Oscillographic Fault Records

3.1 Group Oscillographic Fault Records; Group Osc. Fault Rec.

Group Oscillographic Fault Records; Group Osc. Fault Rec.


No. Settings Value Group

0901 W aveform Capture Save with Pickup All


0903 Max. length of a W aveform Capture Record 1.00 sec All
0904 Captured W aveform Prior to Trigger 0.20 sec All
0905 Captured W aveform after Event 0.10 sec All
0906 Capture Time via Binary Input 0.50 sec All

Page 6 of 9
7UT613 V4_6_prn_18_17_52
Settings groups
ISWP / 20MVA Trafo / 7UT613
SIMATIC V4.6/7UT613 28.04.20 18:17:52

4 Settings groups

4.1 Group Power System Data 2; Group Power System

Group Power System Data 2; Group Power System


No. Settings Value Group

1107 sign of P,Q reversed A

4.2 Group Power System Data 2; Group PoleOpen Detect

Group Power System Data 2; Group PoleOpen Detect


No. Settings Value Group

1111 Pole Open Current Threshold Side 1 0.10 I/InS A


1112 Pole Open Current Threshold Side 2 0.10 I/InS A
1121 Pole Open Current Threshold Meas.Loc. M1 0.04 A A
1122 Pole Open Current Threshold Meas.Loc. M2 0.04 A A

4.3 Group 87 Differential Protection; Group General


Group 87 Differential Protection; Group General
No. Settings Value Group

1201 87 Differential Protection ON A


1205 87 Increase of Trip Char. During Start OFF A
1206 87 Inrush with 2. Harmonic Restraint OFF A
1207 87 n-th Harmonic Restraint 5. Harmonic A
1300 87 Blocking with CWA OFF A
1283A Fault record with inst. diff current NO A

4.4 Group 87 Differential Protection; Group I-Diff

Group 87 Differential Protection; Group I-Diff


No. Settings Value Group

1221 87-1 Pickup Value of Differential Curr. 0.20 I/InO A


1226A 87-1 T I-DIFF> Time Delay 0.00 sec A
1231 87-2 Pickup Value of High Set Trip 8.0 I/InO A
1236A 87-2 T I-DIFF>> Time Delay 0.00 sec A

Page 7 of 9
7UT613 V4_6_prn_18_17_52

ISWP / 20MVA Trafo / 7UT613


SIMATIC V4.6/7UT613 28.04.20 18:17:52

4.5 Group 87 Differential Protection; Group Characteristic

Group 87 Differential Protection; Group Characteristic


No. Settings Value Group

1241A 87 Slope 1 of Tripping Characteristic 0.25 A


1242A 87 Base Point for Slope 1 of Charac. 0.00 I/InO A
1243A 87 Slope 2 of Tripping Characteristic 0.50 A
1244A 87 Base Point for Slope 2 of Charac. 2.50 I/InO A
1251A 87 I-RESTRAINT for Start Detection 0.10 I/InO A
1252A 87 Factor for Increas. of Char. at Start 1.0 A
1253 87 Maximum Permissible Starting Time 5.0 sec A
1261A 87 Pickup for Add-on Stabilization 4.00 I/InO A
1262A 87 Duration of Add-on Stabilization 15 Cycle A
1263A 87 Time for Cross-block Add-on Stabiliz. 3 Cycle A

4.6 Group 87 Differential Protection; Group Inrush 2.HM

Group 87 Differential Protection; Group Inrush 2.HM


No. Settings Value Group

1271 87 2nd Harmonic Content in I-DIFF 15 % A


1272A 87 Time for Cross-blocking 2nd Harm. 3 Cycle A

4.7 Group 87 Differential Protection; Group Restr. n.HM

Group 87 Differential Protection; Group Restr. n.HM


No. Settings Value Group

1276 87 n-th Harmonic Content in I-DIFF 30 % A


1277A 87 Time for Cross-blocking n-th Harm. 0 Cycle A
1278A 87 Limit IDIFFmax of n-th Harm.Restr. 1.5 I/InO A

Page 8 of 9
7UT613 V4_6_prn_18_17_52
Group Supervision; Group General
ISWP / 20MVA Trafo / 7UT613
SIMATIC V4.6/7UT613 28.04.20 18:17:52

4.8 Group Supervision; Group General

Group Supervision; Group General


No. Settings Value Group

8401 Fast Broken Current-wire Supervision OFF A


8403 60 FL Fuse Failure Monitor OFF A
8414 Delay time for BWD supervision 1.0 sec A
8415 min differential current for BW D 1.00 I/InO A
8422A I< for FFM detection M1 0.10 A A
8423A I< for FFM detection M2 0.10 A A
8424A I< for FFM detection M3 0.10 A A
2911A Minimum Voltage Threshold V> 20 V A
8426A Maximum Voltage Threshold V< (3phase) 5 V A

Page 9 of 9
7SJ624 V4_9_prn_16_09_28

ISWP / Bus Coupler / 7SJ624


SIMATIC V4.9/7SJ624 27.04.20 16:09:28

ISWP / Bus Coupler / 7SJ624 V4.9

MLFB: 7SJ6241**B901FG4
Parameter-set version: V04.95.00
Device path: C:\Siemens\DIGSI4\D4PROJ\Iswp\P7DI\GV\SD\0000000a
Author:
Creation date: 27.04.20 15:26:37
Last modified: 27.04.20 15:40:44
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Device Configuration ................................................................................................................................................ 2


2 Power System Data 1 ...........................................................................................................................................… 3
2.1 Group Power System Data 1; Group Power System ...........................................................................................… 3
2.2 Group Power System Data 1; Group CT's ...........................................................................................................… 3
2.3 Group Power System Data 1; Group VT's ............................................................................................................… 3
2.4 Group Power System Data 1; Group Breaker .......................................................................................................... 4
2.5 Group Power System Data 1; Group Prot.Op. quant. ..........................................................................................… 4
3 Settings groups ....................................................................................................................................................… 5
3.1 Group Power System Data 2; Group General ......................................................................................................… 5
3.2 Group 67 Directional Phase/Ground Overcurrent; Group General ......................................................................… 5
3.3 Group 67 Directional Phase/Ground Overcurrent; Group 67 ...............................................................................… 5
3.4 Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC ......................................................................… 6
3.5 Group 67 Directional Phase/Ground Overcurrent; Group 67N .............................................................................… 6
3.6 Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC ....................................................................… 7
3.7 Group Measurement Supervision; Group General ...............................................................................................… 7
3.8 Group Measurement Supervision; Group Fuse Fail Mon. ....................................................................................… 7
3.9 Group Measurement Supervision; Group MeasSupervision .................................................................................... 7
3.10 Group Measurement Supervision; Group VT broken wire ...................................................................................… 8
3.11 Group Energy; Group Measurement ........................................................................................................................ 8

Page 1 of 8
7SJ624 V4_9_prn_16_09_28
Device Configuration
ISWP / Bus Coupler / 7SJ624
SIMATIC V4.9/7SJ624 27.04.20 16:09:28

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0104 Oscillographic Fault Records Disabled
0112 50/51 Disabled
0113 50N/51N Disabled
0115 67, 67-TOC Time Overcurrent Curve IEC
0116 67N, 67N-TOC Time Overcurrent Curve IEC
0127 50 1Ph Disabled
0117 Cold Load Pickup Disabled
0122 2nd Harmonic Inrush Restraint Disabled
0131 (sensitive) Ground fault Disabled
0130 (sens.) Ground fault dir. characteristic cos phi / sin phi measurement (standard)
0140 46 Negative Sequence Protection Disabled
0142 49 Thermal Overload Protection Disabled
0150 27, 59 Under/Overvoltage Protection Disabled
0154 81 Over/Underfrequency Protection Disabled
0155 27 / Q dir. con. Protection Disabled
0161 25 Function group 1 Disabled
0170 50BF Breaker Failure Protection Disabled
0172 52 Breaker W ear Monitoring Disabled
0182 74TC Trip Circuit Supervision Disabled
Flexible Function

Page 2 of 8
7SJ624 V4_9_prn_16_09_28
Power System Data 1
ISWP / Bus Coupler / 7SJ624
SIMATIC V4.9/7SJ624 27.04.20 16:09:28

2 Power System Data 1

2.1 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0214 Rated Frequency 50 Hz All


0209 Phase Sequence ABC All
0276 Unit of temperature measurement Degree Celsius All
0201 CT Starpoint towards Line All
0280 Holmgreen-conn. (for fast sum-i-monit.) NO All
0251A CT Connection Ia, Ib, Ic, (IGnd) All
0213 VT Connection, three-phase Van, Vbn, Vcn All
0240 VT Connection, single-phase NO All
0235A Storage of th. Replicas w/o Power Supply NO All
0250A 50, 51 Time Overcurrent with 2ph. prot. OFF All

2.2 Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's


No. Settings Value Group

0204 CT Rated Primary Current 600 A All


0205 CT Rated Secondary Current 1A All
0217 Ignd-CT rated primary current 600 A All
0218 Ignd-CT rated secondary current 1A All

2.3 Group Power System Data 1; Group VT's

Group Power System Data 1; Group VT's


No. Settings Value Group

0202 Rated Primary Voltage 33.00 kV All


0203 Rated Secondary Voltage (L-L) 110 V All
0206A Matching ratio Phase-VT To Open-Delta-VT 1.73 All

Page 3 of 8
7SJ624 V4_9_prn_16_09_28
Group Power System Data 1; Group Breaker
ISWP / Bus Coupler / 7SJ624
SIMATIC V4.9/7SJ624 27.04.20 16:09:28

2.4 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0210A Minimum TRIP Command Duration 0.15 sec All


0211A Maximum Close Command Duration 1.00 sec All
0212 Closed Breaker Min. Current Threshold 0.04 A All

2.5 Group Power System Data 1; Group Prot.Op. quant.

Group Power System Data 1; Group Prot.Op. quant.


No. Settings Value Group

0613A 50N/51N/67N Ground Overcurrent with Ignd (measured) All

Page 4 of 8
7SJ624 V4_9_prn_16_09_28
Settings groups
ISWP / Bus Coupler / 7SJ624
SIMATIC V4.9/7SJ624 27.04.20 16:09:28

3 Settings groups

3.1 Group Power System Data 2; Group General

Group Power System Data 2; Group General


No. Settings Value Group

1101 Measurem:FullScaleVoltage(Equipm.rating) 33.00 kV A


1102 Measurem:FullScaleCurrent(Equipm.rating) 600 A A
1108 P,Q operational measured values sign not reversed A
1114A Operational current measurement < 1% NO A

3.2 Group 67 Directional Phase/Ground Overcurrent; Group General

Group 67 Directional Phase/Ground Overcurrent; Group General


No. Settings Value Group

1501 67, 67-TOC Phase Time Overcurrent ON A


1513A Manual Close Mode 67-2 instantaneously A
1526 67-3 Direction Forward A
1523 67-2 Direction Forward A
1524 67-1 Direction Forward A
1525 67-TOC Direction Forward A
1518A 67 Drop-Out Time Delay 0.00 sec A
1519A Rotation Angle of Reference Voltage 45 ° A
1601 67N, 67N-TOC Ground Time Overcurrent ON A
1613A Manual Close Mode 67N-2 instantaneously A
1626 67N-3 Direction Forward A
1623 67N-2 Direction Forward A
1624 67N-1 Direction Forward A
1625 67N-TOC Direction Forward A
1617 Ground Polarization with VN and IN A
1618A 67N Drop-Out Time Delay 0.00 sec A
1619A Rotation Angle of Reference Voltage -45 ° A

3.3 Group 67 Directional Phase/Ground Overcurrent; Group 67

Group 67 Directional Phase/Ground Overcurrent; Group 67


No. Settings Value Group

1527A 67-3 measurement of Fundamental component A


1532A 67-3 active always A

Page 5 of 8
7SJ624 V4_9_prn_16_09_28

ISWP / Bus Coupler / 7SJ624


SIMATIC V4.9/7SJ624 27.04.20 16:09:28

Group 67 Directional Phase/Ground Overcurrent; Group 67(2)


No. Settings Value Group

1528 67-3 Pickup oo A A


1529 67-3 Time Delay oo sec A
1520A 67-2 measurement of Fundamental component A
1514A 67-2 active always A
1502 67-2 Pickup oo A A
1503 67-2 Time Delay oo sec A
1521A 67-1 measurement of Fundamental component A
1504 67-1 Pickup 7.00 A A
1505 67-1Time Delay 0.25 sec A

3.4 Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC

Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC


No. Settings Value Group

1522A 67-TOC measurement of Fundamental component A


1507 67-TOC Pickup 1.00 A A
1508 67-TOC Time Dial 0.20 sec A
1510 Drop-Out Characteristic Disk Emulation A
1511 IEC Curve Normal Inverse A

3.5 Group 67 Directional Phase/Ground Overcurrent; Group 67N

Group 67 Directional Phase/Ground Overcurrent; Group 67N


No. Settings Value Group

1627A 67N-3 measurement of Fundamental component A


1632A 67N-3 active always A
1628 67N-3 Pickup oo A A
1629 67N-3 Time Delay oo sec A
1620A 67N-2 measurement of Fundamental component A
1614A 67N-2 active always A
1602 67N-2 Pickup oo A A
1603 67N-2 Time Delay oo sec A
1621A 67N-1 measurement of Fundamental component A
1604 67N-1 Pickup 2.00 A A
1605 67N-1 Time Delay 0.30 sec A

Page 6 of 8
7SJ624 V4_9_prn_16_09_28
Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC
ISWP / Bus Coupler / 7SJ624
SIMATIC V4.9/7SJ624 27.04.20 16:09:28

3.6 Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC

Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC


No. Settings Value Group

1622A 67N-TOC measurement of Fundamental component A


1607 67N-TOC Pickup 0.20 A A
1608 67N-TOC Time Dial 0.30 sec A
1610 Drop-Out Characteristic Disk Emulation A
1611 IEC Curve Normal Inverse A

3.7 Group Measurement Supervision; Group General

Group Measurement Supervision; Group General


No. Settings Value Group

5301 Fuse Fail Monitor OFF A


5310 Block protection by FFM YES A
8101 Measurement Supervision ON A
5201 VT broken wire supervision OFF A

3.8 Group Measurement Supervision; Group Fuse Fail Mon.

Group Measurement Supervision; Group Fuse Fail Mon.


No. Settings Value Group

5302 Zero Sequence Voltage 30 V A


5303 Residual Current 0.10 A A
5308A Differential Current Threshold (3phase) 0.10 A A

3.9 Group Measurement Supervision; Group MeasSupervision

Group Measurement Supervision; Group MeasSupervision


No. Settings Value Group

8102 Voltage Threshold for Balance Monitoring 50 V A


8103 Balance Factor for Voltage Monitor 0.75 A
8104 Current Threshold for Balance Monitoring 0.50 A A
8105 Balance Factor for Current Monitor 0.50 A
8110A T Balance Factor for Voltage Monitor 5 sec A
8111A T Current Balance Monitor 5 sec A

Page 7 of 8
7SJ624 V4_9_prn_16_09_28

ISWP / Bus Coupler / 7SJ624


SIMATIC V4.9/7SJ624 27.04.20 16:09:28

3.10 Group Measurement Supervision; Group VT broken wire

Group Measurement Supervision; Group VT broken wire


No. Settings Value Group

5202 Threshold voltage sum 8.0 V A


5203 Maximum phase to phase voltage 16.0 V A
5204 Minimum phase to phase voltage 16.0 V A
5205 Symmetry phase to phase voltages 16.0 V A
5206 Minimum line current 0.04 A A
5208 Alarm delay time 1.25 sec A

3.11 Group Energy; Group Measurement


Group Energy; Group Measurement
No. Settings Value Group

8315 Meter resolution Standard A

Page 8 of 8
132kV F870_7SS522 V4_7_prn_17_54_28

132kV_Fixed Setting / RAFM / BB /


SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

132kV_Fixed Setting / RAFM / BB / 132kV F870_7SS522 V4.7

MLFB: 7SS5220**B921!A0
Parameter-set version: V04.73.04
Device path: D:\Network Consultancy\2017\PH_12\NCC\S-10
\1_RAFM\FSD\132kV FSD_RAFM\Work\BCU setting\RAF METRO_132KV\P7DI\GV\SD\0000
02b7
Author:
Creation date: 18.04.16 16:23:34
Last modified: 27.04.20 17:40:33
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 Substation Data ....................................................................................................................................................… 2


1.1 Group Power System Data 1; Group Power System ...........................................................................................… 2
2 Oscillographic Fault Records ...............................................................................................................................… 3
2.1 Group Oscillographic Fault Records; Group Osc. Fault Rec. ...............................................................................… 3
3 Settings groups ....................................................................................................................................................… 4
3.1 Group Protection general; Group Power System ..................................................................................................... 4
3.2 Group Bus Bar Protection; Group Bus Zone ............................................................................................................ 4
3.3 Group Bus Bar Protection; Group Check Zone ........................................................................................................ 4
3.4 Group Breaker Failure Protection; Group Breaker Failure ....................................................................................... 4
3.5 Group Monitoring; Group General ........................................................................................................................… 5
3.6 Group Monitoring; Group Idiff Superv ..................................................................................................................… 5
3.7 Group Monitoring; Group 0-Cross Superv ............................................................................................................… 5
3.8 Group Monitoring; Group CB/DCO Superv ..........................................................................................................… 5
3.9 Group Monitoring; Group CB Test ........................................................................................................................… 6
4 Bay units ...............................................................................................................................................................… 7
4.1 Function blocks ....................................................................................................................................................… 7
4.1.1 Group Bay Unit @01; Group General ..................................................................................................................… 7
4.1.2 Group Bay Unit @01; Group Breaker Failure .......................................................................................................… 7
4.1.3 Group Bay Unit @01; Group End fault stage .......................................................................................................… 8
4.1.4 Group Bay Unit @01; Group Breaker ...................................................................................................................… 8

Page 1 of 8
132kV F870_7SS522 V4_7_prn_17_54_28
Substation Data
132kV_Fixed Setting / RAFM / BB /
SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

1 Substation Data

1.1 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

5104 Nominal frequency 50 Hz All

Page 2 of 8
132kV F870_7SS522 V4_7_prn_17_54_28
Oscillographic Fault Records
132kV_Fixed Setting / RAFM / BB /
SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

2 Oscillographic Fault Records

2.1 Group Oscillographic Fault Records; Group Osc. Fault Rec.

Group Oscillographic Fault Records; Group Osc. Fault Rec.


No. Settings Value Group

6401A Mode of fault recording global storage, initiation by CU All


6404 Max. length of a W aveform Capture Record 2.00 sec All
6405 Captured W aveform Prior to Trigger 0.20 sec All
6406 Captured W aveform after Event 0.20 sec All
6407 Capture Time via Binary Input 0.40 sec All

Page 3 of 8
132kV F870_7SS522 V4_7_prn_17_54_28
Settings groups
132kV_Fixed Setting / RAFM / BB /
SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

3 Settings groups

3.1 Group Protection general; Group Power System

Group Protection general; Group Power System


No. Settings Value Group

6106 Minimum duration of TRIP command 0.15 sec All


6320A Sensitive characteristic switchover blocked All
6318 Control release for bay units released All
5401 Selective protection for transfer busbar YES All
5112A Bay unit output enable during test mode NO All
5108A Test mode for module SK OFF All
5111 Language of bay units English All
6120A Additional criterion for tripping nonexistent All

3.2 Group Bus Bar Protection; Group Bus Zone

Group Bus Bar Protection; Group Bus Zone


No. Settings Value Group

6101 Stabilizing factor - BZ 0.40 All


6102 Diff-current threshold - BZ 1.00 I / Ino All

3.3 Group Bus Bar Protection; Group Check Zone


Group Bus Bar Protection; Group Check Zone
No. Settings Value Group

6103 Stabilizing factor - CZ 0.30 All


6104 Diff-current threshold - CZ 1.00 I / Ino All

3.4 Group Breaker Failure Protection; Group Breaker Failure

Group Breaker Failure Protection; Group Breaker Failure


No. Settings Value Group

6201 Stabilizing factor BF protection 0.50 All

Page 4 of 8
132kV F870_7SS522 V4_7_prn_17_54_28

132kV_Fixed Setting / RAFM / BB /


SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

3.5 Group Monitoring; Group General

Group Monitoring; Group General


No. Settings Value Group

6317 Supervision bin. input TRIP-Release 0.06 sec All

3.6 Group Monitoring; Group Idiff Superv

Group Monitoring; Group Idiff Superv


No. Settings Value Group

6306 Differential current supervision ON All


6307 Time delay for diff-current supervision 2.00 sec All
6308 Limit value diff-current supervision -BZ 0.10 I / Ino All
6309 Limit value diff-current supervision -CZ 0.10 I / Ino All
6310 Diff-current supervision mode -BZ blocking during the fault All
6311 Diff-current supervision mode -CZ alarm without blocking All

3.7 Group Monitoring; Group 0-Cross Superv

Group Monitoring; Group 0-Cross Superv


No. Settings Value Group

6312A Zero crossing supervision ON All


6313A Threshold for zero crossing supervision 0.50 I / Ino All

3.8 Group Monitoring; Group CB/DCO Superv

Group Monitoring; Group CB/DCO Superv


No. Settings Value Group

6315 CB supervision time 7.00 sec All


6301 Limit value disconnector time 7.00 sec All
6302 Reaction on disconnector malfunction alarm without blocking All
6303 Treatment disconnector status on DC fail old disconnector status All
6304 Treatment disconn. status not plausible ON All

Page 5 of 8
132kV F870_7SS522 V4_7_prn_17_54_28
Group Monitoring; Group CB Test
132kV_Fixed Setting / RAFM / BB /
SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

3.9 Group Monitoring; Group CB Test

Group Monitoring; Group CB Test


No. Settings Value Group

6316 Limit value for circuit breaker test 0.05 I / In All

Page 6 of 8
132kV F870_7SS522 V4_7_prn_17_54_28
Bay units
132kV_Fixed Setting / RAFM / BB /
SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

4 Bay units

4.1 Function blocks

4.1.1 Group Bay Unit @01; Group General

Group Bay Unit @01; Group General


No. Settings Value Group

0112 Bay status in service All


0106A Combi-Coupler NO All
0151A Maintenance for disconnector 1 YES All
0152A Maintenance for disconnector 2 YES All
0153A Maintenance for disconnector 3 YES All
0154A Maintenance for disconnector 4 YES All
0155A Maintenance for disconnector 5 YES All
0156A Maintenance for CB YES All

4.1.2 Group Bay Unit @01; Group Breaker Failure


Group Bay Unit @01; Group Breaker Failure
No. Settings Value Group

0114 Binary input mode / supervision BF Initiation with supervision All


0115 Operation mode BF TRIP repetition with current query All
0116 Low-current mode BF OFF All
0117 TRIP repeat mode 3pole All
0118 Current threshold for BF 0.50 I / In All
0119A Current threshold for BF - EF 0.25 I / In All
0120 Time delay for BF with 1-pole faults 0.25 sec All
0121 Time delay for BF with multi-pole faults 0.25 sec All
0122 Time delay for BF low current mode 0.25 sec All
0123A Time delay for BF pulse mode 0.50 sec All
0124 Time delay BF after CB fault 0.10 sec All
0125 Time delay for TRIP repeat 0.12 sec All
0127 Supervision bin. input BF-release 15.00 sec All
0128 Supervision time BF start / release 0.06 sec All

Page 7 of 8
132kV F870_7SS522 V4_7_prn_17_54_28
Group Bay Unit @01; Group End fault stage
132kV_Fixed Setting / RAFM / BB /
SIMATIC 132kV F870_7SS522 V4.7/7SS522 27.04.20 17:54:28

4.1.3 Group Bay Unit @01; Group End fault stage

Group Bay Unit @01; Group End fault stage


No. Settings Value Group

0129 End fault protection ON All


0126 Time delay for CB open 0.00 sec All

4.1.4 Group Bay Unit @01; Group Breaker

Group Bay Unit @01; Group Breaker


No. Settings Value Group

0113 Current threshold for TRIP release 0.00 I / In All