You are on page 1of 11

TRAFOBCPU_prn_14_39_11

Factor test ML30MW / 30MW Trafo /


SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

Factor test ML30MW / 30MW Trafo / TRAFOBCPU

MLFB: 7SJ6451**B921FG1
Parameter-set version: V04.96.02
Device path: C:\Siemens\DIGSI4\D4Proj\Factor_3\P7DI\GV\SD\0000000b
Author:
Creation date: 16.12.19 11:35:09
Last modified: 30.07.20 14:36:23
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS

1 General Device Settings ................................................................................................................................................. 2


1.1 Group Device, General Settings; Group General ............................................................................................................ 2
2 Power System Data 1 ..................................................................................................................................................... 3
2.1 Group Power System Data 1; Group Power System ...................................................................................................... 3
2.2 Group Power System Data 1; Group CT's ...................................................................................................................... 3
2.3 Group Power System Data 1; Group VT's ...................................................................................................................... 3
2.4 Group Power System Data 1; Group Breaker ................................................................................................................. 4
2.5 Group Power System Data 1; Group Prot.Op. quant. ..................................................................................................... 4
3 Settings groups ............................................................................................................................................................... 5
3.1 Group Power System Data 2; Group General ................................................................................................................. 5
3.2 Group 50/51 Phase/Ground Overcurrent; Group General .............................................................................................. 5
3.3 Group 50/51 Phase/Ground Overcurrent; Group 50 ....................................................................................................... 5
3.4 Group 50/51 Phase/Ground Overcurrent; Group 51 ....................................................................................................... 6
3.5 Group 50/51 Phase/Ground Overcurrent; Group 50N .................................................................................................... 6
3.6 Group 50/51 Phase/Ground Overcurrent; Group 51N .................................................................................................... 7
3.7 Group 50/51 Phase/Ground Overcurrent; Group InrushRestraint ................................................................................... 7
3.8 Group 27/59 Under/Over Voltage; Group General .......................................................................................................... 7
3.9 Group 27/59 Under/Over Voltage; Group 27 .................................................................................................................. 7
3.10 Group 27/59 Under/Over Voltage; Group 59 .................................................................................................................. 8
3.11 Group Measurement Supervision; Group General .......................................................................................................... 8
3.12 Group Measurement Supervision; Group Fuse Fail Mon. ............................................................................................... 8
3.13 Group Measurement Supervision; Group MeasSupervision ........................................................................................... 9
3.14 Group Measurement Supervision; Group VT broken wire .............................................................................................. 9
3.15 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group General .................................................................................. 9
3.16 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 50Ns .................................................................................... 10
3.17 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 51Ns .................................................................................... 10
3.18 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 64 Disp. Volt. ....................................................................... 10
3.19 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group Direction 67Ns ..................................................................... 10
3.20 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group CT's ..................................................................................... 11
3.21 Group Energy; Group Measurement ............................................................................................................................. 11

Page 1 of 11
TRAFOBCPU_prn_14_39_11
General Device Settings
Factor test ML30MW / 30MW Trafo /
SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

1 General Device Settings

1.1 Group Device, General Settings; Group General

Group Device, General Settings; Group General


No. Settings Value Group

0610 Fault Display on LED / LCD Display Targets on every Pickup All
0611 Spontaneous display of flt.annunciations YES All
0617A T103-transfer limeted to 16 meas. values NO All
0625A Minimum hold time of latched LEDs 0 min All
0700 GOOSE-Stop NO All

Page 2 of 11
TRAFOBCPU_prn_14_39_11
Power System Data 1
Factor test ML30MW / 30MW Trafo /
SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

2 Power System Data 1

2.1 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0214 Rated Frequency 50 Hz All


0209 Phase Sequence ABC All
0276 Unit of temperature measurement Degree Celsius All
0201 CT Starpoint towards Line All
0280 Holmgreen-conn. (for fast sum-i-monit.) NO All
0251A CT Connection Ia, Ib, Ic, (IGnd) All
0213 VT Connection, three-phase Van, Vbn, Vcn All
0240 VT Connection, single-phase NO All
0235A Storage of th. Replicas w/o Power Supply NO All
0250A 50, 51 Time Overcurrent with 2ph. prot. OFF All
0281A Change switch.authority via binary input NO All
0282A Interlocking on or off via binary input NO All

2.2 Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's


No. Settings Value Group

0204 CT Rated Primary Current 150 A All


0205 CT Rated Secondary Current 1A All
0217 Ignd-CT rated primary current 150 A All
0218 Ignd-CT rated secondary current 1A All

2.3 Group Power System Data 1; Group VT's

Group Power System Data 1; Group VT's


No. Settings Value Group

0202 Rated Primary Voltage 132.00 kV All


0203 Rated Secondary Voltage (L-L) 110 V All
0206A Matching ratio Phase-VT To Open-Delta-VT 1.73 All

Page 3 of 11
TRAFOBCPU_prn_14_39_11

Factor test ML30MW / 30MW Trafo /


SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

2.4 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0210A Minimum TRIP Command Duration 0.15 sec All


0211A Maximum Close Command Duration 1.00 sec All
0212 Closed Breaker Min. Current Threshold 0.04 A All

2.5 Group Power System Data 1; Group Prot.Op. quant.

Group Power System Data 1; Group Prot.Op. quant.


No. Settings Value Group

0613A 50N/51N/67N Ground Overcurrent with 3I0 (calculated) All


0614A Opera. Quantity for 59 Overvolt. Prot. Vphph All
0615A Opera. Quantity for 27 Undervolt. Prot. Vphph All

Page 4 of 11
TRAFOBCPU_prn_14_39_11
Settings groups
Factor test ML30MW / 30MW Trafo /
SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

3 Settings groups

3.1 Group Power System Data 2; Group General

Group Power System Data 2; Group General


No. Settings Value Group

1101 Measurem:FullScaleVoltage(Equipm.rating) 132.00 kV A


1102 Measurem:FullScaleCurrent(Equipm.rating) 150 A A
1108 P,Q operational measured values sign not reversed A
1114A Operational current measurement < 1% NO A

3.2 Group 50/51 Phase/Ground Overcurrent; Group General

Group 50/51 Phase/Ground Overcurrent; Group General


No. Settings Value Group

1201 50, 51 Phase Time Overcurrent ON A


1213A Manual Close Mode 50-2 instantaneously A
1215A 50 Drop-Out Time Delay 0.00 sec A
1301 50N, 51N Ground Time Overcurrent ON A
1313A Manual Close Mode 50N-2 instantaneously A
1315A 50N Drop-Out Time Delay 0.00 sec A
2201 Inrush Restraint ON A

3.3 Group 50/51 Phase/Ground Overcurrent; Group 50

Group 50/51 Phase/Ground Overcurrent; Group 50


No. Settings Value Group

1219A 50-3 measurement of Fundamental component A


1216A 50-3 active Always A
1217 50-3 Pickup oo A A
1218 50-3 Time Delay 0.00 sec A
1220A 50-2 measurement of Fundamental component A
1214A 50-2 active Always A
1202 50-2 Pickup oo A A
1203 50-2 Time Delay 0.00 sec A

Page 5 of 11
TRAFOBCPU_prn_14_39_11

Factor test ML30MW / 30MW Trafo /


SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

Group 50/51 Phase/Ground Overcurrent; Group 50(2)


No. Settings Value Group

1221A 50-1 measurement of Fundamental component A


1204 50-1 Pickup 3.50 A A
1205 50-1 Time Delay 0.05 sec A

3.4 Group 50/51 Phase/Ground Overcurrent; Group 51

Group 50/51 Phase/Ground Overcurrent; Group 51


No. Settings Value Group

1222A 51 measurement of Fundamental component A


1207 51 Pickup 0.96 A A
1208 51 Time Dial 0.05 sec A
1210 Drop-out characteristic Disk Emulation A
1211 IEC Curve Normal Inverse A
1223 51V Voltage Influence NO A
1224 51V V< Threshold for Release Ip 75.0 V A

3.5 Group 50/51 Phase/Ground Overcurrent; Group 50N

Group 50/51 Phase/Ground Overcurrent; Group 50N


No. Settings Value Group

1319A 50N-3 measurement of Fundamental component A


1316A 50N-3 active Always A
1317 50N-3 Pickup oo A A
1318 50N-3 Time Delay 0.00 sec A
1320A 50N-2 measurement of Fundamental component A
1314A 50N-2 active Always A
1302 50N-2 Pickup oo A A
1303 50N-2 Time Delay 0.00 sec A
1321A 50N-1 measurement of Fundamental component A
1304 50N-1 Pickup 0.50 A A
1305 50N-1 Time Delay 0.05 sec A

Page 6 of 11
TRAFOBCPU_prn_14_39_11
Group 50/51 Phase/Ground Overcurrent; Group 51N
Factor test ML30MW / 30MW Trafo /
SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

3.6 Group 50/51 Phase/Ground Overcurrent; Group 51N

Group 50/51 Phase/Ground Overcurrent; Group 51N


No. Settings Value Group

1322A 51N measurement of Fundamental component A


1307 51N Pickup 0.20 A A
1308 51N Time Dial 0.05 sec A
1310 Drop-Out Characteristic Disk Emulation A
1311 IEC Curve Normal Inverse A

3.7 Group 50/51 Phase/Ground Overcurrent; Group InrushRestraint

Group 50/51 Phase/Ground Overcurrent; Group InrushRestraint


No. Settings Value Group

2202 2nd. harmonic in % of fundamental 15 % A


2203 Cross Block YES A
2204 Cross Block Time 0.00 sec A
2205 Maximum Current for Inrush Restraint 7.50 A A

3.8 Group 27/59 Under/Over Voltage; Group General

Group 27/59 Under/Over Voltage; Group General


No. Settings Value Group

5101 27 Undervoltage Protection ON A


5001 59 Overvoltage Protection ON A

3.9 Group 27/59 Under/Over Voltage; Group 27

Group 27/59 Under/Over Voltage; Group 27


No. Settings Value Group

5102 27-1 Pickup 88 V A


5106 27-1 Time Delay 3.00 sec A
5110 27-2 Pickup 70 V A
5112 27-2 Time Delay 0.50 sec A

Page 7 of 11
TRAFOBCPU_prn_14_39_11

Factor test ML30MW / 30MW Trafo /


SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

Group 27/59 Under/Over Voltage; Group 27(2)


No. Settings Value Group

5113A 27-1 Dropout Ratio 1.20 A


5114A 27-2 Dropout Ratio 1.20 A
5120A Current Supervision ON A

3.10 Group 27/59 Under/Over Voltage; Group 59

Group 27/59 Under/Over Voltage; Group 59


No. Settings Value Group

5002 59-1 Pickup 121 V A


5004 59-1 Time Delay 1.00 sec A
5005 59-2 Pickup 120 V A
5007 59-2 Time Delay 0.50 sec A
5017A 59-1 Dropout Ratio 0.95 A
5018A 59-2 Dropout Ratio 0.95 A

3.11 Group Measurement Supervision; Group General

Group Measurement Supervision; Group General


No. Settings Value Group

5301 Fuse Fail Monitor OFF A


5310 Block protection by FFM YES A
8101 Measurement Supervision ON A
5201 VT broken wire supervision OFF A

3.12 Group Measurement Supervision; Group Fuse Fail Mon.

Group Measurement Supervision; Group Fuse Fail Mon.


No. Settings Value Group

5302 Zero Sequence Voltage 30 V A


5303 Residual Current 0.10 A A
5308A Differential Current Threshold (3phase) 0.10 A A

Page 8 of 11
TRAFOBCPU_prn_14_39_11

Factor test ML30MW / 30MW Trafo /


SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

3.13 Group Measurement Supervision; Group MeasSupervision

Group Measurement Supervision; Group MeasSupervision


No. Settings Value Group

8102 Voltage Threshold for Balance Monitoring 50 V A


8103 Balance Factor for Voltage Monitor 0.75 A
8104 Current Threshold for Balance Monitoring 0.50 A A
8105 Balance Factor for Current Monitor 0.50 A
8110A T Balance Factor for Voltage Monitor 5 sec A
8111A T Current Balance Monitor 5 sec A

3.14 Group Measurement Supervision; Group VT broken wire

Group Measurement Supervision; Group VT broken wire


No. Settings Value Group

5202 Threshold voltage sum 8.0 V A


5203 Maximum phase to phase voltage 16.0 V A
5204 Minimum phase to phase voltage 16.0 V A
5205 Symmetry phase to phase voltages 16.0 V A
5206 Minimum line current 0.04 A A
5208 Alarm delay time 1.25 sec A

3.15 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group General

Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group General
No. Settings Value Group

3101 (Sensitive) Ground Fault ON A


3111 Time-DELAY Pickup 1.00 sec A
3130 Sensitive Ground Fault PICKUP criteria Vgnd OR INs A
3121A 50Ns Drop-Out Time Delay 0.00 sec A

Page 9 of 11
TRAFOBCPU_prn_14_39_11
Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 50Ns
Factor test ML30MW / 30MW Trafo /
SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

3.16 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 50Ns

Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 50Ns
No. Settings Value Group

3113 50Ns-2 Pickup 10.00 A A


3114 50Ns-2 Time Delay 1.00 sec A

3.17 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 51Ns

Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 51Ns
No. Settings Value Group

3119 51Ns Pickup 0.25 A A


3120 51Ns Time Dial 0.05 sec A
3146 Drop-out characteristic Disk Emulation A
3144 IEC Curve Normal Inverse A

3.18 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 64 Disp. Volt.

Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group 64 Disp. Volt.
No. Settings Value Group

3106 L-Gnd Voltage of Faulted Phase Vph Min 40 V A


3107 L-Gnd Voltage of Unfaulted Phase Vph Max 75 V A
3110 64-1 Ground Displacement Voltage 70.0 V A
3112 64-1 Time Delay 10.00 sec A

3.19 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group Direction 67Ns

Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group Direction 67Ns
No. Settings Value Group

3115 67Ns-2 Direction Non-Directional A


3122 67Ns-1 Direction Non-Directional A
3123 Release directional element 0.50 A A
3124 Correction Angle for Dir. Determination 0.0 ° A
3125 Measurement method for Direction COS Phi A

Page 10 of 11
TRAFOBCPU_prn_14_39_11

Factor test ML30MW / 30MW Trafo /


SIMATIC TRAFOBCPU/7SJ645 30.07.20 14:39:11

Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group Direction 67Ns(2)
No. Settings Value Group

3126 Reset Delay 1 sec A


3160 Alpha1 (reduction directional area) 2° A
3161 Alpha2 (reduction directional area) 2° A

3.20 Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group CT's

Group 64, 50Ns, 51Ns, 67Ns (Sensitive) Gnd Flt; Group CT's
No. Settings Value Group

3102 Current I1 for CT Angle Error 1.00 A A


3103 CT Angle Error at I1 0.0 ° A
3104 Current I2 for CT Angle Error 10.00 A A
3105 CT Angle Error at I2 0.0 ° A

3.21 Group Energy; Group Measurement

Group Energy; Group Measurement


No. Settings Value Group

8315 Meter resolution Standard A

Page 11 of 11