Device Configuration 0103 Setting Group Change Option Disabled 0106 Voltage transformer connection NO 0107 Current transformer connection YES 0110 Trip mode 1/3 Pole 0126 Backup overcurrent Disabled 0139 Breaker Failure Protection Enabled 0140 Trip Circuit Supervision Disabled Setting Group A Breaker Failure (Secondary Values) 3901 Breaker Failure Protection ON 3902 Pick-up threshold I> 0.20 A Set this parameter to YES if the first stage is to trip 1- 3903 1 Pole Retrip with Stage 1 T1 YES* pole, otherwise set it to NO. Same Retrip delay provided 3904 T1, Delay after 1pole start (local trip) 0.05 sec please for 1-pole & 3 pole 3905 T1, Delay after 3pole start (local trip) 0.05 sec please check as per site 3906 T2, Delay of 2nd stage (busbar trip) 0.20 sec 3907 T3, Delay for start with defective bkr. 0.00 sec 3908 Trip output selection with defective bkr NO 3909 Check Breaker contacts YES 3913 T2 Start Criteria Parallel with delay time T1 Kindly check as per site 3921 End fault protection OFF requirement 3922 Trip delay of end fault protection 2.00 sec 3931 Pole Discrepancy supervision OFF 3932 Trip delay with pole discrepancy 2.00 sec *please cross check with the client philosophy