BREAKER FAILURE PROTECTION RELAY 7VK610

Address Description Settings Remark


Device Configuration
0103 Setting Group Change Option Disabled
0106 Voltage transformer connection NO
0107 Current transformer connection YES
0110 Trip mode 1/3 Pole
0126 Backup overcurrent Disabled
0139 Breaker Failure Protection Enabled
0140 Trip Circuit Supervision Disabled
Setting Group A
Breaker Failure (Secondary Values)
3901 Breaker Failure Protection ON
3902 Pick-up threshold I> 0.20 A
Set this parameter to YES if
the first stage is to trip 1-
3903 1 Pole Retrip with Stage 1 T1 YES* pole, otherwise set it to NO.
Same Retrip delay provided
3904 T1, Delay after 1pole start (local trip) 0.05 sec please for 1-pole & 3 pole
3905 T1, Delay after 3pole start (local trip) 0.05 sec please check as per site
3906 T2, Delay of 2nd stage (busbar trip) 0.20 sec
3907 T3, Delay for start with defective bkr. 0.00 sec
3908 Trip output selection with defective bkr NO
3909 Check Breaker contacts YES
3913 T2 Start Criteria Parallel with delay time T1
Kindly check as per site
3921 End fault protection OFF
requirement
3922 Trip delay of end fault protection 2.00 sec
3931 Pole Discrepancy supervision OFF
3932 Trip delay with pole discrepancy 2.00 sec
*please cross check with the client philosophy