This document provides settings for the synchronizing function of a power system. It includes:
1) The synchronizing function is turned on and uses circuit breaker 52 to synchronize.
2) Voltage limits are 88V minimum and 121V maximum for synchronization.
3) Thresholds for voltages V1 and V2 are 45V without voltage and 80V with voltage.
4) Synchronization will occur when voltages and frequencies are within 10V, 0.1Hz and 20 degrees of each other.
This document provides settings for the synchronizing function of a power system. It includes:
1) The synchronizing function is turned on and uses circuit breaker 52 to synchronize.
2) Voltage limits are 88V minimum and 121V maximum for synchronization.
3) Thresholds for voltages V1 and V2 are 45V without voltage and 80V with voltage.
4) Synchronization will occur when voltages and frequencies are within 10V, 0.1Hz and 20 degrees of each other.
This document provides settings for the synchronizing function of a power system. It includes:
1) The synchronizing function is turned on and uses circuit breaker 52 to synchronize.
2) Voltage limits are 88V minimum and 121V maximum for synchronization.
3) Thresholds for voltages V1 and V2 are 45V without voltage and 80V with voltage.
4) Synchronization will occur when voltages and frequencies are within 10V, 0.1Hz and 20 degrees of each other.
6102 Synchronizable circuit breaker 52Breaker All 6103 Minimum voltage limit: Vmin 88 V All 6104 Maximum voltage limit: Vmax 121 V All 6105 Threshold V1, V2 without voltage 45 V All 6106 Threshold V1, V2 with voltage 80 V All 6113A Switching at synchronous condition YES All 6107 ON-Command at V1< and V2> YES All 6108 ON-Command at V1> and V2< YES All 6109 ON-Command at V1< and V2< NO All 6110A Direct ON-Command NO All 6111A Supervision time of V1>;V2> or V1<;V2< 0.10 sec All 6112 Maximum duration of Synchronization 2.00 sec All
1.2 Group SYNC Function group 1; Group Power Sys. Data
Group SYNC Function group 1; Group Power Sys. Data
No. Settings Value Group
6121 Balancing factor V1/V2 1.00 All
6122A Angle adjustment (transformer) 0° All 6123 Connection of V2 A-B All 6125 VT nominal voltage V2, primary 132.00 kV All
1.3 Group SYNC Function group 1; Group Synchron check
Group SYNC Function group 1; Group Synchron check
No. Settings Value Group
6150 Maximum voltage difference V2>V1 10.0 V All
6151 Maximum voltage difference V2<V1 10.0 V All 6152 Maximum frequency difference f2>f1 0.10 Hz All 6153 Maximum frequency difference f2<f1 0.10 Hz All 6154 Maximum angle difference alpha2>alpha1 20 ° All 6155 Maximum angle difference alpha2<alpha1 20 ° All