1 Automatic Voltage Regulator Tapcon 230
+W
Transformer Data
HV side LV side
V I MVA V I MVA
Rating
132KV 109.4 25 33KV 437.4 25
150/1 100/5
CT Ratio for 51NS
%impedance 10.5%
20/25MVA 132/33KV Power Transformer protection settings calculation
Calculations:
Parameter Calculations
Note: 1. The above graph can be taken as the reference for Operating characteristics
Recommended
Parameter Range Step Unit Description
Settings
Rated voltage of trans-former winding 1 (HV
RatedVoltageW1 0.05 - 2000.00 0.05 132 kV
winding) in Kv
ConnectTypeW1 WYE (Y) - WYE (Y) - Connection type of wind-ing 1: Y-wye or D-delta
DELTA (D)
ConnectTypeW2 WYE (Y) - DELTA(D) - Connection type of wind-ing 1: Y-wye or D-delta
DELTA (D)
0 [0 deg] 1 [30
deg lag] 2 [60
deg lag] 3 [90
deg lag] 4
[120
deg lag] 5
[150
deg lag] 6
[180 11 [30 lead
ClockNumberW2 deg] 7 [150 Phase displacement between W2 & W1=HV
- deg] -
winding,
deg
hour notation
lead] 8 [120
deg
lead] 9 [90
deg
lead] 10 [60
deg
lead] 11 [30
deg
lead]
Enable zer. seq. current subtraction for W1 side,
ZSCurrSubtrW1 Off ON ON
On / Off
Enable zer. seq. current subtraction for W2 side,
ZSCurrSubtrW2 Off ON ON
On / Off
Two CT inputs (T-con-fig.) for winding 1, YES /
TconfigForW1 No Yes No
NO
1 150 A CT primary rating in A, T-branch 1, on transf. W1
CT1RatingW1 1 - 99999
side
1 150 A CT primary rating in A, T-branch 2, on transf. W1
CT2RatingW1 1 - 99999
side
20/25MVA 132/33KV Power Transformer protection settings calculation
Recommended
Parameter Range Step Unit Description
Settings
Operation Off / ON On Operation Off / On
Instantaneous stage (50) has been set for 3.58 times of the CT rated current. This has been set for 80% of the
given 3-ph max fault current, that is 673A.
Calculations :
As per the given data, Rated current 109A, CT ratio is 150/1A
The relationship between current and time on the standard curves complies with the standard IEC 60255-
3 and can generally be expressed as:
Calculations:
As per the given inputs, Max 3-ph fault current = 0.673 kA
Assumed the trip time is 0.2S at Max fault current of 0.673 kA
IEC normal inverse has been set for 67. For IEC normal inverse α = 0.02 and β = 0.14
Operating time t = 0.2sec
α = 0.02
β = 0.14
I> = 1.1 times the rated current(Assumed 110% of rated current)
= 120A that is 120/150 = 0.8, 80% of CT rated current.
I = 0.673 kA
Calculated TMS (k) by using above formula, k= 0.0501, hence 0.05 has been set.
Selection of operation
Operation mode 1) - 8) - Normal Inverse mode and inversetime
characteristic
Start current 0.05...40.00 x In 0.8 Start current
Operate time at DT
Operate time 0.05...300.00 S 1.21(NA)
mode
Time multiplier k in
Time multiplier 0.05...1.00 - 0.05
IDMT mode
Basic angle b 0-90o S 45 degrees
Forward Selection of direction
Oper direction - Forward
Reverse for operation
Enabled/ Selection EF
Earth fault protection - Disabled1)
Disabled protection
Note: 1) Not in use 2) Definite time 3) Extremely inverse 4) Very inverse 5) Normal inverse
6) Long time inverse 7) RI-type inverse 8) RD-type inverse
1) Separate block is used for earth fault protection, hence is disabled
20/25MVA 132/33KV Power Transformer protection settings calculation
Control settings
Recommended
Parameter Range Unit Description
Settings
Selection of analog
Measuring mode1) Mode:1 to 4 - Mode:2
signals
Calculations:
As per given inputs, Max 1-ph fault current = 1008A
20/25MVA 132/33KV Power Transformer protection settings calculation
t = 0.2sec
β= 0.14
I> = 0.2 times the rated current(Assumed 20% of rated current)
= 21.8A that is 21.8/150 = 0.15, 15% of CT rated current.
I = 1008 A (As per given data)
Calculated TMS (k) by using above formula, k= 0.113≈ 0.1
Selection of operation
Operation mode 1) - 6) - Normal Inverse mode and inverse time
characteristic
Selection of operation
Operation criteria 1)-5) Basic angle & Uo
criteria
Forward Selection of direction
Oper direction - Forward
Reverse for operation
Basic angle b 0- -90o S -60 degrees
Start current 1.0...500.00 % In 15 Start current
Start voltage 2.0...100.00 %Un 20 Start voltage
Time multiplier 0.05...1.00 - 0.1 Time multiplier k in
20/25MVA 132/33KV Power Transformer protection settings calculation
IDMT mode
Control settings
Recommended
Parameter Range Unit Description
Settings
The residual O/C (51N) setting is 10% of IBase with 0.2 TMS. This has to be coordinated with downstream settings. The
reset is set instantaneous. . Instantaneous E/F (50N) has been set to 100% with min time delay of 20ms.
Recommended
Parameter Range Unit Description
Settings
Start value
1-100 %In 10 Start current of stage, Io>
Io>
Def. Time
IEC ext. inv.
IEC Very inv.
IEC Norm. inv.
4.IEC Normal Selection of operation
IEC long time inv.
Operate mode Io>IDMT mode mode and inverse time
RI type inv. inverse characteristic
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
RD type inv.
20/25MVA 132/33KV Power Transformer protection settings calculation
Time multiplier k in
Time multiplier, ko(IDMT IEC) 0.05-1.00 S 0.2
IDMT mode
Start value, Io>> 5-800 %In 100 Start current of stage, Io>>
The residual O/C (51N) setting is 10% of IBase with 0.2 TMS. This has to be coordinated with downstream settings. The
reset is set instantaneous. . Instantaneous E/F (50N) has been set to 100% with min time delay of 20ms.
Recommended
Parameter Range Unit Description
Settings
Start value
1-100 %In 10 Start current of stage, Io>
Io>
Def. Time
IEC ext. inv.
IEC Very inv.
IEC Norm. inv.
4.IEC Normal Selection of operation
IEC long time inv.
Operate mode Io>IDMT mode mode and inverse time
RI type inv. inverse characteristic
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
RD type inv.
Time multiplier k in
Time multiplier, ko(IDMT IEC) 0.05-1.00 s 0.2
IDMT mode
Start value, Io>> 5-800 %In 100 Start current of stage, Io>>
OTHER DEVICES
Voltage regulator
Since the voltage input is taken from secondary side VRS of 33KV bus bar VT, with a ratio of 33KV/0.1KV. Then
desired voltage level is set as DVL-1=100V.
From the transformer rating plate, one tap of OLTC is to regulate 1.01% of the rated voltage. But the regulating device
can only be accurate to one digit after decimal point. Manufacturers prefer a smaller value than a bigger one, because
higher values may cause lower regulating sensitivity. Then the voltage regulator bandwidth is set at
BANDWIDTH=1.0%.
A default 10 seconds remaining as the setting of DELAY 1 AND DELAY 2.
Find the regulating range between highest and smaller regulated voltage from the rating plate,
U>=1+10x1.01%=110.1%. The over voltage threshold can be set as 111%.
The under voltage setting can be set as the reciprocal of the above ratio,
U<=1-10x1.01%=89.9, set it as 89%.
Other settings remain as default values.
Tapcon 230 Automatic Voltage Regulation device settings of 132/33KV Transformer at Shakiso S/S
Item Value
NORMSET ON
DES. VELTAGE LEVEL 100V
DVL1
BANDWIDTH 1.0%
DELAY T1 10s
T1 LINEAR INTEGRAL LINEAR
DELAY T2 10S
OVERVOLTAGE U> 111%
UNERVOLTAGE U< 89%
NOM. TRANSF. VOLTAGE 33KV