− Frequency, Hz 50 50
− Rated Temperature, °C -5 up to 40 -5 up to 40
− Impedance voltage at Rated MVA ONAF H/L H/T L/T H/L H/T L/T
− Test voltage
a) Induced voltage test
1) 220 kV winding at 200 Hz, kV 395 395
2) 132 kV winding at 200 Hz, kV 325 275
3) 11 kV winding short-duration induced test, kV 28 28
b) Separate source voltages test
− Sound pressure level with all fans working , dBA @ 1meters < 88 <88 pressure level @
1 meters(as per NEMA
TR1)
− On-load tap-changer
a) Manufacturer MR-Germany /ABB-
Sweden
b) Type On Load Tap On Load Tap Changing –
Changing - Vacuum Vacuum
c) Current rating, A 800A
d) Voltage class, kV 132 KV
e) System of design, kV 145 KV
f) Life time of contact 250,000 operations
g) Total number of voltage steps 21 21
h) Total range of voltage variation, % +16/-4x1.25% +16/-4x1.25%
i) Voltage variation per step, V 1587
j) Supply voltage of drive motor (A.C. or D.C., V) 415 VAC/110 VDC 415 VAC/110 VDC
k) Permissible number of duty cycles per hour Suppliers Data
l) Control circuit voltage, V, DC 110 110
− Bushings
a) 220 kV bushing
1) Manufacturer CGL, India
2) Type condenser Condenser
3) Rated current, A 1250 1250
4) Rated voltage, kV 220 245