Professional Documents
Culture Documents
04 1 General
05 2 Standards for reference
06 3 Basic switch configurations
07 4 Electrical performance data
08 5 Features
09 6 Accessories
11 7 Electrical and remote control
11 7.1 ELectrical control
12 7.2 Remote control and automatic sectionalizer
12 7.2.1 Functionality of REC 615
13 7.2.2 Functionality of REC 523
15 7.2.3 Automatic sectionalizer
16 8 Main construction and mounting
16 8.1 Main construction
16 8.2 Mounting modes
16 8.2.1 Below the crossarm
18 8.2.2 Above the crossarm
19 8.2.3 Mounted on pole directly
20 9 Dimension drawings (unit: mm)
20 9.1 NXB load break switch
20 9.2 NXBD load break switch
21 9.3 NXA load break switch
21 9.4 Crossarm NPTRN1T6/J40164
22 9.5 Fixing clamp NXAM 1/NXAM 2
22 9.6 Spacer plate NXBZ 59
22 9.7 Fixing clamp NXAM 4/NXZM 5
23 10 Ordering type code
23 10.1 Type code of Sectos NXB and NXBD
24 10.2 Type code of Sectos NXA
25 10.3 CT, VT and sensor
25 10.3.1 CT and VT
25 10.3.2 Sensor
Product family name "Sectos" is used, when the clause is NXB is designed up to 24 kV rated voltages. The unique
applicable to all NXA_, NXB_, NXBD_ types.The more specific feature of this type is integrated earthing switch option.
type markings are given, when the clause is applicable to
limited types only. NXBD is a 3-way load break switch using NXB components.
Two independent load break switch in one enclosure with
Sectos is an SF6-insulated, outdoor pole mounted load break the third tapped way can be used for easy and reliable line
switch family for overhead lines and specifically designed branching in overhead, cable, or mixed networks.
for use in modern remote controlled distribution automation
systems. The Sectos offers reliable maintenance free NXA is available for rated voltages 24 kV and 36 kV to IEC
operation even in the most demanding climatic conditions standards, and for rated maximum voltage 27 kV and 38 kV to
including salt laden atmospheres, corrosive industrial pollution, ANSI standards
snow and ice. It has excellent load breaking and fault making
capacity and satisfies the isolation requirements specified
for load break switch. The earthed metal tank prevents all
possible leakage currents across an open switch. Sectos can
be manually operated or motor operated for local and remote
electric control, and can be upgraded easily.
Two-position load break switch are available for all NXA_ and
NXB_ types.
1 Two-position switch I 2 Three-position switch I 3 Two-position 3-way switch types NXBD_A_ I 4 Three-position 3-way switch types NXBD_C_
1 2
3 4
3 3
6 Basic switch configurations I Sectos pole mounted SF6 load break switch
4 Electrical performance data
Current ratings
Rated normal current A 630 630 630
Mainly active load breaking current A 630 630 630/400
Number of breaking operations CO n 400 400 50/100
Line-charging breaking current A 50 50 40
Cable-charging breaking current A 50 50 40
Earth fault breaking current A 50 50 175
Cable charging breaking current
under earth fault conditions A 28 28 80
No-load transformer breaking current A 20
Short-circuit ratings
Short-time withstand current, I k kA/s 20 kA/4 s 20 kA/4 s 12.5 kA/3 s
Peak withstand current kA 50 50 31.5
Short-circuit making current kA 50 50 31.5
Number of making operations
- main switch 50 kA (CL E3) n 5 5
- main switch 31.5 kA (CL E3), n 10 10 5
- earthing switch 50 kA (CL E2) n 3 3
- earthing switch 31.5 kA (CL E3) n 5 5
Sectos pole mounted SF6 load break switch I Electrical performance data 7
5 Features
The high quality 3 mm stainless steel are used for tank, which The NXB and NXBD type are available as 2-position (ON-OFF)
is designed for its maximum robustness and minimum welding or 3-position (ON-OFF-EARTH) switch. When supplied as a
line to minimize corrosion, and specifically to guarantee the 3-positions switch the unit has facility to earth the line on one
safety of the operation personnel even with the internal arc side of the switch. The earth position of the 3-positions switch
faults at the maximum fault capacity of the tank the Sectos is manually operated only.
can withstands an internal fault without venting hot gases.
The combined and integrated sensors are optional for NXB
The independent spring operation mechanism adopt ABB and NXBD type, which ensure system safety (no effects
patent spiral spring, provides a guaranteed load break fault of short-circuited or interrupted signal circuits; no risk for
make capability by ensuring the opening and closing speed of ferroresonance), compact design (voltage and current can
the switch. be measured in one combi sensor ) and wide dynamic range
(current from rated continuous current to short-time withstand
Standard SF6 gas density units with temperature compensated current 20 kA, voltage rating is applicable from 7.2 to 24 kV
are provided by Sectos (density switch is standard for networks).
electrical operated type; density gauge is standard for manual
operated type), which ensure no misguide to wrong operating The switch can be manually controlled or it can be provided
or lock-out by reliable and stable gas pressure measuring. with an integrated motor drive device for both remote and/or
local electrical control. The motor drive device can easily be
The Sectos is provided with light reflecting position indicator retrofitted on site to manually operated units.
which are directly connected to the switch operating shaft
providing clear and unambiguous switch position indication. The control cabinet is fitted with an automatism option (equip
Indicator made of light reflecting material, which is easily with advanced FTU type REC 523) which makes the Sectos
visible from ground level even at night in driving rain. an automatic sectionalizer function. It can be current-counter
scheme with current detection or can be voltage-time scheme
Advanced and Integrated helium leakage detecting and filling with voltage detection.
equipment are be adopted, which ensuring SF6 leakage of
each switch is less than 0.15% strictly per year.
1 Single spring mechanism I 2 Low pressure lock out device I 3 Manual locking device I 4 Manual locking device I 5 Density gauge|6 Density switch
1 2 3
4 5 6
Manual operated type 2* * These accessories are for wood pole mounted,accessories for concrete pole can be
offered if required. And this operated type can not be selected when inner earthing
As left picture, Sectos can be selected manual operated by switch is needec.
device which normally located near to the ground level, and
the mechanical movement is transferred to the switch by an
operating rod, which moves up and down.
1 Motor drive device UEMC 40K8-24 VDC I 2 Electrical control cabinet UEMC- I 3 UEMC-A2 I 4 UEMC-A3
1 2 3 4
Sectos pole mounted SF 6 load break switch I Electrical and remote control 11
7 Electrical and remote control
12 Electrical and remote control I Sectos pole mounted SF6 load break switch
7.2.2 Functionality of REC 523 Local automation functions
Control - Current based sectionalizer
■
Two to four objects - Voltage based sectionalizer
■
External heater
■
Integrated temperature-compensated charger Communication media
■
Serial cable
Measurement and data logging ■
Radio modem
■
Phase currents and phase-to-phase voltages ■
Other RS 232 adaptable devices
■
Residual current and voltage ■
Modem
■
Active and reactive energy ■
DLC
■
Frequency ■
Conventional radio
■
Temperature ■
Cellular phones
■
Demand values of current and power
■
Power factor Communication protocols
■
Battery voltage ■
SPA
■
Harmonics ■
Modbus(RTU and ASCII)
■
Disturbance and event recording ■
LON
■
DNP 3.0
Condition monitoring ■
IEC 870-5-10
■
Control circuit supervision
■
SF6 pressure of primary equipment
■
Battery deep discharge protection
■
Internal self-supervision of the unit
■
circuit breaker/disconnector condition monitoring
■
Battery condition monitoring
■
Operation counter for primary equipment
Sectos pole mounted SF6 load break switch I Electrical and remote control 13
7 Electrical and remote control
DTU131 - □ □ □ □
A≥18 Ah batteries
B≥24 Ah long life batteries
C=no batteries
14 Electrical and remote control I Sectos pole mounted SF6 load break switch
7.2.3 Automatic sectionalizer Voltage based automatic sectionalizer
Sectos load break switch can as automatic sectionalizer with ■
Automatic sectionalizers are selfcontained, automatically
DTU-131xxxx control cabinet easily. Which also includes controlled circuit-opening devices
all remote-function at the same time, don't need add any ■
Lose voltage to open
hardware components. If switch detect lost voltage two side of switch, switch
open immediately.
As the 80-90% of medium voltage overhead line faults are ■
Add voltage to close (A-Time)
self clearing or transient by nature and last for a few cycles Either side add voltage and last A-Time switch close
or seconds. In coordination with the main circuit-breaker or ■
A-Time open lockout
reclosers, The Sectos load break switch is able to distinguish Either side add voltage and lost it within A-Time, switch
between transitory and permanent faults occurring in the hold open and lockout.
section it is installed in. Only in case of a permanent fault, it ■
B-Time
will isolate the line automatically. Switch close and start B-Time, If no lost voltage till B-Time
time out, switch hold close.
From principle and application, the Sectos can as two kinds ■
B-Time open lockout
of sectionalizer, one is current based sectionalizer(need current Switch close and start B-Time, If lost voltage within B-Time,
detection), the other is voltage based sectionalizer(need switch open and lockout ( load side fault )
voltage detection). ■
Apply to loop and emanative circuits
Sectos pole mounted SF6 load break switch I Electrical and remote control 15
8 Main construction and mounting
1 Tank I 2 Mechanism box I 3 Control cable I 4 CT measure cable1 I 5 CT junction box I 6 Electric control cabinet I 7 Control unit
16 Main construction and mounting I Sectos pole mounted SF6 load break switch
1 Single pole (suitable for NXA and NXB) I 2 Double poles (suitable for NXA and NXB)
1
1 Crossarm
2 Fixing clamp
3 Spacer plate
4 Surge arrester
2 3 1
1 Crossarm
2 Fixing clamp
3 Spacer plate
4 Surge arrester
Sectos pole mounted SF6 load break switch I Main construction and mounting 17
8 Main construction and mounting
2 1 3
1 Crossarm
2 Fixing clamp
3 Spacer plate
4 Surge arrester
The spacer plates can be without, if a 2-position switch Description of crossarm and surge arrester can be found
(without inner earthing switch). above in point 8.2.1
The spacer plate is standard for NXBD type. see dimension Fixing clamp NXAM 4 or 5
drawings at the point 9.6. NXB is easy to install above the crossarm using 2 pieces fixing
clamps---NXAM 1 or NXAM 2.
Surge arresters MWK
To protect the Sectos against atmospheric overvoltages, it is NXA is easy to install above the crossarm using 2 pieces fixing
often necessary to install surge arresters on one or both sides clamps---NXAM 4 or NXAM 5.
of the switch. normally. It can be purchased locally according
to features of local power network. See dimension drawings at the point 9.7.
Also silicon rubber insulated surge arresters of ABB, type NXAM1 is use for 80...100x80...100 crossarm. NXAM2 is use
MWK can be used, complete information please go to website for 120...160x120...160 crossarm.
http://ABB.com.cn, ABB Hochspannungstechnik AG, Switzerl
and or ABB High Voltage Switchgear Co., LTD., BeiJing, China.
18 Main construction and mounting I Sectos pole mounted SF6 load break switch
NXBD mounted at double poles normally
3 1
1 Crossarm
2 Fixing clamp
3 Surge arrester
Diameter
180-250 mm
Sectos pole mounted SF6 load break switch I Main construction and mounting 19
9 Dimension drawings (unit: mm)
20 Dimension drawings (unit: mm) I Sectos pole mounted SF6 load break switch
9.3 NXA load break switch
Sectos pole mounted SF 6 load break switch I Dimension drawings (unit: mm) 21
9 Dimension drawings (unit: mm)
NXAM 1 NXAM 2
NXBZ 59
NXAM 4 NXAM 5
22 Dimension drawings (unit: mm) I Sectos pole mounted SF6 load break switch
10 Ordering type code
The Pole Mounted load break switch type NXB 24 C 630 A M 3 / 24VDC / 8 M / UEMC-A2
Type of insulators
Standard silicone rubber insulators with 620 mm creepage distance C
Silicone rubber insulators with 960 mm creepage distance D
Silicone rubber insulators with combi sensors and voltage sensors CS
Silicone rubber insulators with 6 CVD sensors and 3-phase CTs CK
Series 400 for underground cable bushings according to IEC E
Sectos pole mounted SF6 load break switch I Ordering type code 23
10 Ordering type code
The pole mounted load break switch type NXA 36 C 630 A M 3 / 24VDC / 8 M / UEMC-A2
Type of insulators
Silicone rubber insulators C
Series 400 for underground cable bushings according to IEC E
10.3.2 Sensors
Combi, voltage and CVD Sensor are a new solution for
measuring currents and voltages for protection and monitoring
of Medium Voltage power systems. In the combi sensors, both
the current and voltage sensors are integrated in the same
compact cast resin part.
Sectos pole mounted SF6 load break switch I Ordering type code 25
10 Ordering type code
www.abb.com.cn