ACCORD TRANSFORMER & SWITCHGEAR PVT. LTD.

Head Office : 725/726 Eros Corporate Park Sec - 2 IMT Manesar Gurugram 122050 (HR) India.
Factory Address : Plot No. H1-39 (F1 & F2), RIICO Industrial Area, Kushkhera- Bhiwadi dist- Alwar (Rajsthan) - 301707
ANNEXURE: 1 Gauranteed
technical Particulars ( Stack Core ) as per IEC-60076 OUTDOOR TYPE, OIL IMMERSED, ONAN COOLED, DISTRIBUTION
TRANSFORMER WITH CORRUGATED TANK

DESCRIPTION DETAILS BY THE BIDDER


1.Quantity Offered N/A
2. Continuous Maximum Rating (KVA) 5000
3.Appplicable Satndard IEC:60076
4.Manufacturer Accord Transformer & Switchgear Pvt. Ltd.
5.Place of manufacturer Plot No. H1-39 (F1 & F2), RIICO Industrial Area, Kushkhera-
Bhiwadi dist- Alwar (Rajsthan) - 301707
6.Rated Voltage (HV) (KV) 33
7.Rated Voltage (LV) (KV) 11
8.Rated KVA Capacity 5000
1.Highest Tap 5000
2.Normal Tap 5000
3.Lowest Tap 5000
9.Number of phases (Nos.) 3
10. Number of windings (Nos.) 3
11. Rated Frequency (HZ) 50
12.Connection of HV side (Star / Delta) Delta
13.Connection of LV side (Star / Delta) Star
14.Vector Group Dyn 11
15.Type of Colling ONAN
16.Polarity Positive
17.Tapping On HV Winding for HV variation
18. No Load Voltage Ratio 5.196
19.Highest System Voltage (HV/LV) 36 KV / 12 KV
20.Type of Tap Changer OLTC
21.Tap Step
1. 34650/11000 34650/11000 Volts
2. 33825/11000 33825/11000 Volts
3. 33000/11000 (Normal Tap Position) 33000/11000 Volts
4. 32175/11000 32175/11000 Volts
5. 31350/11000 31350/11000 Volts
6. 30525/11000 30525/11000 Volts
7. 29700/11000 29700/11000 Volts
8. 28875/11000 28875/11000 Volts
9. 28050/11000 28050/11000 Volts
22.Gauranted Impedance voltage at Rated Current ---
1. Highest Tap ----
2. Normal Tap 7.15 % with IEC tol.
3. Lowest Tap ----
23. Efficiency at 75 C at Unity Power Factor
1. At Full Load 99.21%
2. At 3/4 Full Load 99.30%
3. At 1/2 Full Load 99.55%
24. Core Material Used and Grade MoH or Better Grade
1 Flux Density 1.676 Tesla
2. Over fluxing without saturation (Curve to be furnished by the manufacturer in As per Standard
support of his claim
25. maximum Temperature rise of
1.Winding by resistance method 65 Deg. C
2. Oil by thermometer 60 Deg. C
26. Magnetizing Current (% of Rated Current)
1. At 90% Voltage
2. At 100% Voltage Less than 1% of FLC
3. AT 112.5% Voltage
4. Tolerance As per Standard
ACCORD TRANSFORMER & SWITCHGEAR PVT. LTD.
Head Office : 725/726 Eros Corporate Park Sec - 2 IMT Manesar Gurugram 122050 (HR) India.
Factory Address : Plot No. H1-39 (F1 & F2), RIICO Industrial Area, Kushkhera- Bhiwadi dist- Alwar (Rajsthan) - 301707
ANNEXURE: 1 Gauranteed
technical Particulars ( Stack Core ) as per IEC-60076 OUTDOOR TYPE, OIL IMMERSED, ONAN COOLED, DISTRIBUTION
TRANSFORMER WITH CORRUGATED TANK

27.Losses
1.No load Loss 4 KW
2.Load Loss at normal tap and 75°C 45 KW
3. Tolerance on losses at normal ratio AS per Standard IEC
28. Noise level (db) 60 to 70 dB
29.Impulse test levelof HV & LV windings at 1.2/50 micro second wave 170 kVp / 75 kVp
30. Insulation Material Used Class A
1.Between Core & LV Press board
2. Spacers Press board
3. Inter layer Paper
4.Between HV & LV windings Press board
5. Between Phases Press board
6.End Insulation Uniform Press board+Permawood
31. Resistance of windings at 20 deg. C (with 5% tolerance)
1.HV windings (ohms) 2.9055
2. LV winding (ohms) 0.0804
32. Current density used for
1.HV windings 3.992 A/Sqmm (Approx.)
2. LV windings 3.813 A/Sqmm (Approx)
33. Clearances
1. Core & LV 12 mm
2. LV & HV 18 mm
3. HV Phase to Phase 19 mm
4. End Insulation Clearance to Earth (refer to HV) 50 mm
5. Any point of winding to tank 50 mm
34. Efficiency at 75 deg C.
1. at Unity Power Factor
34.1.1. 125% load 98.90%
34.1.2. 100% load 99.21%
34.1.3. 75% load 99.30%
34.1.4. 50% load 99.55%
34.1.5. 25% load 99.80%
2. at 0.8 lagging power factor
34.2.1. 125% load 99.00%
34.2.2. 100% load 98.88%
34.2.3. 75% load 99.20%
34.2.4. 50% load 99.40%
34.2.5. 25% load 99.50%
35 .Regulation at
1. Unity P.F. 1.108
2. 0.8 P.F. At 75 deg.C. 0.0516
36. Transformer Impulse withstand level at 1.2/50 microseconds
36.1 HV 170 kVp
36.2 LV 75 kVp
37. Over potential Test Double Voltage & Double Frequency for 1 minute 66kV/22kV at 100 Hz frequency
38.Weight Content of
1. Core & Windinds 5800 Kg.
2. Tank & Fittings 2890 kg
3. Weight of Oil 2285 kg.
ACCORD TRANSFORMER & SWITCHGEAR PVT. LTD.
Head Office : 725/726 Eros Corporate Park Sec - 2 IMT Manesar Gurugram 122050 (HR) India.
Factory Address : Plot No. H1-39 (F1 & F2), RIICO Industrial Area, Kushkhera- Bhiwadi dist- Alwar (Rajsthan) - 301707
ANNEXURE: 1 Gauranteed
technical Particulars ( Stack Core ) as per IEC-60076 OUTDOOR TYPE, OIL IMMERSED, ONAN COOLED, DISTRIBUTION
TRANSFORMER WITH CORRUGATED TANK

4. Volume of Oil 2785 Ltrs


5. Total Weight 10975 kg
6. Heaviest Packege Weight during transport 9000 kg
39. Oil Data
1. Qty for first filling (Min) 2785 Ltrs
2. Grade of Oil Used IS:335
40. Tank
1. Shape Rectangular
2. Thickness of tank sheets
40.2.1. Top & Bottom 8 mm
40.2.2. Side walls 5 mm
40.2.3. Radiators 1200 X 520 X 16 Fins 6 Nos.
3. Internal Dimension of tank
40.3.1. Length 2165 mm
40.3.2. Breadth 835 mm
40.3.3. height 1545 mm
41 Over all dimensions L X W X H 4150 mm x 2900 mm x 2750