You are on page 1of 8

IRAN TRANSFO-8130227

Client
Execution date 30/11/2023 Reason of the job

Tested by Location
Approved by Asset Transformer
Report ID 1 Asset type Two-winding
Report
issue date 30/11/2023 Asset serial number 8130227

Work order Manufacturer IRAN TRANSFO

Others
Category Power
Status Repair
Tank type Free
breathing
Insulation Mineral oil
medium
Fluid 10000 kg
insulation
weight
Total 430000 kg
weight

Transformer nameplate data


Serial 8130227 Apparatus ID
number
Manufacturer IRAN TRANFO Feeder IRAN TRANFO
Manufacturin
2003 No. phases 3
g year
Manufacturer
TLSN7349 Vector group YNd11
type

Voltage ratings
Insul. level
Winding Voltage L-L Voltage L-N
L-L

Prim 66 kV 38 kV 72.5kV
Sec 6.3 kV 7.2kV

Power ratings

Rated power Cooling class Temp. rise wind.

20 MVA ONAN/ONAF
Current ratings at rated power
Winding

Prim Sec Rated power

75 A 1833 A 20 MVA

Short-circuit impedance Prim - Sec

OLTC DETC
uk[%] Base power Base voltage Load losses Pk
position position

9.62% 20 MVA 66 kV W 10

Tap Voltage
1 75900 kV
2 74800 kV

3 73700 kV

4 72600 kV

5 71500 kV

6 70400 kV
7 69300 kV

8 68200 kV

9 67100 kV

10 66000 kV
11 64900 kV

12 63800 kV
13 62700 kV
14 61600 kV

15 60500 kV

16 59400 kV

17 58300 kV
18 57200 kV

19 56100 kV
Test set information
Model Serial number Calibration date

CPC100 TD149A 09/04/2022 17:08


CP SB1
CPTD1

Global test conditions


Weather Clear Humidity 90%
Unit location Outside Ambient temperature 20 °C

DC Winding Resistance Prim


Test current 3.0 A
Winding Remot switching
18 °C Mode
temperature of taps and
phases
Temperature
corr. 1.207 Tap time
factor
(K)
Type of
OLTC Impulse time
tap
changer

R(A/N) R(B/N) R(C/N)


tap mΩ mΩ mΩ
1 363.4 436.9 366.1
2 354.9 426.9 357.5
3 346.9 423.1 349.1
4 338.4 415.6 341.1
5 330.3 403 333.5
6 322.4 394.6 325.2
7 314.4 387.2 317.1
8 306 380.1 308.8
9 300 372.4 300.7
10 292.3 361.1 289.4
11 317.7 376.3 307.3
12 308.8 352.2 299.3
13 300.7 346.5 291.8
14 293 342.5 283.4
15 285.3 332.7 275.1
16 276.8 324 267.2
17 268.3 317.3 259.4
18 259.2 310.6 251
19 251.8 302.3 242.4
‫يتبين من الجدول والمنحني أن مبدل الجهد بحاجة إلى تنظيف وصيانة تحدد بعد الكشف على المنظم‬

DC Winding Resistance Set


Test current 3.0 A Use CPC100 Yes

Winding temperature 20 °C Mode manual

Temperature corr.
1.216
factor (K)

Type of tap changer None

A (a2 - b2) B (b2 – c2) C (c2 – a2)

R meas R meas R meas Assessment

4.796mΩ 4.812mΩ 4.8mΩ Pass


Turns Ratio Prim- sec
Phase A Phase B Phase C

Tap Nom. ratio ratio ratio ratio

1 12.047 12.056 12.068 12.065

2 11.873 11.843 11.854 11.855

3 11.698 11.689 11.697 11.688

4 11.523 11.542 11.543 11.534

5 11.349 11.352 11.343 11.355

6 11.174 11.154 11.165 11.165

7 11 11.01 11.02 11.02

8 10.825 10.845 10.864 10.853

9 10.65 10.642 10.634 10.644

10 10.476 10.486 10.467 10.465

11 10.301 10.312 10.321 10.315

12 10.126 10.134 10.135 10.134

13 9.952 9.944 9.953 9.943

14 9.777 9.787 9.765 9.766

15 9.603 9.614 9.632 9.621

16 9.428 9.442 9.441 9.433

17 9.253 9.265 9.247 9.245

18 9.079 9.081 9.072 9.073

19 8.904 8.914 8.923 8.914

PASS
Insulation Resistance Test ( IR ) :

5000 v dc R 15 R 60 R60 / R15

LV - E 2.78 GΩ 3.27 GΩ 1.176

HV - E 5.17 GΩ 5.9 GΩ 1.141

LV - HV 4.3 GΩ 5.04 GΩ 1.172

‫ يفضل إجراء عملية تكرير زيت لتحسين قيم العازلية لورق العزل‬1.2≥ ‫ هو‬R60 /R15 ‫الحد األدنى المقبول لـ‬

Break Down Oil test

67.5 kV /2.5mm PASS

Short circut test


‫قصر طرف المنخفض وتغذية طرف الجهد العالي وقياس الجهد والتيار‬

V(u/v)=369 vac , V(u/w)=370vac , V(v/w)=369vac

Tap U1 V1 W1 U2/v2 V2/w2

1 6.6A 6.5A 6.6A 81.2A 83.1A

2 7A 6.9A 7A 83.9A 86A

10 9.9A 9.8A 9.8A 104A 106

PASS
‫‪NO LOAD TEST‬‬

‫‪Tap‬‬ ‫‪U1 mA‬‬ ‫‪V1 mA‬‬ ‫‪W1 mA‬‬


‫‪1‬‬ ‫‪6.9‬‬ ‫‪4.2‬‬ ‫‪9.2‬‬
‫‪2‬‬ ‫‪7.2‬‬ ‫‪4.4‬‬ ‫‪9.3‬‬
‫‪3‬‬ ‫‪7.3‬‬ ‫‪4.5‬‬ ‫‪9.6‬‬
‫‪4‬‬ ‫‪7.5‬‬ ‫‪4.6‬‬ ‫‪9.9‬‬
‫‪5‬‬ ‫‪7.7‬‬ ‫‪4.8‬‬ ‫‪10.2‬‬
‫‪6‬‬ ‫‪8‬‬ ‫‪4.9‬‬ ‫‪10.5‬‬
‫‪7‬‬ ‫‪8.2‬‬ ‫‪5.1‬‬ ‫‪10.6‬‬
‫‪8‬‬ ‫‪8.4‬‬ ‫‪5.3‬‬ ‫‪11.1‬‬
‫‪9‬‬ ‫‪8.7‬‬ ‫‪5.4‬‬ ‫‪11.4‬‬
‫‪10‬‬ ‫‪8.9‬‬ ‫‪5.6‬‬ ‫‪11.8‬‬
‫‪11‬‬ ‫‪9.2‬‬ ‫‪5.7‬‬ ‫‪12.2‬‬
‫‪12‬‬ ‫‪9.5‬‬ ‫‪5.9‬‬ ‫‪12.6‬‬
‫‪13‬‬ ‫‪9.8‬‬ ‫‪6.1‬‬ ‫‪12.9‬‬
‫‪14‬‬ ‫‪10.1‬‬ ‫‪6.3‬‬ ‫‪13.4‬‬
‫‪15‬‬ ‫‪10.5‬‬ ‫‪6.5‬‬ ‫‪14‬‬
‫‪16‬‬ ‫‪10.8‬‬ ‫‪6.8‬‬ ‫‪14.5‬‬
‫‪17‬‬ ‫‪11.2‬‬ ‫‪7.1‬‬ ‫‪14.9‬‬
‫‪18‬‬ ‫‪11.6‬‬ ‫‪7.2‬‬ ‫‪15.5‬‬
‫‪19‬‬ ‫‪12‬‬ ‫‪7.5‬‬ ‫‪16.1‬‬

‫‪Tap‬‬ ‫‪U1 %‬‬ ‫‪V1 %‬‬ ‫‪W1 %‬‬

‫‪1‬‬ ‫‪0,4552‬‬ ‫‪0,277‬‬ ‫‪0,606‬‬

‫‪10‬‬ ‫‪0,5099‬‬ ‫‪0,3208‬‬ ‫‪0,676‬‬

‫‪19‬‬ ‫‪0,584‬‬ ‫‪0,365‬‬ ‫‪0,783‬‬

‫نسبة تيار الالحمل إلى التيار االسمي يجب أن تكون أقل من ‪≥0.5 %‬‬

‫نالحظ من الجدول السابق ارتفاع الضياعات قليال في الفاز ‪W‬‬


TAN DELTA test
Mode UST

‫جهد الحقن‬ ‫التيار‬ ‫التردد‬ ‫السعة‬ TAN DELTA

Vac mA HZ nF %
4000 9.983 50 7.543 0.2254
6000 14.26 50 7.54 0.2263
8000 18.975 50 7.54 0.2262
PASS

‫المحولة المساعدة‬
Insulation Resistance Test ( IR ) :

2500 v dc R 15 R 60 R60 / R15


LV - E 652 MΩ 852 MΩ 1.25
HV - E 998 MΩ 1260 MΩ 1.26
LV - HV 1070 MΩ 1490 MΩ 1.39

DC Winding Resistance

HV: LV:

R(U/N) =795.7 mΏ R(U/N) = 4.613 mΩ

R(V/N) =848.7 mΏ R(V/N) = 4.512mΩ

R(W/N) =795.2 mΏ R(W/N) =4.618 mΩ