Professional Documents
Culture Documents
b) LV side 433V
10.
Line Current HV 33.07A
11.
Line Current LV 810.5A
12.
Voltage fluctuation ±10%
13.
Frequency 50 Hz ±3%
14.
Tap Changing Arrangement OLTC ±10% @1.25% , 16 steps ,17 postions
15.
Type of cooling ONAN
16. Class of Insulation Class A
17. Winding Material Electrolytic Copper
18.
Core material
used and Grade
a) Thickness 0.23mm
Page 1 of 7
Sl. No. Description Unit As furnished by Bidder
Page 2 of 7
Sl. No. Description Unit As furnished by Bidder
32. Full wave lightning impulse withstand voltage (HV) kV peak 75 kVp
a) At full load
% 99.31
35. b) At 3/4 full load
% 99.41
c) At 1/2 full load
a) At full load
% 99.14
36. b) At 3/4 full load
% 99.41
c) At 1/2 full load
Page 3 of 7
Sl. No. Description Unit As furnished by Bidder
a) Core Kg 780
b) Winding
Kg 610
c) Bare weight of windings without paper insulation
40. Kg 560
and leads
Kg 1102
d)Tanks, fittings and accessories.
e) Oil Kg 918
Reference standards
Details of HV Bushings (Compliance to IS 8603)
Page 4 of 7
Sl. No. Description Unit As furnished by Bidder
a) Voltage class,
kV 1.1
b) Current rating, d)Make
e) Type A 1000A
43.
f) Creepage distance, total mm 30mm
g) Creepage distance, protected.
mm 30mm
h) Year of manufacture.
d) Make A Epothane
a) HV MVA 500MVA
b) LV MVA
Page 5 of 7
Sl. No. Description Unit As furnished by Bidder
Core
a) Material & Grade
CRGO ZDKH
b) thickness
c)Type of core 0.23mm
d)Operating flux density
Core type
e) Maximum flux density
48. f) Over fluxing capability for ±12.5% voltage & ±5% 1.685 tesla @ rated voltage
frequency variation
1.9 Tesla
g) Specific No load loss for the grade of core
chosen at the specified flux density. 1.99 tesla
h) Net weight of CRGO lamination in core. (Kg
0.8w/kg
minimum).
Please submit copy of graph in support of this) 780 Kgs
49.
Rail gauge (along both axis)
Oil Data:
2721x2210x1932 mm
a) Overall Length x Breadth x Height
mm
1165x520x1075
b) Tank length x Breadth x Height
mm
51. c) Thickness of plated for 5
mm 5 (As per CBIP Manual
i) Side plate (min)
Ref (17.3.1(a1) (Pressure Withstanding
mm
ii) Top & Bottom plate
Values attached with testing)
Page 6 of 7
Sl. No. Description Unit As furnished by Bidder
2) Type of paint
PU light grey 631 IS:5
3) Whether galvanized radiator offered as
alternative.
Conservator
b) Volume (m3)
118
c) Inside dia. Of conservator tank pipe (mm) m3
d) Whether conservator outlet pipe is projected 25mm
approx. 20mm inside the conservator tank. mm
53. e) Whether arrangement made so that oil does not Yes
fall on active parts. Yes/No
f) Whether die cast metal oil level gauge indicator Yes
Page 7 of 7