You are on page 1of 2

Xiamen MingHan Electric Co., Ltd.

THREE PHASE VOLTAGE REGULATOR-TVR


Product Engineering Department

Technical Specification

Description Unit Offer Data


I SVR
1 Country of Origin CHINA
2 Brand Minghan
3 Model type SVR-3000kVA
4 Installation indoor
5 Max. ambient temperature ℃ 50
6 Altitude m ≤2000m
7 Transmission Line capacity kVA 3000kVA
8 standards GB/T12325-2008
9 Rated Frequency Hz 50HZ
10 Vector group Ya0
11 Rated current A 157
12 Nominal Input voltage kV 11
kV -20% of nominal minium(8.8)
kV +20% of nominal maximum(13.2)
13 Nominal output voltage kV 11
14 Refrigerant Mineral oil (PCB FREE)
15 Winding material Copper
16 Noise level dB <60
17 Basic insulation level(BIL) kV 75
18 Power frequency withstand voltage kV 35
19 Tap changer positions 25
20 Voltage range of per step(Accuracy) % 2.5
21 Dimensions mm
Color Grey
Length mm 1630
Width mm 1250
Height mm 1500
Oil weight kg 610
Total weight Kg 2640
22 On load tap changer
Tap changing time per step S 10
Mechanical life 500,000 times
Electrical Life 50,00 times
23 Controller
Brand gouuda
Type Microprocessor
Controller power source V AC/DC 110~450V
power consumption W 25
Analog input 2
digital input 10
digital output 2
24 Bucholz relay Yes/No YES
25 Pressure relief Yes/No YES
26 Oil level indicator Yes/No YES
27 Oil drain valve Yes/No YES
28 HV bushing Yes/No YES
29 PT for metering Yes/No YES
30 CT for metering Yes/No YES
II BY Pass panel
1 Maker MINGHAN
2 Country of Origin China
3 Standard IEC
4 Type Indoor
5 Rated Voltage 11kV
6 Rated Current 400A
7 Nominal frecuency 50HZ
8 Rated Power Frequency Withstand Voltage 28kV
9 Rated Lightning Impulse Withstand Voltage
42kV

10 Rated short-circuit current 31.5kA


11 V.C. Indicating Light Included
12 V.C. Selector Switch Included
13 12 kV three Phase Disconnect Switch 2no Single throw switch+Double throw switch
Manufacturer MINGHAN
Standard GB
Model GN19-10
Circuit Breaker Rated Current 400A
Dynamic stable current 31.5kA
Thermal stability current(4s) 12.5kA
Number of auxiliary contacts available NO 2
Number of auxiliary contacts available NC 2