Abootaleb -C12 Q03-7VK61114AB914YQ0-V4.6.

xls 1/1
‫ﺑﺴﻤﻪ ﺗﻌﺎﻟﯽ‬
‫ﺷﺮﮐﺖ ﺑﺮق ﻣﻨﻄﻘﻪ اي ﺧﺮاﺳﺎن‬
‫ دﻓﺘﺮ ﻓﻨﯽ اﻧﺘﻘﺎل‬- ‫ﻣﻌﺎوﻧﺖ ﺑﻬﺮه ﺑﺮداري‬

7VK61114AB914YQ0-V4.6 Primary secondary


Substation : Aboutaleb CT(A) 2000 1
Bay : Line VT(kV) 400 0.11
CB: C12-Q03

Device Configuration 79 Auto Reclosing


103 Setting Group Change Option Disabled 3401 79 Auto-Reclose Function OFF
106 Voltage transformer connection 1phase 25 Synchronism and Voltage Check
107 Current transformer connection YES 3501 25 Synchronism and Voltage Check OFF
110 Trip mode 1-/3pole Circuit breaker failure protection
126 Backup overcurrent Disabled 3901 Breaker Failure Protection * ON
133 79 Auto-Reclose Function 1 AR-cycle 3902 Pick-up threshold I> 0.12 A
134 Auto-Reclose Control mode With Trip & Action time 3903 1pole retrip for local trip NO
135 25 Synchronism and Voltage Check Enabled 3904 T1, Delay after 1pole start (local trip) 0.08 Sec
139 Breaker Failure Protection Enabled 3905 T1, Delay after 3pole start (local trip) 0.08 Sec
140 Trip Circuit Supervision Disabled 3906 T2, Delay of 2nd stage (busbar trip 0.18 Sec
Power System Data 1 3907 T3, Delay for start with defective bkr oo
201 CT starpoint Toward Line 3908 Trip output selec. with defective bkr NO
203 Rated Primary Voltage 400 3909 Check Breaker contacts * YES
204 Rated Secondary Voltage 110 3913 T2 Start Criteria Parallel w T1
205 CT Rated Primary Current 2000 3921 End fault protection ON
206 CT Rated Secondary Current 1 3922 Trip delay of end fault protection 0.05 Sec
210 V4 Voltage transformer is Vsy2 3931 Pole Discrepancy supervision ON
214A Angle adjusment Vsy2-Vsy1 0 3932 Trip delay with pole discrepancy 0.2 Sec
215 Matching Ratio Vsy1/Vsy2 1 Oscillographic Fault Records
220 I4 Current Transformer is Neutral net. 402A Waveform Capture Save w. Pickup
221 Matching Ration I4 / Iph For CT's 1.00 403A Scope of Waveform Data Fault event
207 System Starpoint is Solid Earthed 410 Max. length of a Waveform Capture Record 2 sec
230 Rated Frequency 50 411 Captured Waveform Prior to Trigger 0.1 sec
235 Phase Sequence ABC 412 Captured Waveform after Event 0.1 sec
239 Closing time of 52 0.10 415 Capture Time via Binary Input 1 sec
240A Minimum TRIP Command Duration 0.10
241A Maximum Close Command Duration 0.10
242 Dead Time for CB test-autoreclosure 0.10
Power System Data 2
1103 Measurment:full scale Voltage(100%) 400
1104 Measurment:full scale current(100%) 2000
1130A Pole Open Current Threshold 0.05 A
1131A Pole Open Voltage Threshold 10 V
1135 RESET of Trip Command Pickup Reset

1136 open pole detector w/ measurement

1150A Seal-in Time after MANUAL closures 0.30 sec


.‫* از ﮐﻨﺘﺎﮐﺖ ﻫﺎي ﺑﺮﯾﮑﺮ ﺑﻪ رﻟﻪ واﯾﺮﯾﻨﮓ ﺷﺪه ﺑﺎﺷﺪ‬
1151 Manual CLOSE COMMAND generation NO
1152 MANUAL Closure Impulse after CONTROL none
Measurement Supervision Setup
2901 Measurement Supervision ON
2904A Current Threshold for Bal. moni. 0.1
2905A Bal. factor for Current moni 0.5 ‫ﮔﺮوه ﮐﺎرﺷﻨﺎﺳﺎن ﮐﻨﺘﺮل و ﺣﻔﺎﻇﺖ‬
‫ﺗﺎرﯾﺦ‬
2906A Sum. Current moni threshold 0.1 ‫ﺳﺠﺎدي‬ ‫ﺗﺎﯾﯿﺪ‬ ‫ﺑﻬﺪاﻧﯽ‬ ‫ﻣﺤﺎﺳﺒﻪ‬
2907A Sum. Current moni factor 0.1 1402/11/03
2909A T Current balance monitor 5sec
2941 Limit setting PhiA 200 ° Rev.No
2942 Limit setting PhiB 340 °
2943 Minimum value I1> 0.05 A 2
2944 Minimum value U1> 45 V