Relay Setting

Relay:
Location: NG/EAST/QAISUMAH 380KV/380/A806 Nariyah North Line-2 (NEW)/
NG/EAS Siemens/79+25AR/7VK610 V4.6 - V4.7//BF1706512356
Device:
T/QAISU
MAH
380KV/3
80/A806
Setting:
Nariyah
NorthSetting: 7/9/2023
Date Setting Type: Revised In Service Since: Valid Until:
Line-2
Active: Setting Status: Ready for operation In Service by:
(NEW)/
Comment: It is issued for CSD. Auto Re-close function shall be configured for single phase faults only. After
commissioning the relay Auto-Reclose and Sync Check functions shall be Disabled.

Parameter Set
Name: Parameter Set
Parameters
Device Configuration/Device Configuration
Name Description Value [Unit] / Primary [Unit] Address
0103 Setting Group Change Disabled 0103
Option
0106 Voltage transformer 1-phase 0106
connection
0107 Current transformer NO 0107
connection
0110 Trip mode 1-/3pole 0110
0133 Auto-Reclose Function 1 AR-cycle 0133
0134 Auto-Reclose control mode with Trip and Action time 0134
0135 Synchronism and Voltage Enabled 0135
Check
0140 Trip Circuit Supervision Disabled 0140
Device/Device
Name Description Value [Unit] / Primary [Unit] Address
0610 Fault Display on LED / LCD Display Targets on every Pickup 0610
0625A Minimum hold time of 0 min 0625A
lachted LEDs
0640 Start image Default Display image 1 0640
Oscillographic Fault Records/Time Delays
Name Description Value [Unit] / Primary [Unit] Address
0402A Waveform Capture Save with Pickup 0402A
0403A Scope of Waveform Data Fault event 0403A
0410 Max. length of a Waveform 1s 0410
Capture Record
0411 Captured Waveform Prior to 0.2 s 0411
Trigger
0412 Captured Waveform after 0.1 s 0412
Event
0415 Capture Time via Binary 0.5 s 0415
Input
Power System Data 1/Breaker
Name Description Value [Unit] / Primary [Unit] Address
0239 Closing (operating) time of 0.06 s 0239
CB
Comment: Check and Confirm at Site
0240A Minimum TRIP Command 0.1 s 0240A
Duration
0241A Maximum Close Command 0.1 s 0241A
Duration
Comment: Check and Confirm at Site
0242 Dead Time for CB test- 0.1 s 0242
autoreclosure
Comment: Check and Confirm at Site
Power System Data 1/Power System
Name Description Value [Unit] / Primary [Unit] Address
0207 System Starpoint is Solid earthed 0207

IPS v1.00 Printed: 7/9/2023 9:44:27 AM Page 1 of 4


Relay Setting
Relay:
Location: NG/EAST/QAISUMAH 380KV/380/A806 Nariyah North Line-2 (NEW)/
NG/EAS Siemens/79+25AR/7VK610 V4.6 - V4.7//BF1706512356
Device:
T/QAISU
MAH
380KV/3
80/A806
Power
NariyahSystem Data 1/Power System
Name
North Description Value [Unit] / Primary [Unit] Address
0230
Line-2 Rated Frequency 60 Hz 0230
(NEW)/System Data 1/Transformers
Power
Name Description Value [Unit] / Primary [Unit] Address
0203 Rated Primary Voltage 380 kV 0203
0204 Rated Secondary Voltage 110 V 0204
(Ph-Ph)
0206 CT Rated Secondary 1A 0206
Current
0210 U4 voltage transformer is Usy2 transformer 0210
Comment: Check and Confirm at Site
0214A Angle adjustment Usy2- 0° 0214A
Usy1
Comment: Check and Confirm at Site
0215 Matching ratio Usy1 / Usy2 1 0215
Comment: Check and Confirm at Site
Setting Group (Active)/Automatic Reclosure/1st AR-cyle
Name Description Value [Unit] / Primary [Unit] Address
3450 Start of AR allowed in this YES 3450
cycle
3451 Action time 0.2 s 3451
3456 Dead time after 1pole trip 10 s 3456
3457 Dead time after 3pole trip 10 s 3457
3458 Dead time after evolving 10 s 3458
fault
3459 CB ready interrogation YES 3459
before reclosing
3460 Request for synchro-check YES 3460
after 3pole AR
Setting Group (Active)/Automatic Reclosure/3pTRIP/DLC/RDT/ADT
Name Description Value [Unit] / Primary [Unit] Address
3430 3pole TRIP by AR YES 3430
Setting Group (Active)/Automatic Reclosure/General
Name Description Value [Unit] / Primary [Unit] Address
3401 Auto-Reclose function Off 3401
Comment: Auto Re-Close shall configure for 1-phase faults only. After commissioning Auto Re-Close Function shall be kept OFF.
3402 CB ready interrogation at YES 3402
1st trip
3403 Reclaim time after 300 s 3403
successful AR cycle
3404 AR blocking duration after 1s 3404
manual close
3406 Evolving fault recognition with Pickup 3406
3407 Evolving fault (during the blocks AR 3407
dead time)
3408 AR start-signal monitoring 0.5 s 3408
time
3409 Circuit Breaker (CB) 0.5 s 3409
Supervision Time
3410 Send delay for remote close 10 s 3410
command
3411A Maximum dead time 12 s 3411A
extension
Setting Group (Active)/Power System Data 2/Line Status
Name Description Value [Unit] / Primary [Unit] Address

IPS v1.00 Printed: 7/9/2023 9:44:27 AM Page 2 of 4


Relay Setting
Relay:
Location: NG/EAST/QAISUMAH 380KV/380/A806 Nariyah North Line-2 (NEW)/
NG/EAS Siemens/79+25AR/7VK610 V4.6 - V4.7//BF1706512356
Device:
T/QAISU
MAH
380KV/3
80/A806
Setting
Nariyah Group (Active)/Power System Data 2/Line Status
Name
North Description Value [Unit] / Primary [Unit] Address
1131A
Line-2 Pole Open Voltage 26 V 1131A
(NEW)/ Threshold
1135 RESET of Trip Command with Pole Open Current Threshold only 1135
1136 open pole detector OFF 1136
1150A Seal-in Time after MANUAL 0.3 s 1150A
closures
Comment: Check At Site
1151 Manual CLOSE COMMAND with Synchronism-check 1151
generation
Setting Group (Active)/Power System Data 2/Power System
Name Description Value [Unit] / Primary [Unit] Address
1103 Measurement: Full Scale 380 kV 1103
Voltage (100%)
Setting Group (Active)/Synchronism and Voltage Check/General
Name Description Value [Unit] / Primary [Unit] Address
3501 Synchronism and Voltage ON 3501
Check function
3502 Voltage threshold dead line / 27 V 3502
bus
3503 Voltage threshold live line / 53 V 3503
bus
3504 Maximum permissible 73 V 3504
voltage
3507 Maximum duration of 1s 3507
synchronism-check
3508 Synchronous condition 0s 3508
stability timer
Setting Group (Active)/Synchronism and Voltage Check/Man.Close+CNTRL
Name Description Value [Unit] / Primary [Unit] Address
3530 Operating mode with Man.Cl with consideration of CB closing time 3530
3531 Maximum voltage difference 6.6 V 3531
3532 Maximum frequency 0.1 Hz 3532
difference
3533 Maximum angle difference 20 ° 3533
3535A Manual Close at Usy2>, YES 3535A
Usy1>, and Synchr
Comment: As Per Field Requirements
3536 Manual Close at Usy1< and YES 3536
Usy2>
Comment: As Per Field Requirements
3537 Manual Close at Usy1> and YES 3537
Usy2<
Comment: As Per Field Requirements
3538 Manual Close at Usy1< and NO 3538
Usy2<
Comment: As Per Field Requirements
3539 Override of any check NO 3539
before Man.Cl
Comment: As Per Field Requirements
Setting Group (Active)/Synchronism and Voltage Check/with AR
Name Description Value [Unit] / Primary [Unit] Address
3510 Operating mode with AR without consideration of CB closing time 3510
3511 Maximum voltage difference 6.6 V 3511
3512 Maximum frequency 0.1 Hz 3512
difference

IPS v1.00 Printed: 7/9/2023 9:44:27 AM Page 3 of 4


Relay Setting
Relay:
Location: NG/EAST/QAISUMAH 380KV/380/A806 Nariyah North Line-2 (NEW)/
NG/EAS Siemens/79+25AR/7VK610 V4.6 - V4.7//BF1706512356
Device:
T/QAISU
MAH
380KV/3
80/A806
Setting
Nariyah Group (Active)/Synchronism and Voltage Check/with AR
Name
North Description Value [Unit] / Primary [Unit] Address
3513
Line-2 Maximum angle difference 20 ° 3513
(NEW)/
3515A AR at Usy2>, Usy1>, and YES 3515A
Synchr.
Comment: As Per Field Requirements
3516 AR at Usy1< and Usy2> YES 3516
Comment: As Per Field Requirements
3517 AR at Usy1> and Usy2< YES 3517
Comment: As Per Field Requirements
3518 AR at Usy1< and Usy2< NO 3518
Comment: As Per Field Requirements
3519 Override of any check NO 3519
before AR
Comment: As Per Field Requirements

IPS v1.00 Printed: 7/9/2023 9:44:27 AM Page 4 of 4