Professional Documents
Culture Documents
STTPMSU(Motor Startup
MPTTR (49M ;3Ith>)
supervision
Inst. name STTPMSU Inst. Name Thermal (49)
Start Detection A 0.87 Operation ON
Motor Start up A 2.90 Over load factor 1.05
Motor Start up Time 21 sec Alarm thermal value 90.0 %
Lock rotor time 1 Reset Thermal Value 40
Negative Sequence Factor 7.0
Weighting Factor p 50
Time Constant Normal 320
Time Constant start 320
Time Constant stop 500
Env. Temp. mode Flc only
Initial Thermal Value 74.0 %
MEASUREMENT :
Current Measurement
Current Primary Current Display On Relay
PHASE Injected R phase (A) Y Phase (A) B Phase (A) Io(A)
R-N 1.0 50 - - -
Y-N 1.0 - 50 - -
B-N 1.0 - - 50 -
R-Y-B 1.0 50 50 50 -
CBCT 1.0 Measured Ground Current Ig(A) 50
PT MEASUREMENT:
R 63.51 6.594
Y 63.51 6.591
B 63.51 6.591
6.0 MNSPTOC1 (46; I2>): NEG. PHASE SEQ. char INV CURVE A
PHASE SET CURRENT IN AMP Angle OPE. TIME IN SECS
R 0.12*10 time 0ْ
10.45
Y 0.12*10 time 120ْ
B 0.12*10 time 240ْ
PHASE SET CURRENT IN AMP OPER. CURRENT IN AMP SET TIME IN msec OPE. TIME IN msec
R 1.80 1.74 100 120
Y 1.80 1.74 100 120
B 1.80 1.74 100 120