Technical Data Sheet Indoor Surge Arrester: 7.

5kV 10KA Class 2


General:
Model MCPA2-7.5-IND
Arrester housing Polymeric
Application Indoor
Applicable standard IEC 60099-4/ IS 3070 Part 3
Nominal discharge current 10kA
Line discharge class 2
High current impulse 4/10µs 100kA
Energy capability 4.5 kJ/kV at Ur according to IEC 60099-4

Surge arrester characteristics:


Rated voltage Ur: 7.5 kV
Continuous operating voltage Uc: 6.0 kV
TOV capability 8.55 kV for 1s
7.72 kV for 10 s
7.27 kV for 100 s
Max. app. cant. load 250 Nm
Impulse voltage 1.2/50µs 75 kV
Power frequency voltage-dry 30 kV
Creepage distance 130 mm
Height 147 mm

Maximum residual voltages


Lightning current impulse Steep lightning current Switching current impulse
8/20µs impulse 1/20µs 30/60µs
5kA 10kA 20kA 10kA 125A 500A
17.4kV 18.5kV 20.0kV 19.7kV 14.6kV 15.5kV

Power frequency voltage versus Time

Text A: MCPA2-7.5-IND
Text B: Uc 6.0 kV
Text C: Ur 7.5 kV
Text D: Year
Text E: Batch

The information provided here is correct to best of our knowledge and reliable. User, however, should independently evaluate the suitability of the product for
desired application. Product development is a continuous process, therefore specification provided here is subject to change.

MCPA2-7.5-REV00-6/13