Site Acceptance Test Report

POWER SUPPLY TO AL
YASAT AL SOFLAH ISLAND

Client: ADDC Consultant: AES


Contractor: TASNEEM Vendor: ELMEC
Substation: 33/11kV PU SS Equipment: 33KV H02 TRANSFORMER FEEDER

TEST REPORT FOR RESTRICTED EARTH FAULT RELAY

PANEL REF. : H02 MAKE : SIEMENS

FEEDER : TRAFO FEEDER TYPE : 8DA10

SUBSTATION : YASAT PACKAGE UNIT DATE OF TEST : 26.12.2021

RELAY DATA:
RELAY MAKE SIEMENS MLFB NO 7SR1103-3MA87-2CA0/FF
RATED
DESIGNATION F87N 1A
CURRENT
SERIAL No. BF2106503449 AUX. VOLTAGE 48 V DC
CT RATIO 1250/1A PURPOSE REF RELAY

1. Measurements test

Relay Display
SLNo Phase Injected current (A) Remarks
(A)
0.5 627.5
1 IEE
1.0 1251
2. (I) DMT Element Test (current method)

Set DMT Set REF


current Time Pick up Current Operating Time 1.1X
Ph IS(A) (Sec.) (A) (mSec.)
IEE 0.16 0 0.16 36.90

(I) DMT Element Test (Voltage method) R Value Set : 905.33Ω

Set DMT Set REF


Ph current Time Operating Time
IS(A) (Sec.) Injected Voltage (v)
(m.Sec.)
IEE 0.16 0 146 35.0

Witnessed
Tested By Witnessed By Witnessed By
/Approved By
Sign
Name THAVASELVAN
Date 26-12-2021 26-12-2021 26-12-2021

Company ELMEC TASNEEM AES CONSULTANT ADDC

Page 1 of 3
Site Acceptance Test Report

POWER SUPPLY TO AL
YASAT AL SOFLAH ISLAND

Client: ADDC Consultant: AES


Contractor: TASNEEM Vendor: ELMEC
Substation: 33/11kV PU SS Equipment: 33KV H02 TRANSFORMER FEEDER
3. Testing output contacts:

Relay Terminal
Arrangement Contact Function Test Result
No.
Output B01 NC A2,A1 REF relay faulty OK
Output B02 NO A4,A5 REF Trip to K861 OK
Output B03 NO A7,A8 REF Trip to TC-2 OK
Output B04 NO A9,A10 REF Trip to TC-1 OK
Output B05 NO A11,A12 REF Trip to K861 OK
Output B06 NO B9,B11 REF Trip to DMS OK
Output B07 NO B9,B13 Spare OK
Output B08 NO B9,B15 Spare OK

4. Testing LED Indication & Operation:

Arrangement Function Test Result

LED 1 Protection Relay Healthy (Green LED) OK


LED 2 Protection Relay Pickup OK
LED 3 REF Trip OK
LED 4 Spare OK
LED 5 Spare OK
LED 6 Spare OK
LED 7 Spare OK
LED 8 Spare OK
LED 9 Spare OK
LED 10 Spare OK

Witnessed
Tested By Witnessed By Witnessed By
/Approved By
Sign
Name THAVASELVAN
Date 26-12-2021 26-12-2021 26-12-2021

Company ELMEC TASNEEM AES CONSULTANT ADDC

Page 2 of 3
Site Acceptance Test Report

POWER SUPPLY TO AL
YASAT AL SOFLAH ISLAND

Client: ADDC Consultant: AES


Contractor: TASNEEM Vendor: ELMEC
Substation: 33/11kV PU SS Equipment: 33KV H02 TRANSFORMER FEEDER

5. Testing Input Operation:

Arrangement Function Test Result

Binary Input BI1 Test block inserted OK


Binary Input BI2 Spare OK
Binary Input BI3 Spare OK
Binary Input BI4 Spare OK
Binary Input BI5 Spare OK
Binary Input BI6 Spare OK

6. Accessories Checks:

A. Trip output Contacts Check : OK


B. LED Indication Check : OK
C. Reset function Check : OK
D. Relay wiring Check : OK
E. Relay CT shorting contacts : OK
F. CB Protection trip verified : OK
G. Protection trip for Lockout relay verified : OK

REMARKS:-TEST RESULT FOUND OK

Test Equipment Details

Calibration due
Description Make Serial No Calibrated date
date
Secondary Injection
Omicron JG572S 27.02.2019 27.02.2020
Kit

Witnessed
Tested By Witnessed By Witnessed By
/Approved By
Sign
Name THAVASELVAN
Date 26-12-2021 26-12-2021 26-12-2021

Company ELMEC TASNEEM AES CONSULTANT ADDC

Page 3 of 3