RELAY SITE TEST REPORT

Project Name: Turnkey contract for design, supply, construction, installation,


testing & commissioning work for extension of existing 33kV indoor bay-
breaker and control room building at 132/33 kV cox’s bazar grid sub-station
under cox’s bazar PBS.
Relay Sl.No: 33841499/10/16
Contractor Energypac Engineering Ltd.
Substation Cox’s bazar 132kV Grid Substation
Relay Manufacturer ALSTOM

Inspection and Testing of OC/EF Protection Relay


CT Ratio : 1600/5A Frequency: 50 HZ

Relay Designation : O/C, E/F Relay


Software version: 12.E
OC/EF Protection

A - General Inspection & Testing:


S NO General inspection & testing: Checked
1 Visual inspection of unit OK
2 Installation & wiring correct to relevant drawings OK
3 Relay case connected to local earth bar OK
4 Measured value check OK
5 Relay CT shorting contacts proved OK
6 Relay Binary outputs checked OK
7 Watch dog contact checked OK
8 Injection of current from terminal block with test plug OK

B - Configuration of protection function

Protection Functions
Enabled Disabled
IEC No. Description Relay Description
50/51 Over Current protection [50/51] PHASE OC Enabled -
50N/51N Earth fault Protection [50N/51N] E/Gnd Enabled -
Negative Sequence Disabled
46 [46] NEG SEQ OC -
Overcurrent Protection
Thermal Overload Disabled
49 [49] THERM OL -
Protection
37 Under Current Protection [37] UNDER CURRENT - Disabled

E- LED function
S no Led no Function Checked Remarks
1 LED 5 Over Current Low tI>
2 LED 6 Over Current High tI>>
3 LED 7 Earth Fault Current Low tIe>
4 LED 8 Earth Fault Current High tIe>>

1. MEASURED VALUE TEST:

TESTED BY WITNESSED BY
Signature Signature
Md. Mohsin
Name Sr. Engr, (T&C), Energypac Name
Engineering Ltd.
Date 10-05-2017 Date
RELAY SITE TEST REPORT
Project Name: Turnkey contract for design, supply, construction, installation,
testing & commissioning work for extension of existing 33kV indoor bay-
breaker and control room building at 132/33 kV cox’s bazar grid sub-station
under cox’s bazar PBS.
Relay Sl.No: 33841499/10/16
Contractor Energypac Engineering Ltd.
Substation Cox’s bazar 132kV Grid Substation
Relay Manufacturer ALSTOM

Inject current in the relay as per the table below. Observe the reading on the relay display in Primary values. Inject Current
through the relay connector.

CT RATIO: 1600/5 A

Primary Current read on relay


Current injected
Phase injected display In (A)
(Amps)
IR IY IB In
R-E 1.25A 399 0 0 399
Y-E 1.25A 0 399 0 399
B-E 1.25A 0 0 398.9 399

2.1 Over current function (IDMT- Normal Inverse): 51 0.14


T= 0.02
.TMS [s]
(I/In) -1
Test Relay Operating time at current setting (Sec)
Pick Up Current 2xI
phase setting (A) Tms
Actual Calculated
I (A)
R-Y 1.4 1.56 0.2 2.015 1.002
Y-B 1.4 1.54 0.2 2.017 1.002
R-B 1.4 1.53 0.2 2.020 1.002

2.2 Over current function (DMT): 50

Test phase Injected Current (A) Time setting (Sec) Operating time (Sec)
R-Y 20.0 0 0.052
Y-B 20.0 0 0.053
R-B 20.0 0 0.056

3.1 Earth Fault function (IDMT- Normal inverse curve): 51N


0.14
T= .TMS [s]
0.02
[(I/Ie) - 1]

TESTED BY WITNESSED BY
Signature Signature
Md. Mohsin
Name Sr. Engr, (T&C), Energypac Name
Engineering Ltd.
Date 10-05-2017 Date
RELAY SITE TEST REPORT
Project Name: Turnkey contract for design, supply, construction, installation,
testing & commissioning work for extension of existing 33kV indoor bay-
breaker and control room building at 132/33 kV cox’s bazar grid sub-station
under cox’s bazar PBS.
Relay Sl.No: 33841499/10/16
Contractor Energypac Engineering Ltd.
Substation Cox’s bazar 132kV Grid Substation
Relay Manufacturer ALSTOM

Test Relay Operating time at current setting (Sec)


phase setting Pick Up Tms 2xI
I (A) Current (A) Actual Calculated
R Phase 0.5 0.55 0.15 1.56 1.002
Y Phase 0.5 0.53 0.15 1.55 1.002
B Phase 0.5 0.57 0.15 1.54 1.002

3.2 Earth Fault function (DMT):50N

Relay setting
Test phase Injected Current Time setting (Sec) Operating time (Sec)
Ie >>

R Phase 0.2 12.64A 0.090 0.154


Y Phase 0.2 12.85A 0.090 0.146
B Phase 0.2 12.90A 0.090 0.153

Instrument Used

Instrument: SVERKER 750


Manufacturar: Megger

TESTED BY WITNESSED BY
Signature Signature
Md. Mohsin
Name Sr. Engr, (T&C), Energypac Name
Engineering Ltd.
Date 10-05-2017 Date