Date Tested: 30-Jul-21

Customer : RCBMI
Customer Address : Taysan, Batangas
Test Specimen : Electrical Test
Specimen ID: TR1

TEST SPECIMEN DATA

Make: FPE (Federal Pioneer) Type of Oil: Mineral


Date Mfg. 1978 Total Weight: 54350kg
Model/Type: Sealed Type % Impedance 6.92%
Capacity: 10/13MVA Volume Oil: 13900 Imp. Gallon
High Voltage: 67000V Vector Diagram: Dyn1
Low Voltage: 4160V/2400V H1
Serial No. 62-52-60380 X2
Tap Setting: 3(total taps 5) X1 X0
Class ONAN/ONAF H3 H2 X3

LIST OF STANDARD TESTS

1. Transformer Turns Ratio Test (TTR) 7. Water Content Test


2. Insulation Power Factor Test (IPF) 8
3. Winding Resistance Test (DLRO) 9
4. Insulation Resistance (IR) and PI 10
5. Single-Phase Excitation Current Test 11
6. Dielectric Breakdown Voltage Test 12

REMARKS/ SUMMARY:

Amon Trading Compound, E. Rodriguez Jr. Ave., corner Corporal Cruz Street, Bagong Ilog, Pasig City
Telephone (632) 85327897 • Fax (632) 85327897
Email: sales@deltagrid.ph • Website: www.deltagrid.ph
We reserve all rights in this document and the information here in.
Reproduction, use or disclosure to third parties without our authority is strictly prohibited.
 

Test Conducted TRANSFORMER TURNS RATIO


Test Equipment Make/Model: TRT-63A Serial No. 19X318
Ambient Temp 36C Weather Cloudy
Test Result
PRI Tap Computed
Tap Voltage Value Phase A %Error Phase B %Error Phase C %Error

1 70350 29.290 29.301 0.04 29.302 0.04 29.302 0.04


2 68675 28.593 28.592 0.00 28.592 0.00 28.592 0.00
3 67000 27.895 27.904 0.03 27.904 0.03 27.904 0.03
4 65325 27.198 27.216 0.07 27.216 0.07 27.216 0.07
5 63650 26.500 26.528 0.11 26.508 0.03 26.507 0.03
LIMITS ERROR MUST BE ≤ + or - 0.50%
Remarks: PASSED

Test Conducted INSULATION POWER FACTOR TEST


Test Equipment Make/Model: CDF-12A Serial No. 2014-0232
Ambient Temp 36C Weather Cloudy
Test Result:
Test Connection %IPF
Current Capacitance
Test Connection Mode
Test (mA) Watts (mW) (nF) Computed
TCF
Corrected
Voltage 36°C 20°C
PS UST 10kV 15.18 1.17 4.03 0.77 0.49 0.377
PG GST-g 10kV 8.842 0.59 2.34 0.67 0.49 0.329
SG GST-g 5kV 10.02 0.67 5.32 1.32 0.49 0.646
Criteria Overall IPF A 20ºC MUST BE ≤ 1.0%
Remarks: PASSED

Test Conducted INSULATION RESISTANCE TEST WITH POLARIZATION INDEX


Test Equipment Make/Model: Phenix Technologies Serial No. 19-3804
Ambient Temp 36C Weather Cloudy
Test Connection Test Voltage 30 sec 1 min DAR PI
PS 5kV 1.16GΩ 1.20GΩ 1.04
PG 5kV 1.47GΩ 1.48GΩ 1.02
SG 2.5kV 0.45GΩ 0.49GΩ 1.10
Remarks: Values are more than acceptable limits
Criteria: MΩ ≥ (WNDG. VOLTS X 0.8)/(KVA)^1/2, P.I. > 1.1
Remarks: PASSED

Amon Trading Compound, E. Rodriguez Jr. Ave., corner Corporal Cruz Street, Bagong Ilog, Pasig City
Telephone (632) 85327897 • Fax (632) 85327897
Email: sales@deltagrid.ph • Website: www.deltagrid.ph
We reserve all rights in this document and the information here in.
Reproduction, use or disclosure to third parties without our authority is strictly prohibited.
 

Test Conducted WINDING RESISTANCE TEST


Test Equipment Make/Model: Teldar Instrument Serial No. 13310393
Oil temp 36C Weather Cloudy
Test Result:

Connection Test Current Measured Resistance


Primary Winding Test Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
Current
H1-H2 Auto 2.120Ω 2.080Ω 2.012Ω 1.860Ω 1.776Ω
H2-H3 Auto 2.111Ω 2.096Ω 1.998Ω 1.853Ω 1.840Ω
H3-H1 Auto 2.091Ω 2.091Ω 2.005Ω 1.850Ω 1.880Ω

Secondary
Test Current Measured Resistance@Tap 3
Winding
X1-X0 Auto 2.889mΩ
X2-X0 Auto 2.860mΩ
X3-X0 Auto 2.890mΩ
Criteria Compare resistance with the factory (if available) / Values should be relatively balanced

Remarks: PASSED

Test Conducted EXCITATION CURRENT TEST @ TAP 3, 10kV


Test Equipment Make/Model: CDF-12A Serial No. 2014-0232
Ambient Temp 36C Weather Cloudy

Tap Changer H1-H2 H2-H3 H3-H1


Position
Tap 3
10.66mA 25.84mA 23.93mA

Criteria 2 EQUAL 1 High/LOW

Remarks: PASSED

Amon Trading Compound, E. Rodriguez Jr. Ave., corner Corporal Cruz Street, Bagong Ilog, Pasig City
Telephone (632) 85327897 • Fax (632) 85327897
Email: sales@deltagrid.ph • Website: www.deltagrid.ph
Test Conducted DIELECTRIC BREAKDOWN VOLTAGE, D-1816 2mm
Test Equipment Make/Model: Phenix Serial Number : LD-60 15 - 98999

Test 1 Test 2 Test 3 Test 4 Test 5 Average


37.0 36.4 35.6 47.9 47.4 40.86
LIMITS 34 KV minimum by ASTM D-1816 method 0.080" gap, kV, min IEEE standard 637-2007
REMARKS PASSED

Test Conducted WATER CONTENT TEST


Test Equipment Make/Model: TOET Serial Number : 0021

Toet Temperature 27.9


Water Content 24.2ppm
LIMITS 20 ppm maximum, before oil purification, by IEEE 637-2007
REMARKS PASSED

Tested by: Checked by: Certified by:


Jeremiah Cuisia / Ryan Salumbides Robert Samonte, REE Maximo P. Casipit Jr., PEE
TS Supervisor REE VP - Operations President

Amon Trading Compound, E. Rodriguez Jr. Ave., corner Corporal Cruz Street, Bagong Ilog, Pasig City
Telephone (632) 85327897 • Fax (632) 85327897
Email: sales@deltagrid.ph • Website: www.deltagrid.ph
Amon Trading Compound, E. Rodriguez Jr. Ave., corner Corporal Cruz Street, Bagong Ilog, Pasig City
Telephone (632) 85327897 • Fax (632) 85327897
Email: sales@deltagrid.ph • Website: www.deltagrid.ph
Date Tested: 31-Jul-21
Customer : RCBMI
Customer Address : Taysan, Batangas
Test Specimen : Electrical Test
Specimen ID: TR1

TEST SPECIMEN DATA

Make: FPE (Federal Pioneer) Type of Oil: Mineral


Date Mfg. 1978 Total Weight: 54350kg
Model/Type: Sealed Type % Impedance 6.92%
Capacity: 10/13MVA Volume Oil: 13900 Imp. Gallon
High Voltage: 67000V Vector Diagram: Dyn1
Low Voltage: 4160V/2400V H1
Serial No. 62-52-60380 X2
Tap Setting: 3(total taps 5) X1 X0
Class ONAN/ONAF H3 H2 X3

LIST OF STANDARD TESTS

1. Transformer Turns Ratio Test (TTR) 6. Dielectric Breakdown Voltage Test


2. Insulation Power Factor Test (IPF) 7. Water Content Test
3. Winding Resistance Test (DLRO) 9
4. Insulation Resistance (IR) and PI 10
5. Single-Phase Excitation Current Test 11
6. C1 Overall IPF Test 12

REMARKS/ SUMMARY:
We reserve all rights in this document and the information here in.
Reproduction, use or disclosure to third parties without our authority is strictly prohibited.
 

Test Conducted TRANSFORMER TURNS RATIO


Test Equipment Make/Model: TRT-63A Serial No. 19X318
Ambient Temp 44C Weather Cloudy
Test Result
PRI Tap Computed
Tap Voltage Value Phase A %Error Phase B %Error Phase C

3 67000 27.895 27.904 0.03 27.904 0.03 27.904

LIMITS ERROR MUST BE ≤ + or - 0.50%


Remarks: PASSED

Test Conducted INSULATION POWER FACTOR TEST


Test Equipment Make/Model: CDF-12A Serial No. 2014-0232
Ambient Temp 44C Weather Sunny
Test Result:
Test Connection %IPF
Current
Test Watts (mW) Capacitance
(nF) Computed
Test Connection Mode (mA) TCF
Voltage 36°C

PS UST 10kV 15.27 2.29 4.05 1.50 0.36


PG GST-g 10kV 8.86 0.57 2.35 0.65 0.36
SG GST-g 5kV 10.20 0.65 5.41 1.29 0.36
Criteria Overall IPF A 20ºC MUST BE ≤ 1.0%
Remarks: PASSED

Test Conducted INSULATION RESISTANCE TEST WITH POLARIZATION INDEX


Test Equipment Make/Model: Phenix Technologies Serial No. 19-3804
Ambient Temp 44C Weather Sunny
Test Connection Test Voltage 30 sec 1 min 10 min PI
PS 5kV 0.411GΩ 0.422GΩ 0.469GΩ 1.11
PG 5kV 0.922GΩ 0.927GΩ 0.952GΩ 1.03
SG 2.5kV 0.599GΩ 0.756GΩ 1.35GΩ 1.79
Remarks: Values are more than acceptable limits
Criteria: MΩ ≥ (WNDG. VOLTS X 0.8)/(KVA)^1/2, P.I. > 1.1
Remarks: PASSED

We reserve all rights in this document and the information here in.
Reproduction, use or disclosure to third parties without our authority is strictly prohibited.
 

Test Conducted WINDING RESISTANCE TEST


Test Equipment Make/Model: Teldar Instrument Serial No. 13310393
Oil temp 44C Weather Sunny
Test Result:

Connection Test Current Measured Resistance


Primary Winding Test Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
Current
H1-H2 Auto 2.011Ω
H2-H3 Auto 2.009Ω
H3-H1 Auto 2.002Ω

Secondary
Winding Test Current Measured Resistance@Tap 3

X1-X0 Auto 2.890mΩ


X2-X0 Auto 2.888mΩ
X3-X0 Auto 2.886mΩ
Criteria Compare resistance with the factory (if available) / Values should be relatively balanced
Remarks: PASSED

Test Conducted C1 OVERALL IPF TEST


Test Equipment Make/Model: CDF-12A Serial No. 2014-0232
Ambient Temp 44C Weather Sunny
Test Result:
Test Connection %IPF
Current
Test Watts (mW) Capacitance
(pF)
Test Connection Mode (mA) IPF
Voltage
H1 UST 10kV 733.0 48.49 194.00 0.39
H2 UST 10kV 739.7 42.24 196.70 0.44
H3 UST 10kV 742.3 42.62 196.30 0.57
Criteria Overall IPF A 20ºC MUST BE ≤ 1.0%
Remarks: PASSED

Test Conducted EXCITATION CURRENT TEST @ TAP 3, 10kV


Test Equipment Make/Model: CDF-12A Serial No. 2014-0232
Ambient Temp 44C Weather Sunny

Tap Changer H1-H2 H2-H3 H3-H1


Position
Tap 3
7.998mA 24.25mA 23.69mA
Criteria 2 EQUAL 1 High/LOW

Remarks: PASSED

Test Conducted DIELECTRIC BREAKDOWN VOLTAGE, D-1816 2mm


Test Equipment Make/Model: Phenix Serial Number : LD-60 15 - 98999

Test 1 Test 2 Test 3 Test 4 Test 5 Average


60.0 58.7 58.3 59.3 60.0 59.26
LIMITS 40 KV minimum by ASTM D-1816 method 0.080" gap, kV, min IEEE standard 637-2007
REMARKS PASSED

Test Conducted WATER CONTENT TEST


Test Equipment Make/Model: TOET Serial Number : 0021

Toet Temperature 33.9


Water Content 19.1ppm
LIMITS 20 ppm maximum, before oil purification, by IEEE 637-2007
REMARKS PASSED

Tested by: Checked by: Certified by:


Jeremiah Cuisia / Ryan Salumbides Robert Samonte, REE Maximo P. Casipit Jr., PEE
TS Supervisor REE VP - Operations President

We reserve all rights in this document and the information here in.
Reproduction, use or disclosure to third parties without our authority is strictly prohibited.
 
Cloudy

%Error

0.03

Sunny

%IPF
Corrected
20°C
0.540
0.233
0.463

NDEX
Sunny

Sunny
Sunny

%IPF

Sunny
m
98999

37-2007

asipit Jr., PEE