TEST REPORT FOR MOTOR PROTECTION RELAY

DATE: 15.04.2021 Sheet No.1 of 5


PROJECT : RELAY RETROFITTING
END CUSTOMER: PARADEEP PHOSPHATES LIMITED

1. NAME PLATE DETAILS:

SUBSTATION : CAP

BOARD NAME :11KV 500 MVA SWITCHGEAR

FEEDER NAME : SPARE

PANEL NO : 13

RELAY MAKE : ABB

MODEL NO : REM 615

SI.NO : 1VYV91319034

CT RATIO : 100/1 A

ORDER CODE : HBMBCAAHANB1BNN1XE

2. MEASUREMENT:
Inject current in the relay as per the table below. Observe the reading on the relay display, in primary
values.

INJECTED PRIMARY CURRENT DISPLAYED ON RELAY


PHASE CURRENT (A)
100% (A) I1 I2 I3 I0
L1 1.0 A 100.0 0 0 100.0
L2 1.0 A 0 100.0 0 100.0
L3 1.0 A 0 0 100.0 100.0
L1-L2-L3 1.0 A 100.0 100.0 100.0 0

Approved/Checked By:
TESTED BY ABB WITNESSED BY ABB APPROVED BY PPL
Mr. SANJEET KUMAR
Name: Mr. R.VIGNESH Mr. SUBRATA MAHAPATRA
BISWAL
Sign:

Date: 15.04.2021 15.04.2021


TEST REPORT FOR MOTOR PROTECTION RELAY

DATE: 15.04.2021 Sheet No.2 of 5


PROJECT : RELAY RETROFITTING
END CUSTOMER: PARADEEP PHOSPHATES LIMITED

3. OVER CURRENT TIME PROTECTION: - PHIPTOC 1(50)

Setting=5.0×In, DT= 0.04 sec ,


INJECTED CURRENT CALCULATED TIME OPERATED TIME
REF (A) (sec) (sec)
IL1 5.0 0.04 0.045
IL2 5.0 0.04 0.045
IL3 5.0 0.04 0.045

4. OVER CURRENT TIME PROTECTION: - PHLPTOC 1(51)

Setting=1.5.0×In, TMS-0.7sec, Curve-IEC NI


INJECTED CURRENT CALCULATED TIME OPERATED TIME
(A) (sec) (sec)
REF
x2 x5 x10 x2 x5 x10 x2 x5 x10
IL1 3.0 7.5 15 7.02 2.996 2.079 7.048 3.010 2.086
IL2 3.0 7.5 15 7.02 2.996 2.079 7.048 3.010 2.086
IL3 3.0 7.5 15 7.02 2.996 2.079 7.048 3.010 2.086

5. EARTH FAULT PROTECTION: - EFHPTOC 1(50N)

Setting=0.25×In, DT= 0.1 sec


INJECTED CURRENT CALCULATED TIME OPERATED TIME
REF (A) (sec) (sec)
IL1-N 0.25 0.1 0.113
IL2-N 0.25 0.1 0.112
IL3-N 0.25 0.1 0.111

6. LOCKED ROTOR PROTECTION: JAMPTOC1 (51L/R)

Approved/Checked By:
TESTED BY ABB WITNESSED BY ABB APPROVED BY PPL
Mr. SANJEET KUMAR
Name: Mr. R.VIGNESH Mr. SUBRATA MAHAPATRA
BISWAL
Sign:

Date: 15.04.2021 15.04.2021


TEST REPORT FOR MOTOR PROTECTION RELAY

DATE: 15.04.2021 Sheet No.3 of 5


PROJECT : RELAY RETROFITTING
END CUSTOMER: PARADEEP PHOSPHATES LIMITED

Setting=1.5×In, DT= 6 sec


REF INJECTED CURRENT(A) SET TIME (sec) OPERATING TIME (sec)
R 1.5
Y 1.5 6.0 6.020
B 1.5

7. NEGATIVE PHASE SEQUENCE: MNSPTOC1 (46)

Setting=0.1×In, DT= 5 sec


REF INJECTED CURRENT(A) SET TIME (sec) OPERATED TIME (sec)
R 0.10‫ے‬°
Y 0.1120‫ے‬° 5.0 5.034
B 0.1120-‫ے‬°

8. PHASE REVERSAL PROTECTION: PREVPTOC1 (46R)

Setting=0.75×In, DT=0.1 sec


REF INJECTED CURRENT(A) SET TIME (sec) OPERATED TIME (sec)
R 0.750‫ے‬°
Y 0.75120‫ے‬° 0.100 0.123
B 0.75120-‫ے‬°

9. START UP SUPERVISION: STTPMSU1 (66)

Approved/Checked By:
TESTED BY ABB WITNESSED BY ABB APPROVED BY PPL
Mr. SANJEET KUMAR
Name: Mr. R.VIGNESH Mr. SUBRATA MAHAPATRA
BISWAL
Sign:

Date: 15.04.2021 15.04.2021


TEST REPORT FOR MOTOR PROTECTION RELAY

DATE: 15.04.2021 Sheet No.4 of 5


PROJECT : RELAY RETROFITTING
END CUSTOMER: PARADEEP PHOSPHATES LIMITED

Motor Startup Current=2.9×In, Startup time= 5sec


REF INJECTED CURRENT(A) SET TIME (sec) OPERATED TIME (sec)
R 2.9
Y 2.9 5.0 5.010
B 2.9

10. LOSS OF LOAD : LOFLPTUC1 (37)

Start value low =0.1×In, Start value high =0.5×In Operate time= 2sec
REF INJECTED CURRENT(A) SET TIME (sec) OPERATED TIME (sec)
R 0.11
Y 0.11 2.0 2.023
B 0.11

11. THERMAL OVER LOAD PROTECTION: MPTTR1 (49M)

Over load factor=1.05 Rated current=0.5×In


REF INJECTED CURRENT (A) OPERATED TIME (sec)
R 2.0
Y 2.0 42.89
B 2.0

Approved/Checked By:
TESTED BY ABB WITNESSED BY ABB APPROVED BY PPL
Mr. SANJEET KUMAR
Name: Mr. R.VIGNESH Mr. SUBRATA MAHAPATRA
BISWAL
Sign:

Date: 15.04.2021 15.04.2021


TEST REPORT FOR MOTOR PROTECTION RELAY

DATE: 15.04.2021 Sheet No.5 of 5


PROJECT : RELAY RETROFITTING
END CUSTOMER: PARADEEP PHOSPHATES LIMITED

12. INTERNAL FUNCTIONAL CHECKS:

LED Checked OK
Measurements Checked in Relay Display OK
Binary inputs and Outputs are Checked OK
13. USING KIT DETAILS:

Name of the Sec. Injection Kit: Omicron

Model Number : CMC 356 Serial No: JA087R

14. REMARKS:

Relay tested as per existing setting relay. OK


Master trip(86) operation OK
Relay Found Healthy. OK

Approved/Checked By:
TESTED BY ABB WITNESSED BY ABB APPROVED BY PPL
Mr. SANJEET KUMAR
Name: Mr. R.VIGNESH Mr. SUBRATA MAHAPATRA
BISWAL
Sign:

Date: 15.04.2021 15.04.2021