The test report summarizes the results of protection relay testing for feeder P-A3114-M0 at substation SS-02. The tests included metering checks with injected currents matching measured values, thermal overload protection tripping within 2 seconds as set, unbalance protection tripping within 10 seconds as set, earth fault protection tripping within 3 seconds as set, short circuit protection tripping within 0.058 seconds as set, and overcurrent protection tripping within 3 seconds as set. All protection, indications, and alarms were found to be in healthy working condition.
The test report summarizes the results of protection relay testing for feeder P-A3114-M0 at substation SS-02. The tests included metering checks with injected currents matching measured values, thermal overload protection tripping within 2 seconds as set, unbalance protection tripping within 10 seconds as set, earth fault protection tripping within 3 seconds as set, short circuit protection tripping within 0.058 seconds as set, and overcurrent protection tripping within 3 seconds as set. All protection, indications, and alarms were found to be in healthy working condition.
The test report summarizes the results of protection relay testing for feeder P-A3114-M0 at substation SS-02. The tests included metering checks with injected currents matching measured values, thermal overload protection tripping within 2 seconds as set, unbalance protection tripping within 10 seconds as set, earth fault protection tripping within 3 seconds as set, short circuit protection tripping within 0.058 seconds as set, and overcurrent protection tripping within 3 seconds as set. All protection, indications, and alarms were found to be in healthy working condition.