1) The feeder E-A3002-M2 at substation SS-02 was tested with injected currents and its protection devices were found to operate within specifications except for earth fault protection.
2) Earth fault protection was set to 0.05A but picked up at 0.170A as noted in the remarks.
3) All other protection devices like thermal overload, unbalance, short circuit, and overcurrent operation were verified and the feeder was found to be in healthy working condition.
1) The feeder E-A3002-M2 at substation SS-02 was tested with injected currents and its protection devices were found to operate within specifications except for earth fault protection.
2) Earth fault protection was set to 0.05A but picked up at 0.170A as noted in the remarks.
3) All other protection devices like thermal overload, unbalance, short circuit, and overcurrent operation were verified and the feeder was found to be in healthy working condition.
1) The feeder E-A3002-M2 at substation SS-02 was tested with injected currents and its protection devices were found to operate within specifications except for earth fault protection.
2) Earth fault protection was set to 0.05A but picked up at 0.170A as noted in the remarks.
3) All other protection devices like thermal overload, unbalance, short circuit, and overcurrent operation were verified and the feeder was found to be in healthy working condition.