Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm² [a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 90 + Separate 25 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.07847 Z1 0.00503 Z2 0.00662 Zs 0.09001 Max. Zs 0.27504 Earth Fault
Disconnection time (s) From characteristic: 0.08 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 90 + Separate 25 [f]
2.57
CPC Adiabatic check (mm 2) CPC Section = Armour 29 + Separate 25 Total = 54.0 Min. Section = 2.66
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 9.107 / 5.886 Load End: 8.138 / 4.785
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 145.00 x 10 3 Adiabatic Limit k²S² (A²s): 51.12 x 10 6
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.9 Voltage drop limit = 11.86 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.38000 Z2 0.44704 Zs 1.04176 Max. Zs 1.76939 Earth Fault
Disconnection time (s) From characteristic: 0.06 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [f]
0.22
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.23
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.309 / 0.242
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,100.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 48
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.3 Voltage drop limit = 11.95 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.45600 Z2 0.53645 Zs 1.20714 Max. Zs 1.76939 Earth Fault
Disconnection time (s) From characteristic: 0.08 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [f]
0.19
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.23
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.267 / 0.209
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,100.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting. insulated, non-mag armoured Cu Table 4E3 1 x 4 x 1c Size (mm2): 185 [f]
Neutral: 185 mm² [a] Length (m): 10
BICC data - In underground single way ducts
Rating Factors
Ground Temperature (°C) = 15.0 Ctg = 1.00 Cgg = 1.00
Circuits In Group =1 Depth of Lay (m) = 0.50 Cd = 1.00
Thermal Resistivity = 1.20 Cs = 0.996
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 84 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.01763 Z1 0.00162 Z2 0.00471 Zs 0.02081 Max. Zs 0.11413 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 84 [f]
11.10
CPC Adiabatic check (mm 2) CPC Section = Armour 49.9 Total = 49.9 Min. Section = 6.25
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 13.100 / 13.100 Load End: 12.285 / 11.437
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 800.00 x 10 3 Adiabatic Limit k²S² (A²s): 699.87 x 10 6
Comments:
Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm² [a] Length (m): 35
30 - On horizontal/vertical unperforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 131 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.02081 Z1 0.01221 Z2 0.05334 Zs 0.07847 Max. Zs 0.20253 Earth Fault
Disconnection time (s) From characteristic: 0.10 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 131 [f]
2.94
CPC Adiabatic check (mm 2) CPC Section = Armour 42.1 Total = 42.1 Min. Section = 3.83
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 12.285 / 11.437 Load End: 9.107 / 5.886
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 300.00 x 10 3 Adiabatic Limit k²S² (A²s): 100.20 x 10 6
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 5c Size (mm2): 16 [f]
Neutral: 16 mm² [a] Length (m): 20
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 72 + Integral 16 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.02887 Z2 0.02130 Zs 0.13919 Max. Zs 0.78845 Earth Fault
Disconnection time (s) From characteristic: 0.07 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 72 + Integral 16 [a]
1.66
CPC Adiabatic check (mm 2) CPC Section = Armour 15.8 + Integral 16 Total = 31.8 Min. Section = 0.96
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 4.785 Load End: 4.975 / 2.267
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 18.80 x 10 3 Adiabatic Limit k²S² (A²s): 5.23 x 10 6
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.18475 Z2 0.09791 Zs 0.37057 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.62
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 1.405 / 1.108
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.27713 Z2 0.14686 Zs 0.51172 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.45
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.978 / 0.768
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 19.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.38798 Z2 0.20560 Zs 0.68120 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a]
0.34
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.716 / 0.562
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.68120 Z1 0.01848 Z2 0.00990 Zs 0.70955 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.716 / 0.562 Load End: 0.686 / 0.538
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.70955 Z1 0.01848 Z2 0.00990 Zs 0.73791 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.31
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.686 / 0.538 Load End: 0.657 / 0.515
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 19.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.38798 Z2 0.20560 Zs 0.68120 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.34
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.716 / 0.562
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.68120 Z1 0.01848 Z2 0.00990 Zs 0.70955 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.716 / 0.562 Load End: 0.686 / 0.538
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.70955 Z1 0.01848 Z2 0.00990 Zs 0.73791 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.31
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.686 / 0.538 Load End: 0.657 / 0.515
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.20540 Zs 0.69368 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.18
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.44704 Zs 0.93523 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
0.25
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.13
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.18475 Z2 0.09791 Zs 0.37057 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.62
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 1.405 / 1.108
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.27713 Z2 0.14686 Zs 0.51172 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.45
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.978 / 0.768
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 21.6 Voltage drop limit = 11.55 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 29.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.41569 Z2 0.22029 Zs 0.72357 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.09 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.32
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.41
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.671 / 0.526
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 21.6 Voltage drop limit = 11.55 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 21.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.72357 Z1 0.01848 Z2 0.00990 Zs 0.75193 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.11 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.31
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.70
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.671 / 0.526 Load End: 0.644 / 0.505
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 2 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 21.6 Voltage drop limit = 11.55 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.75193 Z1 0.01848 Z2 0.00990 Zs 0.78029 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.12 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.30
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.72
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.644 / 0.505 Load End: 0.619 / 0.485
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 48
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 21.6 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 29.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.44341 Z2 0.23497 Zs 0.76595 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.11 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.30
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.71
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.632 / 0.495
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 21.6 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 21.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.76595 Z1 0.01848 Z2 0.00990 Zs 0.79431 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.13 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.73
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.632 / 0.495 Load End: 0.608 / 0.476
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 2 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 21.6 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.79431 Z1 0.01848 Z2 0.00990 Zs 0.82267 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.15 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.28
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.76
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 0.608 / 0.476 Load End: 0.585 / 0.459
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.20540 Zs 0.69368 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.18
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.20540 Zs 0.69368 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.18
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1.8 Voltage drop limit = 11.97 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.46188 Z2 0.24476 Zs 0.92139 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.25
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.12
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.834 / 2.271 Load End: 0.525 / 0.411
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1.8 Voltage drop limit = 11.88 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.38798 Z2 0.20560 Zs 0.80837 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.12
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.834 / 2.271 Load End: 0.604 / 0.473
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 16
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 3.3 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.15200 Z2 0.08216 Zs 0.44919 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.51
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.12
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.590 / 0.463
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 21
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 3.3 Voltage drop limit = 11.64 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.19950 Z2 0.10784 Zs 0.52229 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.44
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.12
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.496 / 0.389
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm² [a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 12 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 49 + Separate 16 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.03753 Z2 0.02763 Zs 0.15400 Max. Zs 0.57501 Earth Fault
Disconnection time (s) From characteristic: 0.06 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 49 + Separate 16 [f]
1.50
CPC Adiabatic check (mm 2) CPC Section = Armour 15.8 + Separate 16 Total = 31.8 Min. Section = 1.40
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 8.138 / 4.785 Load End: 4.398 / 1.945
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 40.00 x 10 3 Adiabatic Limit k²S² (A²s): 5.23 x 10 6
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 6 [f]
Neutral: 6 mm² [a] Length (m): 10
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 36 + Separate 6 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.15400 Z1 0.03926 Z2 0.02282 Zs 0.21562 Max. Zs 1.84027 Earth Fault
Disconnection time (s) From characteristic: 0.05 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 36 + Separate 6 [f]
1.07
CPC Adiabatic check (mm 2) CPC Section = Armour 11.6 + Separate 6 Total = 17.6 Min. Section = 0.41
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 4.398 / 1.945 Load End: 2.834 / 1.178
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 736.16 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 0.5 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.04750 Z2 0.05588 Zs 0.31863 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
0.72
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.12
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 1.011 / 0.795
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 0.5 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.04750 Z2 0.02568 Zs 0.28851 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.80
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.12
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 1.011 / 0.795
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1.6 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.04750 Z2 0.05588 Zs 0.31863 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
0.72
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.12
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 1.011 / 0.795
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 28
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 9.4 Voltage drop limit = 11.53 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 24.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.26600 Z2 0.26600 Zs 0.66979 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.34
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.467 / 0.366
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 26
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 9.4 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 24.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.24700 Z2 0.24700 Zs 0.63181 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.37
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.497 / 0.389
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0 Voltage drop limit = 11.67 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 18.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.38000 Z2 0.38000 Zs 0.89770 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.26
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.344 / 0.269
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 35
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 7.8 Voltage drop limit = 11.62 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.33250 Z2 0.33250 Zs 0.80273 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.386 / 0.302
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 50
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 7.8 Voltage drop limit = 11.79 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.47500 Z2 0.47500 Zs 1.08765 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.21
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.281 / 0.220
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 80
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 4.0 Voltage drop limit = 7.53 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 12.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.24000 Z2 1.24000 Zs 2.61752 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.09
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.115 / 0.090
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 4 [f]
Neutral: 4 mm² [a] Length (m): 20
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 42.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 4 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.12000 Z2 0.12000 Zs 0.37807 Max. Zs 7,663.60151 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 4 [f]
0.61
CPC Adiabatic check (mm 2) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.866 / 0.680
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 327.18 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 4 [f]
Neutral: 4 mm² [a] Length (m): 45
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 5.0 Voltage drop limit = 11.73 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 42.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 4 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.27000 Z2 0.27000 Zs 0.67778 Max. Zs 7,663.60151 * Earth Fault
Disconnection time (s) From characteristic: 0.04 * Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 4 [f]
0.34
CPC Adiabatic check (mm 2) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.48
*Calculated for RCD protection
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.461 / 0.361
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 327.18 x 10 3
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 84
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 2.0 Voltage drop limit = 7.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.30200 Z2 1.30200 Zs 2.74151 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.08
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.109 / 0.085
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 84
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 2.0 Voltage drop limit = 7.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.30200 Z2 1.30200 Zs 2.74151 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.08
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.109 / 0.085
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 70
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 2.5 Voltage drop limit = 12.02 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.08500 Z2 1.08500 Zs 2.30753 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.10
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.130 / 0.102
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 3.0 Voltage drop limit = 7.3 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 11.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.93000 Z2 0.93000 Zs 1.99755 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.12
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.151 / 0.118
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3
Comments:
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 2.5 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 30.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.54000 Z2 0.57000 Zs 1.24762 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.19
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.67
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.236 / 0.196
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 82.66 x 10 3
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 70
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 1.0 Voltage drop limit = 7.42 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.08500 Z2 1.08500 Zs 2.30753 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.10
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.130 / 0.102
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 62
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 4.7 Voltage drop limit = 11.93 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 17.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.58900 Z2 0.58900 Zs 1.31561 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.231 / 0.181
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 50
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.5 Voltage drop limit = 11.79 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 19.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.47500 Z2 0.47500 Zs 1.08765 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.21
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.281 / 0.220
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 35
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.5 Voltage drop limit = 11.62 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 19.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.33250 Z2 0.33250 Zs 0.80273 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.386 / 0.302
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 4.7 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 17.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.57000 Z2 0.57000 Zs 1.27762 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.238 / 0.186
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.5 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.57000 Z2 0.57000 Zs 1.27762 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.238 / 0.186
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Comments:
Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 6.5 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 19.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]
Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.57000 Z2 0.57000 Zs 1.27762 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.238 / 0.186
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Id No.: Name:
Connected From: LVAC Section 400V 3PH&N To: DB-2
Load Type: Distribution Board Design Current Ib (A): 10.0
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 1
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.00950 Z2 0.01118 Zs 0.11017 Max. Zs 1.84027 Earth Fault
Disconnection time (s) From characteristic: 0.05 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
2.10
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.41
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 5.533 / 4.785 Load End: 4.260 / 3.546
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3
Id No.: Name:
Connected From: LVAC Section 400V 3PH&N To: DB-1
Load Type: Distribution Board Design Current Ib (A): 10.0
Comments:
Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 1
31 - On horizontal/vertical perforated tray
Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed
Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.00950 Z2 0.01118 Zs 0.11017 Max. Zs 1.84027 Earth Fault
Disconnection time (s) From characteristic: 0.05 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
2.10
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.41
Phase Fault
Phase Fault Current Max./Min. (kA) Source End: 5.533 / 4.785 Load End: 4.260 / 3.546
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80
Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3