Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV 101 Name:


Connected From: Intake Board To: LVAC Section 400V 3PH&N
Load Type: Main cable to Switchboard Design Current Ib (A): 108.6

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Eaton HRC Fuse SD6 BS88 Part 2


Rating In (A): 160 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 50 [f]
Neutral: 50 mm² [a] Length (m): 10
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 108.6


Device Rating In = 160 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 165.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 197.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 108.6 / 0.86 100.5 / 0.87 106.5 / 0.85 9.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.51 / 0.22 0.40 / 0.18 0.44 / 0.19 -----
Voltage Drop - From Source (V/%) 1.86 / 0.81 1.48 / 0.64 1.63 / 0.71 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 90 + Separate 25 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.07847 Z1 0.00503 Z2 0.00662 Zs 0.09001 Max. Zs 0.27504 Earth Fault
Disconnection time (s) From characteristic: 0.08 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 90 + Separate 25 [f]
2.57
CPC Adiabatic check (mm 2) CPC Section = Armour 29 + Separate 25 Total = 54.0 Min. Section = 2.66

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 9.107 / 5.886 Load End: 8.138 / 4.785
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 145.00 x 10 3 Adiabatic Limit k²S² (A²s): 51.12 x 10 6

Project: Croham Cable Calcs 200415.p17 Page 1 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV 206 Name:


Connected From: Essential Services Panel To: PU01
Load Type: Motor, DOL, single phase and neutral Design Current Ib (A): 6.9

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 20 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 6.9 Voltage drop limit = 11.86 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.5 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 6.9 / 1.00 6.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.75 / 2.07 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.73 / 2.93 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.38000 Z2 0.44704 Zs 1.04176 Max. Zs 1.76939 Earth Fault
Disconnection time (s) From characteristic: 0.06 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [f]
0.22
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.23

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.309 / 0.242
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,100.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 2 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV 213 Name:


Connected From: Essential Services Panel To: PU02
Load Type: Motor, DOL, single phase and neutral Design Current Ib (A): 5.3

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 20 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 48
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.3 Voltage drop limit = 11.95 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.3 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 5.3 / 0.97 0.0 / 0.00 5.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 4.24 / 1.84 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 6.09 / 2.65 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.45600 Z2 0.53645 Zs 1.20714 Max. Zs 1.76939 Earth Fault
Disconnection time (s) From characteristic: 0.08 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [f]
0.19
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.23

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.267 / 0.209
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,100.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 3 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV DNO Name:


Connected From: DNO LV Cabinet To: Sb-1
Load Type: Main cable to Switchboard Design Current Ib (A): 108.6

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 315 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting. insulated, non-mag armoured Cu Table 4E3 1 x 4 x 1c Size (mm2): 185 [f]
Neutral: 185 mm² [a] Length (m): 10
BICC data - In underground single way ducts

Rating Factors
Ground Temperature (°C) = 15.0 Ctg = 1.00 Cgg = 1.00
Circuits In Group =1 Depth of Lay (m) = 0.50 Cd = 1.00
Thermal Resistivity = 1.20 Cs = 0.996
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 108.6


Device Rating In = 315 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 316.3
Actual Cable Rating It = 437.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 108.6 / 0.86 100.5 / 0.87 106.5 / 0.85 9.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.16 / 0.07 0.13 / 0.06 0.15 / 0.07 -----
Voltage Drop - From Source (V/%) 0.16 / 0.07 0.13 / 0.06 0.15 / 0.07 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 84 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.01763 Z1 0.00162 Z2 0.00471 Zs 0.02081 Max. Zs 0.11413 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 84 [f]
11.10
CPC Adiabatic check (mm 2) CPC Section = Armour 49.9 Total = 49.9 Min. Section = 6.25

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 13.100 / 13.100 Load End: 12.285 / 11.437
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 800.00 x 10 3 Adiabatic Limit k²S² (A²s): 699.87 x 10 6

Project: Croham Cable Calcs 200415.p17 Page 4 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV100 Name:


Connected From: Sb-1 To: Intake Board
Load Type: Main cable to Switchboard Design Current Ib (A): 108.6

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Eaton HRC Fuse SD6 BS88 Part 2


Rating In (A): 200 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 1 x 1 x 4c Size (mm2): 70 [f]
Neutral: 70 mm² [a] Length (m): 35
30 - On horizontal/vertical unperforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 108.6


Device Rating In = 200 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 200.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 238.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 108.6 / 0.86 100.5 / 0.87 106.5 / 0.85 9.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 1.19 / 0.52 0.94 / 0.41 1.04 / 0.45 -----
Voltage Drop - From Source (V/%) 1.35 / 0.59 1.07 / 0.47 1.19 / 0.52 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 131 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.02081 Z1 0.01221 Z2 0.05334 Zs 0.07847 Max. Zs 0.20253 Earth Fault
Disconnection time (s) From characteristic: 0.10 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 131 [f]
2.94
CPC Adiabatic check (mm 2) CPC Section = Armour 42.1 Total = 42.1 Min. Section = 3.83

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 12.285 / 11.437 Load End: 9.107 / 5.886
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 300.00 x 10 3 Adiabatic Limit k²S² (A²s): 100.20 x 10 6

Project: Croham Cable Calcs 200415.p17 Page 5 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV201 Name:


Connected From: LVAC Section 400V 3PH&N To: Dist.Board 3PH&N( DB1)
Load Type: Distribution Board Design Current Ib (A): 22.7

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Eaton HRC Fuse SD5 BS88 Part 2


Rating In (A): 63 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 5c Size (mm2): 16 [f]
Neutral: 16 mm² [a] Length (m): 20
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 22.7


Device Rating In = 63 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 63.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 99.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 20.5 / 1.00 22.7 / 1.00 18.0 / 1.00 4.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.49 / 0.21 0.62 / 0.27 0.34 / 0.15 -----
Voltage Drop - From Source (V/%) 2.34 / 1.02 2.09 / 0.91 1.97 / 0.86 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 72 + Integral 16 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.02887 Z2 0.02130 Zs 0.13919 Max. Zs 0.78845 Earth Fault
Disconnection time (s) From characteristic: 0.07 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 72 + Integral 16 [a]
1.66
CPC Adiabatic check (mm 2) CPC Section = Armour 15.8 + Integral 16 Total = 31.8 Min. Section = 0.96

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 4.785 Load End: 4.975 / 2.267
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 18.80 x 10 3 Adiabatic Limit k²S² (A²s): 5.23 x 10 6

Project: Croham Cable Calcs 200415.p17 Page 6 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV202 Name:


Connected From: LVAC Section 400V 3PH&N To: Cooling Fan No.1 FM01
Load Type: Motor, DOL, three phase Design Current Ib (A): 10.2

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.2 / 0.67 10.2 / 0.67 10.2 / 0.67 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.17 / 0.51 1.17 / 0.51 1.17 / 0.51 -----
Voltage Drop - From Source (V/%) 3.02 / 1.32 2.64 / 1.15 2.80 / 1.22 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.18475 Z2 0.09791 Zs 0.37057 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.62
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 1.405 / 1.108
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 7 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV203 Name:


Connected From: LVAC Section 400V 3PH&N To: Cooling Fan No.2 FM02
Load Type: Motor, DOL, three phase Design Current Ib (A): 10.2

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.2 / 0.67 10.2 / 0.67 10.2 / 0.67 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.75 / 0.76 1.75 / 0.76 1.75 / 0.76 -----
Voltage Drop - From Source (V/%) 3.61 / 1.57 3.23 / 1.40 3.38 / 1.47 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.27713 Z2 0.14686 Zs 0.51172 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.45
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.978 / 0.768
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 8 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV204 Name:


Connected From: LVAC Section 400V 3PH&N To: J Box-1
Load Type: Junction Box Design Current Ib (A): 14.1
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Rowd Route Pump PM01
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): 14.1

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 19.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.1 / 0.86 14.1 / 0.86 14.1 / 0.86 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 4.41 / 1.92 4.41 / 1.92 4.41 / 1.92 -----
Voltage Drop - From Source (V/%) 6.26 / 2.72 5.88 / 2.56 6.04 / 2.62 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.38798 Z2 0.20560 Zs 0.68120 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a]
0.34
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.716 / 0.562
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 9 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV204 1 Name:


Connected From: J Box-1 To: VSD
Load Type: Motor Starter Design Current Ib (A): 14.1
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Rowd Route Pump PM01
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): 14.1

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.1 / 0.86 14.1 / 0.86 14.1 / 0.86 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.19 / 0.08 0.19 / 0.08 0.19 / 0.08 -----
Voltage Drop - From Source (V/%) 6.45 / 2.81 6.07 / 2.64 6.23 / 2.71 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.68120 Z1 0.01848 Z2 0.00990 Zs 0.70955 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.716 / 0.562 Load End: 0.686 / 0.538
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 10 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV204 2 Name:


Connected From: VSD To: Cro-Rowd Route Pump PM01
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.1
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Rowd Route Pump PM01
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): 14.1

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.1 / 0.86 14.1 / 0.86 14.1 / 0.86 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.20 / 0.09 0.20 / 0.09 0.20 / 0.09 -----
Voltage Drop - From Source (V/%) 6.65 / 2.89 6.27 / 2.73 6.42 / 2.79 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.70955 Z1 0.01848 Z2 0.00990 Zs 0.73791 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.31
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.686 / 0.538 Load End: 0.657 / 0.515
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 11 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV205 Name:


Connected From: LVAC Section 400V 3PH&N To: J Box-2
Load Type: Junction Box Design Current Ib (A): 14.1
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Rowd Route Pump PM02
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): 14.1

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 19.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.1 / 0.86 14.1 / 0.86 14.1 / 0.86 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 4.41 / 1.92 4.41 / 1.92 4.41 / 1.92 -----
Voltage Drop - From Source (V/%) 6.26 / 2.72 5.88 / 2.56 6.04 / 2.62 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.38798 Z2 0.20560 Zs 0.68120 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.34
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.716 / 0.562
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 12 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV205 1 Name:


Connected From: J Box-2 To: VSD
Load Type: Motor Starter Design Current Ib (A): 14.1
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Rowd Route Pump PM02
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): 14.1

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.1 / 0.86 14.1 / 0.86 14.1 / 0.86 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.19 / 0.08 0.19 / 0.08 0.19 / 0.08 -----
Voltage Drop - From Source (V/%) 6.45 / 2.81 6.07 / 2.64 6.23 / 2.71 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.68120 Z1 0.01848 Z2 0.00990 Zs 0.70955 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.716 / 0.562 Load End: 0.686 / 0.538
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 13 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV205 2 Name:


Connected From: VSD To: Cro-Rowd Route Pump PM02
Load Type: Motor, other assisted start, three phase Design Current Ib (A): 14.1
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Rowd Route Pump PM02
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): 14.1

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 14.1 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Motor Overload Setting Ir = 14.1 [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 14.1 / 0.86 14.1 / 0.86 14.1 / 0.86 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.20 / 0.09 0.20 / 0.09 0.20 / 0.09 -----
Voltage Drop - From Source (V/%) 6.65 / 2.89 6.27 / 2.73 6.42 / 2.79 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.70955 Z1 0.01848 Z2 0.00990 Zs 0.73791 Max. Zs 1.35300 Earth Fault
Disconnection time (s) From characteristic: 0.04 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.31
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.686 / 0.538 Load End: 0.657 / 0.515
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 14 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV207 Name: LM01


Connected From: DB-2/1/L3 To: Louvre Actuator 1
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 5.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS EN60947-2 MCB Type B Th/Mag


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 5.0 / 0.80 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 2.48 / 1.08 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 4.23 / 1.84 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.20540 Zs 0.69368 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.18

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 15 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV208 Name:


Connected From: DB-2/2/L3 To: Louvre Actuator 2
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 5.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS EN60947-2 MCB Type B Th/Mag


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 5.0 / 0.80 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 2.48 / 1.08 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 4.23 / 1.84 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.44704 Zs 0.93523 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
0.25
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.13

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 16 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV209 Name:


Connected From: LVAC Section 400V 3PH&N To: Cooling Fan FM11
Load Type: Motor, DOL, three phase Design Current Ib (A): 10.2

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 20
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.2 / 0.67 10.2 / 0.67 10.2 / 0.67 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.17 / 0.51 1.17 / 0.51 1.17 / 0.51 -----
Voltage Drop - From Source (V/%) 3.02 / 1.32 2.64 / 1.15 2.80 / 1.22 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.18475 Z2 0.09791 Zs 0.37057 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.62
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 1.405 / 1.108
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 17 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV210 Name:


Connected From: LVAC Section 400V 3PH&N To: Cooling Fan FM12
Load Type: Motor, DOL, three phase Design Current Ib (A): 10.2

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 25 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 30
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 10.2 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 25 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 25.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.2 / 0.67 10.2 / 0.67 10.2 / 0.67 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 1.75 / 0.76 1.75 / 0.76 1.75 / 0.76 -----
Voltage Drop - From Source (V/%) 3.61 / 1.57 3.23 / 1.40 3.38 / 1.47 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.27713 Z2 0.14686 Zs 0.51172 Max. Zs 1.35207 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.45
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.30

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.978 / 0.768
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 1,850.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 18 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV211 Name:


Connected From: LVAC Section 400V 3PH&N To: J Box-3
Load Type: Junction Box Design Current Ib (A): 21.6
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Bed Route Pump PM11
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): 21.56

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 45
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 21.6 Voltage drop limit = 11.55 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 29.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 21.6 / 0.82 21.6 / 0.82 21.6 / 0.82 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 7.22 / 3.14 7.22 / 3.14 7.22 / 3.14 -----
Voltage Drop - From Source (V/%) 9.08 / 3.95 8.70 / 3.78 8.85 / 3.85 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.41569 Z2 0.22029 Zs 0.72357 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.09 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.32
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.41

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.671 / 0.526
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 19 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV211 1 Name:


Connected From: J Box-3 To: VSD
Load Type: Motor Starter Design Current Ib (A): 21.6
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Bed Route Pump PM11
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): 21.56

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 21.6 Voltage drop limit = 11.55 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 21.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 21.6 / 0.82 21.6 / 0.82 21.6 / 0.82 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.29 / 0.13 0.29 / 0.13 0.29 / 0.13 -----
Voltage Drop - From Source (V/%) 9.37 / 4.07 8.99 / 3.91 9.14 / 3.98 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.72357 Z1 0.01848 Z2 0.00990 Zs 0.75193 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.11 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.31
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.70

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.671 / 0.526 Load End: 0.644 / 0.505
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 20 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV211 2 Name:


Connected From: VSD To: Cro-Bed Route Pump PM11
Load Type: Motor, Star Delta started, three phasebetween LVAC Section 400V 3PH&N and Cro-Bed Design Current
Route Ib (A): PM11
Pump 21.6
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Bed Route Pump PM11
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): 21.56

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 2 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 21.6 Voltage drop limit = 11.55 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 21.6 / 0.82 21.6 / 0.82 21.6 / 0.82 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.31 / 0.13 0.31 / 0.13 0.31 / 0.13 -----
Voltage Drop - From Source (V/%) 9.68 / 4.21 9.30 / 4.04 9.45 / 4.11 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.75193 Z1 0.01848 Z2 0.00990 Zs 0.78029 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.12 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.30
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.72

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.644 / 0.505 Load End: 0.619 / 0.485
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 21 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV212 Name:


Connected From: LVAC Section 400V 3PH&N To: J Box-4
Load Type: Junction Box Design Current Ib (A): 21.6
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Bed Route Pump PM12
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): 21.56

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 48
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 10 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 21.6 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 29.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 21.6 / 0.82 21.6 / 0.82 21.6 / 0.82 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 7.71 / 3.35 7.71 / 3.35 7.71 / 3.35 -----
Voltage Drop - From Source (V/%) 9.56 / 4.16 9.18 / 3.99 9.33 / 4.06 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.44341 Z2 0.23497 Zs 0.76595 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.11 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.30
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.71

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 7.416 Load End: 0.632 / 0.495
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 22 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV212 1 Name:


Connected From: J Box-4 To: VSD
Load Type: Motor Starter Design Current Ib (A): 21.6
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Bed Route Pump PM12
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): 21.56

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 21.6 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 21.6 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 21.6 / 0.82 21.6 / 0.82 21.6 / 0.82 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.29 / 0.13 0.29 / 0.13 0.29 / 0.13 -----
Voltage Drop - From Source (V/%) 9.85 / 4.28 9.47 / 4.12 9.63 / 4.19 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.76595 Z1 0.01848 Z2 0.00990 Zs 0.79431 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.13 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.73

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.632 / 0.495 Load End: 0.608 / 0.476
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 23 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV212 2 Name:


Connected From: VSD To: Cro-Bed Route Pump PM12
Load Type: Motor, Star Delta started, three phasebetween LVAC Section 400V 3PH&N and Cro-Bed Design Current
Route Ib (A): PM12
Pump 21.6
Motor Starter Position: between LVAC Section 400V 3PH&N and Cro-Bed Route Pump PM12
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): 21.56

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 2 x 1 x 3c Size (mm2): 2.5 [f]
Length (m): 2
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =2 Cg = 0.88 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 2
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 21.6 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 32 Motor Overload Setting Ir = 21.56 [Ir _> Ib]
Min. Cable Capacity Iz = 14.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 21.6 / 0.82 21.6 / 0.82 21.6 / 0.82 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.31 / 0.13 0.31 / 0.13 0.31 / 0.13 -----
Voltage Drop - From Source (V/%) 10.16 / 4.42 9.78 / 4.25 9.93 / 4.32 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.79431 Z1 0.01848 Z2 0.00990 Zs 0.82267 Max. Zs 1.04761 Earth Fault
Disconnection time (s) From characteristic: 0.15 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 19 + Separate 2.5 [f]
0.28
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Separate 2.5 Total = 8.6 Min. Section = 0.76

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 0.608 / 0.476 Load End: 0.585 / 0.459
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 24 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV214 Name:


Connected From: DB-1/1/L1 To: Louvre Actuator LM11
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 5.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS EN60947-2 MCB Type B Th/Mag


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.0 / 0.80 0.0 / 0.00 0.0 / 0.00 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.48 / 1.08 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 4.46 / 1.94 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.20540 Zs 0.69368 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [a]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.18

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 25 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV215 Name:


Connected From: DB-1/2/L1 To: Louvre Actuator LM12
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 5.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS EN60947-2 MCB Type B Th/Mag


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.0 / 0.80 0.0 / 0.00 0.0 / 0.00 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.48 / 1.08 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 4.46 / 1.94 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.11017 Z1 0.38000 Z2 0.20540 Zs 0.69368 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.33
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.18

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 4.260 / 3.546 Load End: 0.360 / 0.282
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 475.63 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 26 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV216 Name:


Connected From: Essential Services Panel To: Anti-Freeze Pump
Load Type: Motor, DOL, three phase Design Current Ib (A): 1.8

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 50
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 1.8 Voltage drop limit = 11.97 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.8 / 0.85 1.8 / 0.85 1.8 / 0.85 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.62 / 0.27 0.62 / 0.27 0.62 / 0.27 -----
Voltage Drop - From Source (V/%) 2.78 / 1.21 2.47 / 1.08 2.60 / 1.13 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.46188 Z2 0.24476 Zs 0.92139 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.25
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.12

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.834 / 2.271 Load End: 0.525 / 0.411
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 27 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV217 Name:


Connected From: Essential Services Panel To: Anti-Freeze Pump
Load Type: Motor, DOL, three phase Design Current Ib (A): 1.8

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 2.5 [f]
Length (m): 42
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 1.8 Voltage drop limit = 11.88 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 33.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.8 / 0.85 1.8 / 0.85 1.8 / 0.85 N/A
3rd Harmonic Current (A) 0.0 0.0 0.0 N/A
Voltage Drop - This circuit (V/%) 0.52 / 0.23 0.52 / 0.23 0.52 / 0.23 -----
Voltage Drop - From Source (V/%) 2.68 / 1.17 2.37 / 1.03 2.50 / 1.09 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.38798 Z2 0.20560 Zs 0.80837 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Armour 6.1 + Integral 2.5 Total = 8.6 Min. Section = 0.12

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.834 / 2.271 Load End: 0.604 / 0.473
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 28 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV218A Name:


Connected From: Essential Services Panel To: RTU 4
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 3.3

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 16
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 3.3 Voltage drop limit = 11.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 3.3 / 1.00 0.0 / 0.00 0.0 / 0.00 3.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.82 / 0.35 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 2.98 / 1.30 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.15200 Z2 0.08216 Zs 0.44919 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.51
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.12

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.590 / 0.463
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 29 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV218B Name:


Connected From: Essential Services Panel To: RTU 5
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 3.3

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 21
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 3.3 Voltage drop limit = 11.64 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 3.3 / 1.00 0.0 / 0.00 3.3
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 1.07 / 0.47 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 2.92 / 1.27 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.19950 Z2 0.10784 Zs 0.52229 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.44
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.12

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 0.496 / 0.389
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 30 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV221 Name: UPS


Connected From: LVAC Section 400V 3PH&N To: UPS
Load Type: Main cable to Switchboard Design Current Ib (A): 7.3

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 80 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 16 [f]
Neutral: 16 mm² [a] Length (m): 26
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 12 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 7.3


Device Rating In = 80 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 80.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 99.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 7.3 / 1.00 7.3 / 1.00 7.3 / 1.00 0.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.25 / 0.11 0.25 / 0.11 0.25 / 0.11 -----
Voltage Drop - From Source (V/%) 2.10 / 0.91 1.72 / 0.75 1.88 / 0.82 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 49 + Separate 16 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.03753 Z2 0.02763 Zs 0.15400 Max. Zs 0.57501 Earth Fault
Disconnection time (s) From characteristic: 0.06 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 49 + Separate 16 [f]
1.50
CPC Adiabatic check (mm 2) CPC Section = Armour 15.8 + Separate 16 Total = 31.8 Min. Section = 1.40

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 8.138 / 4.785 Load End: 4.398 / 1.945
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 40.00 x 10 3 Adiabatic Limit k²S² (A²s): 5.23 x 10 6

Project: Croham Cable Calcs 200415.p17 Page 31 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV222 Name:


Connected From: UPS To: Essential Services Panel
Load Type: Main cable to Switchboard Design Current Ib (A): 3.6

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 4c Size (mm2): 6 [f]
Neutral: 6 mm² [a] Length (m): 10
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 3.6


Device Rating In = 32 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 32.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 56.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 2.7 / 0.98 3.6 / 0.96 3.0 / 0.98 0.9
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.06 / 0.03 0.13 / 0.06 0.10 / 0.04 -----
Voltage Drop - From Source (V/%) 2.16 / 0.94 1.85 / 0.81 1.98 / 0.86 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 36 + Separate 6 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.15400 Z1 0.03926 Z2 0.02282 Zs 0.21562 Max. Zs 1.84027 Earth Fault
Disconnection time (s) From characteristic: 0.05 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 36 + Separate 6 [f]
1.07
CPC Adiabatic check (mm 2) CPC Section = Armour 11.6 + Separate 6 Total = 17.6 Min. Section = 0.41

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 4.398 / 1.945 Load End: 2.834 / 1.178
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 736.16 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 32 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV223 Name:


Connected From: Essential Services Panel To: CS C1/H1
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 0.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 0.5 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.5 / 1.00 0.0 / 0.00 0.0 / 0.00 0.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 2.21 / 0.96 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.04750 Z2 0.05588 Zs 0.31863 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
0.72
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.12

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 1.011 / 0.795
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 33 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV224 Name:


Connected From: Essential Services Panel To: CS C2/A1
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 0.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 3c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 0.5 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.5 / 1.00 0.0 / 0.00 0.0 / 0.00 0.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.04 / 0.02 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 2.21 / 0.96 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.04750 Z2 0.02568 Zs 0.28851 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 + Integral 2.5 [f]
0.80
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 + Integral 2.5 Total = 8.0 Min. Section = 0.12

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 1.011 / 0.795
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 34 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV230 Name:


Connected From: Essential Services Panel To: CWS trace heating
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 1.6

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 5
31 - On horizontal/vertical perforated tray Arrangement: Horizontal Touching

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 11 Cg = 0.72 [BS 7671, Table 4C4] Not Subject to Simultaneous Overload
No. of trays = 1 No. of circuits per tray = 12
3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 1.6 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 1.6 / 1.00 0.0 / 0.00 0.0 / 0.00 1.6
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.14 / 0.06 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 2.30 / 1.00 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.21562 Z1 0.04750 Z2 0.05588 Zs 0.31863 Max. Zs 4.87675 Earth Fault
Disconnection time (s) From characteristic: 0.03 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
0.72
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.12

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 1.490 / 1.178 Load End: 1.011 / 0.795
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 280.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 35 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV301 Name: Upstairs heating-LVAC Rm


Connected From: Dist.Board 3PH&N( DB1)/1/L1 To: Htg & Thermostat
Load Type: Heating and power, single phase Design Current Ib (A): 9.4

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 28
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 9.4 Voltage drop limit = 11.53 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 24.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 9.4 / 1.00 0.0 / 0.00 0.0 / 0.00 9.4
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 4.95 / 2.15 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 7.29 / 3.17 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.26600 Z2 0.26600 Zs 0.66979 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.34
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.467 / 0.366
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 36 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV302 Name: Upstairs heating Plt Rm


Connected From: Dist.Board 3PH&N( DB1)/1/L2 To: Htg & Thermostat
Load Type: Heating and power, single phase Design Current Ib (A): 9.4

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 26
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 9.4 Voltage drop limit = 11.51 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 24.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 9.4 / 1.00 0.0 / 0.00 9.4
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 4.59 / 2.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 6.69 / 2.91 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.24700 Z2 0.24700 Zs 0.63181 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.01 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.37
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.497 / 0.389
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 37 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV303 Name: Upstairs heating Plt Rm


Connected From: Dist.Board 3PH&N( DB1)/1/L3 To: Htg & Thermostat
Load Type: Heating and power, single phase Design Current Ib (A): 5.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 40
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.0 Voltage drop limit = 11.67 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 18.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 5.0 / 1.00 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 3.72 / 1.62 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 5.69 / 2.47 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.38000 Z2 0.38000 Zs 0.89770 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.26
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.344 / 0.269
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 38 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV304 Name: Upstairs heating Plt Rm


Connected From: Dist.Board 3PH&N( DB1)/2/L1 To: Htg & Thermostat
Load Type: Heating and power, single phase Design Current Ib (A): 7.8

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 35
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 7.8 Voltage drop limit = 11.62 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.7 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 7.8 / 1.00 0.0 / 0.00 0.0 / 0.00 7.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 5.12 / 2.23 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 7.47 / 3.25 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.33250 Z2 0.33250 Zs 0.80273 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.386 / 0.302
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 39 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV305 Name: Upstairs heating Plt Rm


Connected From: Dist.Board 3PH&N( DB1)/2/L2 To: Htg & Thermostat
Load Type: Heating and power, single phase Design Current Ib (A): 7.8

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 50
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 7.8 Voltage drop limit = 11.79 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 7.8 / 1.00 0.0 / 0.00 7.8
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 6.12 / 2.66 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 8.22 / 3.57 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.47500 Z2 0.47500 Zs 1.08765 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.21
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.281 / 0.220
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 40 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV306 Name: GF Lighting


Connected From: Dist.Board 3PH&N( DB1)/2/L3 To: Gnd fl ltg
Load Type: Lighting, radial circuits Design Current Ib (A): 4.0
Length to First Fitting (m): 3.00
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 80
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 4.0 Voltage drop limit = 7.53 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 12.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 4.0 / 1.00 4.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 5.04 / 2.19 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 7.01 / 3.05 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.24000 Z2 1.24000 Zs 2.61752 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.09
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.115 / 0.090
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 41 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV307 Name: G Floor SP & CWS TH


Connected From: Dist.Board 3PH&N( DB1)/3/L1 To: Sockets & Trace htg
Load Type: Sockets BS 1363, 20A radial circuit to sockets up to 50m² Design Current Ib (A): 5.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 RCBO C60H Type C 30mA


Rating In (A): 20 [f] Overload Setting Ir (A): N/A
RCD Trip rating : 0.03A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 4 [f]
Neutral: 4 mm² [a] Length (m): 20
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.0 Voltage drop limit = 11.5 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 42.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 5.0 / 1.00 0.0 / 0.00 0.0 / 0.00 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.98 / 0.43 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 3.32 / 1.44 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 4 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.12000 Z2 0.12000 Zs 0.37807 Max. Zs 7,663.60151 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 4 [f]
0.61
CPC Adiabatic check (mm 2) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.866 / 0.680
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 327.18 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 42 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV308 Name: Upsatirs Power Sockets


Connected From: Dist.Board 3PH&N( DB1)/3/L2 To: Sockets
Load Type: Sockets BS 1363, 20A radial circuit to sockets up to 50m² Design Current Ib (A): 5.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 RCBO C60H Type C 30mA


Rating In (A): 20 [f] Overload Setting Ir (A): N/A
RCD Trip rating : 0.03A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 4 [f]
Neutral: 4 mm² [a] Length (m): 45
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 5.0 Voltage drop limit = 11.73 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 20 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 42.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 5.0 / 1.00 0.0 / 0.00 5.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 2.20 / 0.96 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 4.30 / 1.87 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 4 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.27000 Z2 0.27000 Zs 0.67778 Max. Zs 7,663.60151 * Earth Fault
Disconnection time (s) From characteristic: 0.04 * Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 4 [f]
0.34
CPC Adiabatic check (mm 2) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.48
*Calculated for RCD protection

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.461 / 0.361
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 327.18 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 43 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV309 Name: Downstairs Lighting


Connected From: Dist.Board 3PH&N( DB1)/3/L3 To: GF l& Toilet ighting
Load Type: Lighting, radial circuits Design Current Ib (A): 2.0
Length to First Fitting (m): 5.00
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 84
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 2.0 Voltage drop limit = 7.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 2.0 / 1.00 2.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 2.69 / 1.17 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 4.66 / 2.03 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.30200 Z2 1.30200 Zs 2.74151 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.08
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.109 / 0.085
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 44 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV312 Name: Upstairs Lighting


Connected From: Dist.Board 3PH&N( DB1)/4/L3 To: LVAC Rm ltg
Load Type: Lighting, radial circuits Design Current Ib (A): 2.0
Length to First Fitting (m): 5.00
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 84
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 2.0 Voltage drop limit = 7.58 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.6 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 2.0 / 1.00 2.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 2.69 / 1.17 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 4.66 / 2.03 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.30200 Z2 1.30200 Zs 2.74151 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.08
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.109 / 0.085
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 45 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV314 Name: Security System


Connected From: Dist.Board 3PH&N( DB1)/5/L2 To: SEC Panel
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 2.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 70
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 2.5 Voltage drop limit = 12.02 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.9 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 2.5 / 1.00 0.0 / 0.00 2.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 5.29 / 2.30 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 7.38 / 3.21 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.08500 Z2 1.08500 Zs 2.30753 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.10
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.130 / 0.102
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 46 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV315 Name: Upstairs Lighting


Connected From: Dist.Board 3PH&N( DB1)/5/L3 To: Plt Rm ltg
Load Type: Lighting, radial circuits Design Current Ib (A): 3.0
Length to First Fitting (m): 1.00
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60947-2


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 3.0 Voltage drop limit = 7.3 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 11.2 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 3.0 / 1.00 3.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 2.77 / 1.20 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 4.74 / 2.06 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.93000 Z2 0.93000 Zs 1.99755 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.12
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.151 / 0.118
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 47 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV317 Name: Fire Alarm System


Connected From: Dist.Board 3PH&N( DB1)/5/L1 To: FAP
Load Type: Fixed equipment single phase and neutral Design Current Ib (A): 2.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Merlin Gerin Multi9 MCB C60H Type B BS EN60898


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Pirelli FP200 Fire resistant cable Cu 1 x 1 x 2c Size (mm2): 2.5 [f]


Neutral: 2.5 mm² [a] Length (m): 60
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 2.5 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 30.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 2.5 / 1.00 0.0 / 0.00 0.0 / 0.00 2.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 2.34 / 1.02 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 4.69 / 2.04 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.54000 Z2 0.57000 Zs 1.24762 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.19
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.67

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.236 / 0.196
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 82.66 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 48 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV318 Name: External Lighting


Connected From: Dist.Board 3PH&N( DB1)/6/L3 To: Ext Ltg
Load Type: Lighting, radial circuits Design Current Ib (A): 1.0
Length to First Fitting (m): 5.00
Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type B BS EN60898


Rating In (A): 10 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 1.5 [f]
Neutral: 1.5 mm² [a] Length (m): 70
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 1.0 Voltage drop limit = 7.42 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 10 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 10.1 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 23.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 1.0 / 1.00 1.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 1.13 / 0.49 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 3.10 / 1.35 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 1.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 1.08500 Z2 1.08500 Zs 2.30753 Max. Zs 4.59995 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 1.5 [f]
0.10
CPC Adiabatic check (mm 2) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.54

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.130 / 0.102
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 6,000.00 Adiabatic Limit k²S² (A²s): 46.01 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 49 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV319A Name: Trace Heating 1


Connected From: Dist.Board 3PH&N( DB1)/7/L1 To: Trace htg C-R/TR01
Load Type: Heating and power, single phase Design Current Ib (A): 4.7

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type C BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 62
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 4.7 Voltage drop limit = 11.93 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 17.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 4.7 / 1.00 0.0 / 0.00 0.0 / 0.00 4.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 5.40 / 2.35 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 7.74 / 3.37 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.58900 Z2 0.58900 Zs 1.31561 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.231 / 0.181
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 50 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV319B Name: RAD 1 Heater)


Connected From: Dist.Board 3PH&N( DB1)/7/L2 To: Rad heater C-R/TH01
Load Type: Heating and power, single phase Design Current Ib (A): 6.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type C BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 50
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 6.5 Voltage drop limit = 11.79 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 19.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 6.5 / 1.00 0.0 / 0.00 6.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 6.08 / 2.64 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 8.17 / 3.55 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.47500 Z2 0.47500 Zs 1.08765 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.21
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.281 / 0.220
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 51 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV319C Name: RAD 2 (Heater)


Connected From: Dist.Board 3PH&N( DB1)/7/L3 To: Rad heater C-R/TH02
Load Type: Heating and power, single phase Design Current Ib (A): 6.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type C BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 35
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 6.5 Voltage drop limit = 11.62 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 19.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 6.5 / 1.00 6.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 4.26 / 1.85 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 6.23 / 2.71 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.33250 Z2 0.33250 Zs 0.80273 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.29
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.386 / 0.302
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 52 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV320A Name: Trace Heating 2


Connected From: Dist.Board 3PH&N( DB1)/8/L1 To: Trace htg C-B/TR11
Load Type: Heating and power, single phase Design Current Ib (A): 4.7

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Merlin Gerin Multi9 MCB C60H Type B BS EN60898


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 4.7 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 17.8 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 4.7 / 1.00 0.0 / 0.00 0.0 / 0.00 4.7
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 5.22 / 2.27 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 7.57 / 3.29 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.57000 Z2 0.57000 Zs 1.27762 Max. Zs 2.87504 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.238 / 0.186
Protective Device Breaking Capacity (kA) Icu: 10 Ics: 10

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 53 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV320B Name: RAD 3 (Heater)


Connected From: Dist.Board 3PH&N( DB1)/8/L2 To: Rad heater C-B/TH11
Load Type: Heating and power, single phase Design Current Ib (A): 6.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type C BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 6.5 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 6.5 / 1.00 0.0 / 0.00 6.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 6.10 / 2.65 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 8.20 / 3.56 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.57000 Z2 0.57000 Zs 1.27762 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.238 / 0.186
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 54 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: LV320C Name: RAD 4 (Heater)


Connected From: Dist.Board 3PH&N( DB1)/8/L3 To: Rad heater C-B/TH12
Load Type: Heating and power, single phase Design Current Ib (A): 6.5

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Schneider Multi9 MCB C60H Type C BS EN60947-2


Rating In (A): 16 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Single-core, 90°C thermosetting insulated, non-arm, LSF Cu Table 4E1 1 x 2 x 1c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 60
6 - In horizontal trunking on a wooden/masonry wall Trunking: Metal

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group = 20 Cg = 0.38 [BS 7671, Table 4C1] Not Subject to Simultaneous Overload

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 6.5 Voltage drop limit = 11.9 V (BS 7671:2008 (2011) App. 4)
Device Rating In = 16 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 19.4 [BS 7671, Appendix 4.5, Formula (3/4)]
Actual Cable Rating It = 31.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 6.5 / 1.00 6.5
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 7.29 / 3.17 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 9.27 / 4.03 -----

Earth Fault Circuit Protective Conductor (mm²) Separate 2.5 [f] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.13919 Z1 0.57000 Z2 0.57000 Zs 1.27762 Max. Zs 1.43762 Earth Fault
Disconnection time (s) From characteristic: 0.02 Maximum for circuit: 0.40 Current (kA)
Circuit Protective Conductor (mm²) Separate 2.5 [f]
0.18
CPC Adiabatic check (mm 2) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.59

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 2.813 / 2.267 Load End: 0.238 / 0.186
Protective Device Breaking Capacity (kA) Icu: 15 Ics: 7.5

Adiabatic Check: CPD Energy Let-through (A²s): 7,000.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 55 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: Name:
Connected From: LVAC Section 400V 3PH&N To: DB-2
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 1
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 10.0


Device Rating In = 32 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 32.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 0.0 / 0.00 0.0 / 0.00 10.0 / 0.80 10.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.00 / 0.00 0.00 / 0.00 0.13 / 0.05 -----
Voltage Drop - From Source (V/%) 0.00 / 0.00 0.00 / 0.00 1.75 / 0.76 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.00950 Z2 0.01118 Zs 0.11017 Max. Zs 1.84027 Earth Fault
Disconnection time (s) From characteristic: 0.05 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
2.10
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.41

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 5.533 / 4.785 Load End: 4.260 / 3.546
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 56 of 57 Printed on: 06/05/2015


Created using: v2013.0.0 BS 7671:2008 (2011) - Parsons Brinckerhoff Ltd Copyright © Amtech Group Ltd 2013
Cable Calculation Report

Project Reference: Croham Cooling Station Job Number: EBG285252A


Document No: SCHE201 (NG 73/EAA/0019) Created On : 20/04/2010 Rev Date : 20/04/2015
Created By : ShankasS Modified By: OA Rev No: G

Calculated in accordance with BS 7671


Active Source: DNO LV Cabinet
Circuit

Id No.: Name:
Connected From: LVAC Section 400V 3PH&N To: DB-1
Load Type: Distribution Board Design Current Ib (A): 10.0

Comments:

Protective Device [a] = Auto, [f] = Fixed, [m] = Max.

Overcurrent protection: Generic BS 88-2 Fuse System E


Rating In (A): 32 [f] Overload Setting Ir (A): N/A

Conductors [a] = Auto, [f] = Fixed, [d] = Double

Multicore, 90°C thermosetting insulated, armoured LSF Cu Table 4E4 1 x 1 x 2c Size (mm2): 2.5 [f]
Neutral: 2.5 mm² [a] Length (m): 1
31 - On horizontal/vertical perforated tray

Rating Factors
Air Temperature (°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C4]

3rd Harmonics (%) = 0.00 Ch = 1.00

Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.

Design Current Ib = 10.0


Device Rating In = 32 Overload Setting Ir = N/A [Ir _> Ib]
Min. Cable Capacity Iz = 32.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 39.0 [It _> Iz]

Load Current and Voltage Drop L1 L2 L3 Neutral


Design Current Ib (A/PF) 10.0 / 0.80 0.0 / 0.00 0.0 / 0.00 10.0
3rd Harmonic Current (A) 0.0 0.0 0.0 0.0
Voltage Drop - This circuit (V/%) 0.13 / 0.05 0.00 / 0.00 0.00 / 0.00 -----
Voltage Drop - From Source (V/%) 1.98 / 0.86 0.00 / 0.00 0.00 / 0.00 -----

Earth Fault Circuit Protective Conductor (mm²) Armour 22 [a] [a] = Auto, [f] = Fixed

Earth Fault Loop Impedance ( ) Ze 0.09001 Z1 0.00950 Z2 0.01118 Zs 0.11017 Max. Zs 1.84027 Earth Fault
Disconnection time (s) From characteristic: 0.05 Maximum for circuit: 5.00 Current (kA)
Circuit Protective Conductor (mm²) Armour 22 [a]
2.10
CPC Adiabatic check (mm 2) CPC Section = Armour 5.5 Total = 5.5 Min. Section = 0.41

Phase Fault

Phase Fault Current Max./Min. (kA) Source End: 5.533 / 4.785 Load End: 4.260 / 3.546
Protective Device Breaking Capacity (kA) Icu: 80 Ics: 80

Adiabatic Check: CPD Energy Let-through (A²s): 3,400.00 Adiabatic Limit k²S² (A²s): 127.81 x 10 3

Project: Croham Cable Calcs 200415.p17 Page 57 of 57 Printed on: 06/05/2015