Technical data sheet

Hitachi ABB Power Grids


Project No. Date Rev
Project: Nitto Denko 502855671 2023-June 0

Design no.: 1LKR205709 Dgn. by: YPS


General Specification
Transformer Type Cast coil dry type Transformer
Standard IEC 60076-11:2018
Installation Indoor
Phase 3
Frequency [Hz] 50
Rated power [kVA] 2000
Rated high voltage [V] 22000
Rated low voltage [V] 208
Tapping on HV (De-energized tap changer) ± 2 steps X 2.5 %
Vector group Dyn11
Type of cooling AN
Insulation system thermal class (HV/LV) [°C] F/F (155/155)
Temperature rise at principal tapping (HV/LV) [K] 100/100
Winding conductor (HV/LV) Al/Al
Ambient temperature (Max./ Monthly / Yearly) [°C] 40/30/20
Altitude (below -) [m] 1000
C/E/F class C1/E2/F1

Technical Characteristic at AN, 75°C


No load loss [W] 4000 +15% IEC tolerance
Load loss [W] 14500 +15% IEC tolerance
Impedance [%] 6 ±10% IEC tolerance
Full wave lightning impulse (HV/LV) [kV] 125 / -
Applied voltage (HV/LV) [kV] 50 / 3
Sound pressure level at 1.0m (LpA) dB(A) 66

Accessories
- Rating plate
- Lifting lug, Jacking point and Pulling hole
- Thermometer: KN-805

- Cooling fan
- Bi-directional roller

Notes
1. Other accessories which are not mentioned in the above statements are not included.
2. Cable connection and termination materials are not included. (e.g. cable lug, flexible bus bar)
3. Routine test: voltage ratio test for each tapping and other tests at principal tapping according to IEC standard.
4. The tolerances for all guaranteed values are subject to IEC standard.
5. If no other standards or rules are specified, transformers are manufactured according to IEC standard.
6. Harmonic effects are not considered if not specified in the data sheet.