Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 4 x 1c Size (mm2 ): 6 [a]
Neutral: 6 mm²[a] Length (m): 10
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 37.1
Device Rating In = 40 Overload Setting Ir = 40 _ Ib]
[Ir >
Min. Cable Capacity Iz = 40.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 40.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.63
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 1.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.846 / 8.495 Load End: 5.206 / 2.240
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 25
Adiabatic Check: CPD Energy Let-through (A²s): 41.71 x 103 Adiabatic Limit k²S² (A²s): 736.16 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 4 x 1c Size (mm2 ): 25 [a]
Neutral: 25 mm²[a] Length (m): 10
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Design Current Ib = 73.4
Device Rating In = 80 Overload Setting Ir = 80 _ Ib]
[Ir >
Min. Cable Capacity Iz = 80.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 95.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 5.00
0.84
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 1.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 12.846 / 8.495 Load End: 9.542 / 5.106
Protective Device Breaking Capacity (kA): Icu: 45 Ics: 25
Adiabatic Check: CPD Energy Let-through (A²s): 152.36 x 103 Adiabatic Limit k²S² (A²s): 12.78 x 106
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 24
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.0
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.20
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.26
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.577 / 0.412
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 73
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 6.5
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.26 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.37
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.204 / 0.154
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 37
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.09 Maximum for circuit: 0.40
0.36
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.777 / 1.079
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 4,373.12 Adiabatic Limit k²S² (A²s): 327.18 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 57
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.3
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.29 Maximum for circuit: 0.40
0.10
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.39
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.259 / 0.194
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 40
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 2.6
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.14
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.26
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.362 / 0.267
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 29
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 2.6
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 2.076 / 1.215
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 4,932.67 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 24
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.19 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.67
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.860 / 0.590
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 2,041.07 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 13
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.31
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.399 / 0.891
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 3,186.04 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 19
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.05 Maximum for circuit: 0.40
0.25
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.043 / 0.697
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 2,448.19 Adiabatic Limit k²S² (A²s): 327.18 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 38
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.0
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.14
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.26
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.379 / 0.279
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 13
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.31
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.399 / 0.891
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 3,186.04 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 19
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.05 Maximum for circuit: 0.40
0.25
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.043 / 0.697
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 2,448.19 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 21
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.09 Maximum for circuit: 0.40
0.24
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 0.961 / 0.650
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 2,268.81 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 65
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.0
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.08 Maximum for circuit: 0.40
0.37
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.341 / 0.969
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 3,923.69 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 56
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 9.6
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.03 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.528 / 1.093
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 4,432.16 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 57
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.2
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.04 Maximum for circuit: 0.40
0.40
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.505 / 1.078
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 4,369.34 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 33
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.8
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.02 Maximum for circuit: 0.40
0.45
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 2.370 / 1.623
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 6,812.49 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 51
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.2
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.11 Maximum for circuit: 0.40
0.36
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.84
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.656 / 1.177
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 4,774.94 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 72
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.2
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.15 Maximum for circuit: 0.40
0.35
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.95
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 1.224 / 0.891
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 3,601.34 Adiabatic Limit k²S² (A²s): 327.18 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 116
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 7.9
Device Rating In = 10 Overload Setting Ir = 10 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.16 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.132 / 0.102
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 12.28 Actual disconnection time (s) = 0.33
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 72
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 11.0
Device Rating In = 16 Overload Setting Ir = 16 [Ir >
_ Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.39 Maximum for circuit: 0.40
0.17
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.72
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.212 / 0.163
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 4.81 Actual disconnection time (s) = 0.43
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 68
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 4.8
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.11 Maximum for circuit: 0.40
0.12
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.26
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.224 / 0.172
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 33
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 9.2
Device Rating In = 16 Overload Setting Ir = 16 _ Ib]
[Ir >
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.31 Maximum for circuit: 0.40
0.17
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.67
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.452 / 0.344
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,600.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 76
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 5.3
Device Rating In = 10 Overload Setting Ir = 10 _ Ib]
[Ir >
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.24 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.37
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.201 / 0.155
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,350.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 27
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.19 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 1 Total = 1.0 Min. Section = 0.66
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.845 / 0.628
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 2,187.36 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 41
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.05 Maximum for circuit: 0.40
0.25
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.571 / 0.431
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 32
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.08 Maximum for circuit: 0.40
0.24
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.721 / 0.540
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,851.45 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 43
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.07 Maximum for circuit: 0.40
0.24
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.29
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.545 / 0.412
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 50
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 6.9 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 7.9
Device Rating In = 16 Overload Setting Ir = 16 _ Ib]
[Ir >
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.16 Maximum for circuit: 0.40
0.19
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.52
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.302 / 0.232
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,600.00 Adiabatic Limit k²S² (A²s): 127.81 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 51
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.20 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.68
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.463 / 0.352
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 65
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.19 Maximum for circuit: 0.40
0.22
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.66
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.366 / 0.280
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 116
4 - In conduit on a wooden/masonry wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 7.9
Device Rating In = 10 Overload Setting Ir = 10 [Ir >
_ Ib]
Min. Cable Capacity Iz = 10.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 31.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.16 Maximum for circuit: 0.40
0.11
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.132 / 0.102
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 12.28 Actual disconnection time (s) = 0.33
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 54
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.29 Maximum for circuit: 0.40
0.21
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.79
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.438 / 0.333
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 46
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.10 Maximum for circuit: 0.40
0.23
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.53
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.511 / 0.387
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 46
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 12.0
Device Rating In = 20 Overload Setting Ir = 20 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 2.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.10 Maximum for circuit: 0.40
0.23
Adiabatic check (mm 2 ) CPC Section = Separate 2.5 Total = 2.5 Min. Section = 0.53
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.511 / 0.387
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: CPD Energy Let-through (A²s): 1,700.00 Adiabatic Limit k²S² (A²s): 327.18 x 103
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 1 x 2 x 1c Size (mm2 ): 2.5 [f]
Neutral: 2.5 mm²[a] Length (m): 64
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (User defined)
Design Current Ib = 9.7
Device Rating In = 16 Overload Setting Ir = 16 [Ir >
_ Ib]
Min. Cable Capacity Iz = 16.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 26.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 4 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.20 Maximum for circuit: 0.40
0.18
Adiabatic check (mm 2 ) CPC Section = Separate 4 Total = 4.0 Min. Section = 0.57
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 9.542 / 5.106 Load End: 0.237 / 0.183
Protective Device Breaking Capacity (kA): Icu: 15 Ics: 7.5
Adiabatic Check: Max. disconnection time (s) = (k²S²/I²): 3.82 Actual disconnection time (s) = 0.19
Cable CKTP105
Connection From: DB-P1/1/L3 To: P105
Active Source: Source-1
Load Type: Sockets BS 1363, 32A ring final circuit to sockets up to 100m² Design Current Ib (A): 6.1
Comments
Single-core, 90°C thermosetting, insulated, non-arm Cu Table 4E1 2 x 2 x 1c Size (mm2 ): 4 [f]
Neutral: 4 mm²[a] Length (m): 46
1 - In conduit in a thermally insulated wall Conduit: Plastic
Rating Factors
Air Temperature(°C) = 30.0 Ca = 1.00 [BS 7671, Table 4B1]
Circuits In Group =1 Cg = 1.00 [BS 7671, Table 4C1]
Cable sizing (A) Sized For: Phase Current Carrying Capacity Auto-sized for current-carrying capacity and voltage drop limits.
Voltage drop limit = 11.5 V (to BS 7671:2008 Appendix 12)
Design Current Ib = 6.1
Device Rating In = 32 Overload Setting Ir = 32 [Ir >
_ Ib]
Min. Cable Capacity Iz = 20.0 [BS 7671, Appendix 4.5, Formula (1)]
Actual Cable Rating It = 35.0 _ Iz]
[It >
Earth Fault Circuit Protective Conductor (CPC) (mm²): Separate 1.5 [a] [a] = Auto, [f] = Fixed
Disconnection time (s): From characteristic: 0.06 Maximum for circuit: 0.40
0.38
Adiabatic check (mm 2 ) CPC Section = Separate 1.5 Total = 1.5 Min. Section = 0.31
Phase Fault
Phase Fault Current Max./Min. (kA): Source End: 5.206 / 2.240 Load End: 1.529 / 0.958
Protective Device Breaking Capacity (kA): Icu: 10 Ics: 10
Adiabatic Check: CPD Energy Let-through (A²s): 3,876.76 Adiabatic Limit k²S² (A²s): 327.18 x 103