" POWER DETAILS "

PROJECT NAME: LTE PH 18 AC UPGRADE

SITE NAME : MALVAR-BULIHAN

SITE ID : V16

AREA: SOUTH LUZON

SURVEYED DATE: June 17, 2019

SUBCON: BM Power General Construction and Sales Corp.

ASSESSMENT:

APPROVED REMARKS:

DISAPPROVED REMARKS:

SIGNATURE OVER PRINTED NAME


SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: V16
SMART Site Name: Malvar - Bulihan
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

A3 - AC Power Details / Checklists


AC Power System

RATING NEED PICTURES

1 CAPACITY / RATING OF THE DISTRIBUTION TRANSFORMER


SINGLE PHASE (ex. 15KVA, 25KVA, 37.5KVA, 50KVA) 1 x 37.5 kVA
THREE PHASE (i.e., 2x25KVA; 3x25KVA, 2x37.5KVA, 2x50KVA)
2 COMMERCIAL POWER AVAILABILITY
PERMANENT
PERMANENT TAPPED TO BUILDING
TEMPORARY TAPPED TO RESIDENTIAL/BLDG
PRIME SITES (RUNNING ON GENSET)
3 SIZE OF DROP WIRE (BATELEC II)
CABLE , BRAND 2x38mm2 THHN
LENGTH FROM THE PRIVATE POLE TO MCB 12m
4 SIZE OF MAIN CIRCUIT BREAKER (MCB)
AMPERE TRIP RATING (ex. 100AT, 125AT, 150AT) 150 AT
KAIC RATING 25 kAIC @ 240 V
NO. OF POLES (ex. 2P, 3P) 2P
BRAND (Square D, GE) Square D
TYPE OF ENCLOSURE (Nema 1, Nema 2) NEMA 3R
5 CLAMPMETER LOAD READING AT MCB
LINE 1 45.7
LINE 2 40.6
LINE 3
6 IDENTIFY THE CAPACITY OF KWHR METER
CLASS, RATING CL200
SINGLE PHASE / THREE PHASE 2W, Single Phase
Voltage 240
Form 1S
Brand FOCUS
7 SIZE OF THE CABLE / WIRE SEVICE ENTRANCE
CABLE , BRAND 2x50mm2, THHN
NUMBER OF WIRES 2
8 MAIN PANEL BOARD
TYPE OF ENCLOSURE NEMA 1
NO OF BRANCH CIRCUIT BREAKER (IDENTIFY THRU DRAWING) 11
ACTUAL CURRENT CONSUMPTION (USING CLAMP METER ) L1-45.7/ L2-40.6
9 AUTOMATIC TRANSFER SWITCH
TYPE OF ENCLOSURE NEMA 3R
AMPERE TRIP RATING 250
KAIC RATING
AMPERE FRAME
NO. OF POLES 3
BRAND Powercity
10 MANUAL TRANSFER SWITCH
NO. OF POLES 2
TYPE OF ENCLOSURE NEMA 3R
AMPERE TRIP RATING 2x150AT
VOLTAGE RATING 240
BRAND Square D
11 GENSET PAD AND FUEL LINE (Y/N) N
12 GENSET FUEL TANK (LITERS)
13 SITE CATEGORY (PLEASE CHECK BELOW)
LOT SITE
BUILDING SITE
ROOF DECK
COW
MEOW
METRO SITE / POLE MOUNTED
14 SITE TYPE (PLEASE CHECK BELOW)
INDOOR
OUTDOOR
SITE SURVEY REPORT
DOCUMENT NO PAGE

TECHNICAL SERVICES DIVISION


SITE ID AREA SITE NAME: VENDOR

V16 SL
MALVAR-BULIHAN

ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS

AC POWER DETAILS
Electrical Connectivity: Permanent Temporary Tap to neighbor

Others pls specify

Power Source: Commercial power available Name of provider: BATELEC II

Genset

Genset 1 Brand: Powercity Genset 1 capacity: 60 KVA With Pad & Fuel Line (Y/N): N

Genset 1 Brand: Genset 2 capacity: With Pad & Fuel Line (Y/N):
Genset 1 Brand: Genset 3 capacity: With Pad & Fuel Line (Y/N):

Phase: Single phase Three Phase

KWHR Meter Rating: CL200 ATS Brand: Powercity ATS Capacity: 225A, 3P

MTS: 2x150AT

Main breaker capacity( inside radio room ): 150 AT Wire size: 2-50mm²THHN

Thermal Reading: 11 BRANCHES


Wires: _____________ Circuit Breakers: __________________

Actual AC Load: L1-45.7 / L2-40.6

MCB ACPDB
Rating ON/OFF LOAD Rating ON/OFF LOAD
150 ON SPACE
70 ON RECTIFIER
50 ON RECTIFIER
50 OFF SPARE
40 OFF SPARE
*put NO LABEL for those
without proper labelling 20 ON COMBA REPEATER
40 ON PERIMETER LIGHT
40 ON TOWER LIGHT
32 ON ACU2
32 ON ACU 1
20 ON C.O.
20 ON ROOM LIGHT
SITE SURVEY REPORT
DOCUMENT NO PAGE

TECHNICAL SERVICES DIVISION


SITE ID AREA Site Name

V16 S.L MALVAR-BULIHAN


SITE ACTIVITY
LTE AC UPGRADE AC & DC POWER DETAILS
AC Power System

SHELTER TYPE (VAN, CONCETE SHELTER, BLDG):VAN AC Loading @ MAIN (AMPERES): L1-45.7 / L2-40.6
SHELTER AREA: LOT SITE SIZE OF WIRE @ ACPDB - MAIN (mm²/AWG): 2-50mm²
TYPE OF VAN (COLLAPSIBLE, RIGID) : LENGTH OF WIRE: 25 m
TRANSFORMER QUANTITY & CAPACITY (KVA): 37.5 KVA
ACPDB RATING (AT): 150 MAIN BREAKER RATING(AT): 150
Breaker Ratings (AT) Load AMP Load Description
SPACE
70 17.5 RECTIFIER
50 14.1 RECTIFIER
50 SPARE
40 SPARE
20 COMBA REPEATER
40 1.0 PERIMETER LIGHT
40 1.3 TOWER LIGHT
32 9.1 ACU 2
32 6.5 ACU 1
20 0.3 C.O.
20 0.8 ROOM LIGHT

PICTURE OF AC CONFIDENTIAL CONFIDENTIAL CONFIDENTIAL


CLAMP METER INSERT PICTURE INSERT PICTURE INSERT PICTURE
READING
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: V16
SMART Site Name: Malvar - Bulihan
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

AC POWER SUFFICIENCY
Current (I)
AC LOAD Voltage (V) VA Remarks
L1 L2 L3
MAIN BREAKER 210 45.7 40.6 At ACPDB

9597.00

Total 45.7

It = Highest line current reading x 130 % (Safety factor considering Battery charging, WACU starting current & DC loading increase)
It = 45.7 x 130 %
It = 59.41 Amps.
Recommendation/s:

Transformer loading:
Actual AC load (V x It) / Transformer KVA Rating X 100 %
% loading = 33.27 %
Note: Sufficient

TRANSFORMER KWHR METER

NO PICTURE NO PICTURE

ECB MCB

NO PICTURE NA
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: V16
SMART Site Name: Malvar - Bulihan
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

PHOTOS

MTS ATS

N/A

MOBILE BOX ACPDB

N/A

GENSET FUEL TANK

N/A N/A
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: V16
SMART Site Name: Malvar - Bulihan
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

PHOTOS

N/A

Damaged Service Cap

N/A

Sign of Termination Overheating

N/A N/A
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: V16
SMART Site Name: Malvar - Bulihan
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

PHOTOS

Sign of Termination Overheating

N/A

N/A

N/A N/A
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: V16
SMART Site Name: Malvar - Bulihan
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

B5 - SITE LAYOUT

RECTIFIER
RECTIFIER

ACPDB
150 AT
50 mm2 + 14 mm2 THHN U.G.,
25 meters, 1 1/2 in. dia. IMC
ATS
225 A ECB
MTS 150 AT
GENERATOR 150 AT
50 mm2 + 14 mm2 THHN U.G.,
6 meters, 1 1/2 in. dia. IMC
KWHR
CL200
12 meters - 38 mm2 THHN AERIAL
TRANSFORMER 7 meters - 50 mm2 THHN 1 1/2 in. dia. IMC
37.5KVA

BRGY. SAN ISIDRO ROAD

NEW SITE LAYOUT


RECTIFIER
RECTIFIER

NEW
ACPDB
150 AT 50 mm2 + 14 mm2 THHN U.G.,
25 meters, 1 1/2 in. dia. IMC
MB
ATS 150 AT
225 A ECB
MTS 150 AT
GENERATOR 150 AT
50 mm2 + 14 mm2 THHN U.G.,
6 meters, 1 1/2 in. dia. IMC
KWHR
CL200
( Replace service cap )
12 meters - 50 mm2 THHN AERIAL
TRANSFORMER 7 meters - 50 mm2 THHN 1 1/2 in. dia. IMC
37.5KVA

BRGY. SAN ISIDRO ROAD


DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR

V16 S.L
MALVAR-BULIHAN

ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS

Existing AC Power Single Line Diagram

7 meters
50 mm2 THHN,
2 in. dia. IMC
TRANSFORMER
37.5 KVA 12 meters
38 mm2 THHN AERIAL CL200 M
50 mm2 + 14 mm2 THHN U.G.,
L1: 45.7 6 meters, 1 1/2 in. dia. IMC
ECB
150 AT L2: 40.6
50 mm2 + 14 mm2 THHN U.G., V: 210
25 meters, 1 1/2 in. dia. IMC

N E
ATS
225 A
G
L
50 mm2 + 14 mm2 THHN ,
3 meters, 1 1/2 in. dia. IMC

N E
MTS
150 AT
L
50 mm2 + 14 mm2 THHN U.G.,
3 meters, 1 1/2 in. dia. PVC
ACPDB L1: 45.7
L2: 40.6
(Square D)

150AT,2P

70AT,2P
SPACE 1 2 RECTIFIER
50AT,2P 50AT,2P
RECTIFIER 3 4 SPARE
40AT,2P 20AT,2P
COMBA REPEATER
SPARE 5 6
40AT,2P 40AT,2P
PERIMETER
LIGHT 7 8 TOWER LIGHT
32AT,2P 32AT,2P
ACU 2 9 10 ACU 1
20AT,2P 20AT,2P
C.O 11 12 ROOM LIGHT
DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR

V16 S.L
MALVAR-BULIHAN

ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS

Proposed SLD

7 meters
50 mm2 THHN,
2 in. dia. IMC
(Replace service cap)
TRANSFORMER
37.5 KVA 12 meters
50 mm2 THHN AERIAL CL200 M
50 mm2 + 14 mm2 THHN U.G.,
L1: 45.7 6 meters, 1 1/2 in. dia. IMC
ECB
150 AT L2: 40.6
50 mm2 + 14 mm2 THHN U.G., V: 210
25 meters, 1 1/2 in. dia. IMC

N E
ATS
225 A
G
L 50 mm2 + 14 mm2 THHN ,
50 mm2 + 14 mm2 THHN , 3 meters, 1 1/2 in. dia. IMC
3 meters, 1 1/2 in. dia. IMC

N E
MB
MTS 150AT
150 AT
50 mm2 + 14 mm2 THHN , L
3 meters, 1 1/2 in. dia. PVC
NEW ACPDB

150AT,2P

70AT,2P 70AT,2P
RECTIFIER #1 SUPPLY A 1 2 RECTIFIER #1 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #2 SUPPLY A 3 4 RECTIFIER #2 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #3 SUPPLY A 5 6 RECTIFIER #3 SUPPLY B
30AT,2P 30AT,2P
ACU 1 7 8 ACU 2
30AT,2P 30AT,2P
ACU 3 9 10 ACU ( FUTURE )
20AT,2P 20AT,2P
C.O. 11 12 LIGHTINGS
20AT,2P 20AT,2P
TOWER LIGHT
13 14 PERIMETER LIGHT
20AT,2P 20AT,2P
SPARE 15 16 SPARE