SITE ID : S1317
ASSESSMENT:
APPROVED REMARKS:
DISAPPROVED REMARKS:
S1317 SL
SUN-BALETE-MALABANAN
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
AC POWER DETAILS
Electrical Connectivity: Permanent Temporary Tap to neighbor
Genset
Genset 1 Brand: Genset 1 capacity: With Pad & Fuel Line (Y/N):
Genset 1 Brand: Genset 2 capacity: With Pad & Fuel Line (Y/N):
Genset 1 Brand: Genset 3 capacity: With Pad & Fuel Line (Y/N):
MTS: 200 A
Main breaker capacity( inside radio room ): 250 AT Wire size: 2-80mm²THHN
MCB MDP
Rating ON/OFF LOAD Rating ON/OFF LOAD
250 ON 100 OFF NO LABEL
32 ON NO LABEL
20 ON NO LABEL
32 ON NO LABEL
16 ON NO LABEL
*put NO LABEL for those
without proper labelling 32 OFF NO LABEL
16 OFF NO LABEL
20 ON NO LABEL
20 OFF SPARE
50 ON NO LABEL
SPACE
50 ON NO LABEL
SITE SURVEY REPORT
DOCUMENT NO PAGE
SHELTER TYPE (VAN, CONCETE SHELTER, BLDG):VAN AC Loading @ MAIN (AMPERES): L1-31.3/ L2-30.0
SHELTER AREA: LOT SITE SIZE OF WIRE @ ACPDB - MAIN (mm²/AWG): 2-80mm²
TYPE OF VAN (COLLAPSIBLE, RIGID) : LENGTH OF WIRE: 32m
TRANSFORMER QUANTITY & CAPACITY (KVA): Rating not Indicated
ACPDB RATING (AT): 250 MAIN BREAKER RATING(AT): 250
Breaker Ratings (AT) Load AMP Load Description
100 NO LABEL
32 0.5 NO LABEL
20 1.1 NO LABEL
32 0.6 NO LABEL
16 0.8 NO LABEL
32 NO LABEL
16 NO LABEL
### 20 0.3 NO LABEL
20 SPARE
50 10.5 NO LABEL
SPACE
50 11.5 NO LABEL
AC POWER SUFFICIENCY
Current (I)
AC LOAD Voltage (V) VA Remarks
L1 L2 L3
MAIN BREAKER 213 31.3 30.0 At ACPDB
6666.90
Total 31.3
It = Highest line current reading x 130 % (Safety factor considering Battery charging, WACU starting current & DC loading increase)
It = 31.3 x 130 %
It = 40.69 Amps.
Recommendation/s:
Transformer loading:
Actual AC load (V x It) / Transformer KVA Rating X 100 %
% loading = Transformer rating not identified
Note: Sufficient
NO PICTURE NO PICTURE
ECB MCB
NO PICTURE NA
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
MTS ATS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
B5 - SITE LAYOUT
TO LEVISTE HIGHWAY
RECTIFIER
RECTIFIER
ACPDB
250 AT
MTS
200 AT
(mounted below
the ACPDB)
MB
80 mm2 + 22 mm2 THHN U.G.,
200 A 32 meters, 2 in. dia. IMC
Lugs Only
ECB
175 AT
(DETERIORATED) DAMAGE SERVICE CAP
TRANSFORMER
Rating not indicated
RECTIFIER
RECTIFIER
NEW ACPDB
150 AT
NEW MB
150 AT
NEW ECB
150 AT
REPLACE SERVICE CAP
TRANSFORMER
25 KVA
DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR
S1317 S.L
SUN-BALETE-MALABANAN
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
5 meters
80 mm2 THHN,
2 in. dia. IMC
DAMAGE SERVICE CAP
TRANSFORMER
Rating not indicated 35 meters
38 mm2 THHN AERIAL CL200 M
(DETERIORATED)
N E
MTS MB
200 AT 200A LUGS ONLY
NEMA 1 NEMA 3R
L
250AT,2P
100AT,2P 32AT,2P
NO LABEL 1 2 NO LABEL
20AT,2P 32AT,2P
NO LABEL 3 4 NO LABEL
16AT,2P 32AT,2P
NO LABEL 5 6 NO LABEL
16AT,2P 20AT,2P
NO LABEL 7 8 NO LABEL
20AT,2P 50AT,2P
SPARE 9 10 NO LABEL
50AT,2P
SPACE 11 12 NO LABEL
DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR
S1317 S.L
SUN-BALETE-MALABANAN
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
Proposed SLD
5 meters
80 mm2 THHN,
2 in. dia. IMC
REPLACE SERVICE CAP
TRANSFORMER
25 KVA 35 meters
50 mm2 THHN AERIAL CL200 M
N E MB
MTS 150 AT
150AT
NEMA 3R NEMA 3R
L
(RELOCATE MTS OUTSIDE THE CABIN)
80 mm2 + 22 mm2 THHN ,
4 meters, 1 1/2 in. dia. IMC
NEW ACPDB
150AT,2P
70AT,2P 70AT,2P
RECTIFIER #1 SUPPLY A 1 2 RECTIFIER #1 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #2 SUPPLY A 3 4 RECTIFIER #2 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #3 SUPPLY A 5 6 RECTIFIER #3 SUPPLY B
20AT,2P 20AT,2P
ACU 1 7 8 ACU 2
20AT,2P 20AT,2P
ACU 3 9 10 ACU ( FUTURE )
20AT,2P 20AT,2P
C.O. 11 12 LIGHTINGS
TOWER LIGHT 13 14 PERIMETER LIGHT
SPARE 15 16 SPARE