You are on page 1of 16

" POWER DETAILS "

PROJECT NAME: LTE PH 18 AC UPGRADE

SITE NAME : LIAN

SITE ID : 698

AREA: SOUTH LUZON

SURVEYED DATE: June 19, 2019

SUBCON: BM Power General Construction and Sales Corp.

ASSESSMENT:

APPROVED REMARKS:

DISAPPROVED REMARKS:

SIGNATURE OVER PRINTED NAME


SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: 698
SMART Site Name: Lian
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

A3 - AC Power Details / Checklists


AC Power System

RATING NEED PICTURES

1 CAPACITY / RATING OF THE DISTRIBUTION TRANSFORMER


SINGLE PHASE (ex. 15KVA, 25KVA, 37.5KVA, 50KVA) 1 x 25 kVA
THREE PHASE (i.e., 2x25KVA; 3x25KVA, 2x37.5KVA, 2x50KVA)
2 COMMERCIAL POWER AVAILABILITY
PERMANENT
PERMANENT TAPPED TO BUILDING
TEMPORARY TAPPED TO RESIDENTIAL/BLDG
PRIME SITES (RUNNING ON GENSET)
3 SIZE OF DROP WIRE (BATELEC I)
CABLE , BRAND 2x38mm2 THHN
LENGTH FROM THE PRIVATE POLE TO MCB 100m
4 SIZE OF MAIN CIRCUIT BREAKER (MCB)
AMPERE TRIP RATING (ex. 100AT, 125AT, 150AT) 150 AT
KAIC RATING 22 kAIC @ 240 V
NO. OF POLES (ex. 2P, 3P) 2P
BRAND (Square D, GE) Square D
TYPE OF ENCLOSURE (Nema 1, Nema 2) NEMA 3R
5 CLAMPMETER LOAD READING AT MCB
LINE 1 40.1
LINE 2 37.3
LINE 3
6 IDENTIFY THE CAPACITY OF KWHR METER
CLASS, RATING CL200
SINGLE PHASE / THREE PHASE 3W, Single Phase
Voltage 240
Form 2S
Brand G.E.
7 SIZE OF THE CABLE / WIRE SEVICE ENTRANCE
CABLE , BRAND 2x50mm2, THHN
NUMBER OF WIRES 2
8 MAIN PANEL BOARD
TYPE OF ENCLOSURE NEMA 1
NO OF BRANCH CIRCUIT BREAKER (IDENTIFY THRU DRAWING) 14
ACTUAL CURRENT CONSUMPTION (USING CLAMP METER ) L1-40.1/ L2-37.3
9 AUTOMATIC TRANSFER SWITCH
TYPE OF ENCLOSURE NEMA 3R
AMPERE TRIP RATING 250
KAIC RATING
AMPERE FRAME
NO. OF POLES 3
BRAND Powercity
10 MANUAL TRANSFER SWITCH
NO. OF POLES 2
TYPE OF ENCLOSURE NEMA 3R
AMPERE TRIP RATING Unidentified
VOLTAGE RATING 240
BRAND
11 GENSET PAD AND FUEL LINE (Y/N) Y
12 GENSET FUEL TANK (LITERS)
13 SITE CATEGORY (PLEASE CHECK BELOW)
LOT SITE
BUILDING SITE
ROOF DECK
COW
MEOW
METRO SITE / POLE MOUNTED
14 SITE TYPE (PLEASE CHECK BELOW)
INDOOR
OUTDOOR
SITE SURVEY REPORT
DOCUMENT NO PAGE

TECHNICAL SERVICES DIVISION


SITE ID AREA SITE NAME: VENDOR

698 SL
LIAN

ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS

AC POWER DETAILS
Electrical Connectivity: Permanent Temporary Tap to neighbor

Others pls specify

Power Source: Commercial power available Name of provider: BATELEC I

Genset

Genset 1 Brand: Powercity Genset 1 capacity: 45 KVA With Pad & Fuel Line (Y/N): Y

Genset 1 Brand: Genset 2 capacity: With Pad & Fuel Line (Y/N):
Genset 1 Brand: Genset 3 capacity: With Pad & Fuel Line (Y/N):

Phase: Single phase Three Phase

KWHR Meter Rating: CL200 ATS Brand: Powercity ATS Capacity: 250A, 3P

MTS: Unable to identify

Main breaker capacity( inside radio room ): 100 AT Wire size: 2-50mm²THHN

Thermal Reading: 14 BRANCHES


Wires: _____________ Circuit Breakers: __________________

Actual AC Load: L1-40.1 / L2-37.3

MCB ACPDB
Rating ON/OFF LOAD Rating ON/OFF LOAD
150 ON 70 ON ELTEK RECT 1 A
70 ON ELTEK L1
50 ON ELTEK L2
50 ON ELTEK RECT 1 B
40 ON NO LABEL
*put NO LABEL for those
without proper labelling 40 OFF SPARE
40 ON SPARE
40 ON SPARE
30 ON NO LABEL
30 ON ACU 2
30 ON NO LABEL
30 ON ACU 1
20 ON LIGHTINGS
20 ON C.O.
SITE SURVEY REPORT
DOCUMENT NO PAGE

TECHNICAL SERVICES DIVISION


SITE ID AREA Site Name

698 S.L LIAN


SITE ACTIVITY
LTE AC UPGRADE AC & DC POWER DETAILS
AC Power System

SHELTER TYPE (VAN, CONCETE SHELTER, BLDG):VAN AC Loading @ MAIN (AMPERES): L1-40.1 / L2-37.3
SHELTER AREA: LOT SITE SIZE OF WIRE @ ACPDB - MAIN (mm²/AWG): 2-50mm²
TYPE OF VAN (COLLAPSIBLE, RIGID) : LENGTH OF WIRE: 50 m
TRANSFORMER QUANTITY & CAPACITY (KVA): 25 KVA
ACPDB RATING (AT): 100 MAIN BREAKER RATING(AT): 150
Breaker Ratings (AT) Load AMP Load Description
70 4.1 ELTEK RECT 1 A
70 12.5 ELTEK L1
50 10.9 ELTEK L2
50 4.3 ELTEK RECT 1 B
40 0.1 NO LABEL
40 SPARE
40 SPARE
40 SPARE
30 0.7 NO LABEL
30 9.4 ACU 2
30 0.2 NO LABEL
30 0.5 ACU 1
20 0.4 LIGHTINGS
20 0.2 C.O.

(MAIN) (BRANCHES)

PICTURE OF AC CONFIDENTIAL CONFIDENTIAL CONFIDENTIAL


CLAMP METER INSERT PICTURE INSERT PICTURE INSERT PICTURE
READING
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: 698
SMART Site Name: Lian
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

AC POWER SUFFICIENCY
Current (I)
AC LOAD Voltage (V) VA Remarks
L1 L2 L3
MAIN BREAKER 212 40.1 37.3 At ACPDB

8501.20

Total 40.1

It = Highest line current reading x 130 % (Safety factor considering Battery charging, WACU starting current & DC loading increase)
It = 40.1 x 130 %
It = 52.13 Amps.
Recommendation/s:

Transformer loading:
Actual AC load (V x It) / Transformer KVA Rating X 100 %
% loading = 44.21 %
Note: Sufficient

TRANSFORMER KWHR METER

NO PICTURE NO PICTURE

ECB MCB

NO PICTURE NA
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: 698
SMART Site Name: Lian
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

PHOTOS

MTS ATS

N/A

MOBILE BOX ACPDB

N/A

GENSET FUEL TANK

N/A N/A
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: 698
SMART Site Name: Lian
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

PHOTOS

N/A

N/A

Sign of Termination Overheating at ECB ( Line Side )

N/A N/A
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: 698
SMART Site Name: Lian
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

PHOTOS

Sign of Termination Overheating at ECB ( Load Side )

N/A

N/A

N/A N/A
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: 698
SMART Site Name: Lian
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

PHOTOS

N/A

N/A

N/A N/A
SITE SURVEY REPORT
DOCUMENT NO

TECHNICAL SERVICES DIVISION


VENDOR
Scope: LTE AC UPGRADE
SMART Site No.: 698
SMART Site Name: Lian
SUN Site No.:
SUN Site Name:
Area: SOUTH LUZON

B5 - SITE LAYOUT

KWHR
ECB
CL200
150 AT
DETERIORATED
50 mm2 + 14 mm2 THHN U.G.,
50 meters, 2 in. dia. IMC
TO ST. JOHN BAPTIST PARISH CHURCH

MTS
SWITCH ACPDB
TYPE 100 AT

50 mm2 + 14 mm2 THHN,


5 meters, 2 in. dia. IMC

MCB
GENERATOR

150 AT RECTIFIER
DETERIORATED
ATS RECTIFIER
250 A

FUEL TANK
50 mm2 + 14 mm2 THHN U.G.,
17 meters, 2 in. dia. IMC

100 meters - 38 mm2 THHN AERIAL


8 meters - 50 mm2 THHN 1 1/2 in. dia. IMC

TRANSFORMER
25 KVA
CALATAGAN - LIAN HIGHWAY

NEW SITE LAYOUT

KWHR
ECB
CL200
150 AT

50 mm2 + 14 mm2 THHN U.G.,


50 meters, 2 in. dia. IMC
TO ST. JOHN BAPTIST PARISH CHURCH

ACPDB
MB 150 AT
150 AT
50 mm2 + 14 mm2 THHN,
5 meters, 2 in. dia. IMC
MTS
150 AT
MCB
GENERATOR

150 AT RECTIFIER

ATS RECTIFIER
250 A

FUEL TANK
50 mm2 + 14 mm2 THHN U.G.,
17 meters, 2 in. dia. IMC

100 meters - 50 mm2 THHN AERIAL


8 meters - 50 mm2 THHN 1 1/2 in. dia. IMC

TRANSFORMER
37.5 KVA
CALATAGAN - LIAN HIGHWAY
DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR

698 S.L
LIAN

ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS

Existing AC Power Single Line Diagram

8 meters
50 mm2 THHN,
2 in. dia. IMC
TRANSFORMER
25 KVA 100 meters
38 mm2 THHN AERIAL CL200 M

ECB L1: 40.1


150 AT L2: 37.3
NEMA 3R V: 212
50 mm2 + 14 mm2 THHN U.G., (ALREADY DETERIORATED)
50 meters, 2 in. dia. IMC

50 mm2 + 14 mm2 THHN U.G.,


MCB 17 meters, 2 in. dia. IMC
150 AT
NEMA 3R
50 mm2 + 14 mm2 THHN ,
3 meters, 2 in. dia. IMC (ALREADY DETERIORATED)

N E
ATS
250 A G
NEMA 3R
L
50 mm2 + 14 mm2 THHN ,
4 meters, 2 in. dia. IMC

N E
MTS
SWITCH TYPE
L
50 mm2 + 14 mm2 THHN U.G.,
5 meters, 2 in. dia. IMC
ACPDB L1: 40.1
L2: 37.3
(Square D)

100AT,2P

70AT,3P 70AT,3P
ELTEK RECT 1A 1 2 ELTEK L1
50AT,3P 50AT,3P
ELTEK L2 3 4 ELTEK RECT 1B
40AT,3P 40AT,3P
NO LABEL 5 6 SPARE
40AT,2P 40AT,3P
SPARE 7 8 SPARE
30AT,2P 30AT,2P
NO LABEL 9 10 ACU 2
30AT,2P 30AT,2P
NO LABEL 11 12 ACU 1
20AT,2P 20AT,2P
LIGHTINGS 13 14 C.O.
DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR

698 S.L
LIAN

ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS

Proposed SLD

8 meters
50 mm2 THHN,
2 in. dia. IMC
TRANSFORMER
25 KVA 100 meters
50 mm2 THHN AERIAL CL200 M

ECB
150 AT
NEMA 3R
50 mm2 + 14 mm2 THHN U.G.,
50 meters, 2 in. dia. IMC

50 mm2 + 14 mm2 THHN U.G.,


MCB 17 meters, 2 in. dia. IMC
150 AT
NEMA 3R
50 mm2 + 14 mm2 THHN ,
3 meters, 2 in. dia. IMC

N E
ATS
250 A G
NEMA 3R
L 50 mm2 + 14 mm2 THHN
50 mm2 + 14 mm2 THHN , 2 meters, 2 in. dia. IMC
4 meters, 2 in. dia. IMC

N E
MTS MB
150 AT 150AT
NEMA 3R NEMA 3R
50 mm2 + 14 mm2 THHN U.G., L
5 meters, 2 in. dia. IMC
NEW ACPDB

150AT,2P

70AT,2P 70AT,2P
RECTIFIER #1 SUPPLY A 1 2 RECTIFIER #1 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #2 SUPPLY A 3 4 RECTIFIER #2 SUPPLY B
70AT,2P 70AT,2P
RECTIFIER #3 SUPPLY A 5 6 RECTIFIER #3 SUPPLY B
20AT,2P 20AT,2P
ACU 1
7 8 ACU 2
20AT,2P 20AT,2P
ACU 3 9 10 ACU ( FUTURE )
20AT,2P 20AT,2P
C.O. 11 12 LIGHTINGS
TOWER LIGHT
13 14 PERIMETER LIGHT
SPARE 15 16 SPARE
SPARE 15 16 SPARE