Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

Benefits:
Ÿ
Ÿ Microcontroller based, hence precise and accurate
Ÿ It measures load current – true RMS
Ÿ Over Voltage and Under Voltage cut-off for EB and DG(optional)
Ÿ Significant saving on wall space and wiring.
Ÿ In Single Phase ACCL during the event of change over from DG to EB the neutral is
first isolated, then the phase is isolated.
Ÿ Tropicalized and Rugged design.
Ÿ Three Phase DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE CHANGEOVER
CUM / WITH CURRENT LIMITER (ACCL) are enclosed in aesthetically made powder
coated sheet metal enclosures.
Ÿ Single Phase DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE CHANGEOVER
CUM / WITH CURRENT LIMITER (ACCL) are enclosed in ABS grade Thermo plastic
enclosure.
Ÿ LED indication of all operational status.
Ÿ Two line 16 Character LCD with Back-lit, Displays Voltage, Current and Frequency
(Three Phase). Mechanical inter-lock between 4 pole contactors in three phase
models.
Ÿ ACCL are provided with different ON-TIME delay, so that generators are not loaded
suddenly. This feature enhances the life of the generators and switchgear. Teflon
wires having very high insulations are used for the internal wiring.
Ÿ Wiring connections-using insulated feed trough terminal blocks for Three Phase
models.

www.prokdvs.com
Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE CHANGEOVER CUM / WITH CURRENT


LIMITER (ACCL)) For Single Phase and Three Phase Application

SPECIFICATIONS Single Phase ACCL Three Phase ACCL


EB Input 240V AC, 50 Hz 415V AC, 50 Hz, 3Ph 4W
DG Input 240V AC, 50 Hz 415V AC, 50 Hz, 3Ph 4W
LCD Display - 2 line 16 Character back-lit LCD
EB LED ON Load on EB Load on EB
DG LED ON Load on DG Load on DG
EB LED blinks(Optional) Over Load on EB -
DG LED blinks(Optional) Over Load on DG -
Trip LED ON Over Load Over Load
Trip LED Blinks Lock Out Mode -
Relay Contact Rating 240V AC, 30A Max Makings(tiRve
e)si -
Reset Manually Through RESET Switch on the unit Manually Through RESET Switch on the Unit

Specifications

SINGLE PHASE EB MAXIMUM DG MAXIMUM LOAD CURRENT DIMENSION


MODEL LOAD CURRENT MOUNTING (mm)
ACCL 1 PHASE EB 30 AMPS 0.5-20 AMPS USER DEFINED DIN 80 X 94 X 76
1PHASE EG FACTORY SET (Existing)
(in steps of 0.5 Amps) 80 X 95 X 75
(New)

THREE PHASE EB LOAD MAXIMUM PER PHASE DG LOAD MAXIMUM DIMENSION


MODELS AC1 DUTY CONTACTOR RATING PER PHASE MOUNTING (mm)
ACCL 0-20 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE 20 AMPS / PHASE USER DEFINED
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-25 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE USER DEFINED
25 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-32 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE USER DEFINED
32 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-40 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE USER DEFINED
40 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-63 AMPS/PHASE SURFACE 280X175X193
3 PHASE EB 4 WIRE USER DEFINED
63 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-20 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE USER DEFINED
20 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-25 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE USER DEFINED
25 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-32 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE USER DEFINED
32 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-40 AMPS/PHASE SURFACE 153X137X200
3 PHASE EB 4 WIRE USER DEFINED
40 AMPS / PHASE
3 PHASE DG 4 WIRE FACTORY SET
ACCL 0-63 AMPS/PHASE SURFACE 280X175X193
3 PHASE EB 4 WIRE 63 AMPS / PHASE USER DEFINED
3 PHASE DG 4 WIRE FACTORY SET

www.prokdvs.com
Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

All the 3 phase models will display the main voltages of 3 Voltages, 3 Currents and
Frequency in EB and DG present through the LCD and trip indication through LED.

Optional:

1) In ACCL 3 phase 4 wire EB and single phase DG ACCL can be tailored to the customer
specification like current setting on the ACCL DG as arithmetic/ cumulative sum of
currents.
2) The 3 Phase ACCL with field selectable 50% - 100% of load current on DG is optional.
3) Only ACCL logic can supplied for current rating 70 Amps and above i.e. without
contactors, Bus Bars and CT's
4) EB Current limiting is provided as per the customer requirement (as an optional feature).

ACCL ORDERING INFORMATION:

Specify: 1) Single Phase/ Three phase


2) Current rating on EB & DG
3) Individual Phase Current/Arithmetic sum of phase currents( 3 Ph. ACCL)
4) Over/Under Voltage Limits(Optional)
` 5) Duration and Number of ON/OFF Cycles
Current setting cannot be Greater than the Contactor rating

www.prokdvs.com
Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

Features
Ÿ While monitoring the Generator supply, Allows only limited load and functions as load
limiter as per desired current.
Ÿ Current sealing while monitoring the DG and EB will be factory-Set.(Field selectable
Model-Optional)
Ÿ Whenever the load current exceeds the preset limit, power is automatically switched-
off and resets after 9sec and trips again if the overload exists, this cycle is ( 3Sec ON &
6Sec OFF) is repeated every nine seconds. If overloading on DG persists the ACCL
enters lock out mode after 5 ON & OFF cycles. The unit can be reset manually by
reset switch. However tailor made units i.e field adaptable as per customer
requirement can be provided as it is a microcontroller based.
Ÿ Display of each Phase Voltage, Current and Frequency in Three Phase ACCL by 2 line
16 character LCD.
Ÿ Over Voltage and Under Voltage cut-off limit for both EB and DG and is optional
Ÿ On the resumption of the EB main supply, ACCL changes over from DG to EB and
allows the full load current.
Ÿ

PROK DV'S DIGITAL MICROCONTROLLER BASED


AUTOMATIC SOURCE CHANGEOVER CUM / WITH
CURRENT LIMITER (ACCL)
S P E C IF IC A T IO N S S IN G L E P H A S E A C C L TH REE PH A SE ACCL
T e c h n o lo g y M ic ro p r o c e s s o r B a s e d . H e n c e M ic ro p r o c e s s o r B a s e d . H e n c e
p r e c is e m e a s u r e m e n t p r e c is e m e a s u r e m e n t
Fre q u e n cy 50Hz 50Hz
D is p la y L E D in d ic a t io n s t a t u s 2 L in e 1 6 c h a r a c t e r L C D d is p la y
L E D In d ic a t io n s fo r D G P re s e n c e , E B
D is p la y o f O v e r lo a d e d p h a s e
D is p la y o f U V t r ip & O V t r ip
T r ip T im e a n d O F F t im e T r ip t im e O N - 3 S e c T r ip t im e O n - 3 S e c
O F F T im e - 6 S e c O F F T im e - 6 S e c
F iv e O N & O F F C y c le s F iv e O N & O F F C y c le s
(o t h e r t im in g s a n d c y c le s c a n b e (o t h e r t im in g s a n d c y c le s c a n b e
p r o v id e d a s p e r t h e c u s t o m e r p r o v id e d a s p e r t h e c u s t o m e r
r e q u ir e m e n t ) r e q u ir e m e n t )
O u t P u t C o n ta ct T y p e E le c t ro m e c h a n ic a l R e la y 4 P o le C o n t a c t o r s
P r o t e c t io n fo r C h a n g e O v e r B r e a k N e u t r a l b e fo r e b r e a k in g t h e 4 P o le C o n t a c to r s
P h ase
E B M a x . L o a d C u r re n t 30A 20Am p, 25Am p, 32Am p, 40Am p
and 63Am p.
A b o v e 6 3 A m p o n ly lo g ic s h a ll b e
p r o v id e d .
D G C u r re n t R a n g e ( F a c to ry S e t) 0 .5 A to 2 0 A F a c to r y S e t 0 -2 0 A , 0 -2 5 A , 0 -3 2 A , 0 -4 0 A ,a n d
In s t e p s o f 0 .5 A m p 0 -6 3 A D e p e n d in g o n t h e M o d e l in
s t e p s o f 0 .5 A m p
U n d e r a n d O v e r V o lt a g e p ro t e c t io n U V 1 6 0 V -2 0 0 V F a c t o ry S e t U V 1 6 0 V -2 0 0 V F a c t o ry S e t
O V 2 5 0 V -2 8 0 V F a c t o ry s e t O V 2 5 0 V -2 8 0 V F a c t o ry s e t
( C a n b e p ro v id e d a s a n o p tio n a l ( C a n b e p ro v id e d a s a n o p tio n a l
fe a t u r e ) fe a t u r e )
M o d e ls 1 p h a se E B & 1 p h a se D G 3 P h a se E B & 3 P h ase D G
3 P h a se E B & 1 P h a se D G
(O p t io n o f s u m m a t io n c u r re n t a ls o
a v a ila b le )
P ro d u ct g u a ra n te e Fo r 1 8 M o n th s Fo r 1 8 M o n th s
E B C u r r e n t lim it in g E B C u r r e n t L im it in g is a v a ila b le a s E B C u r r e n t lim it in g is a v a ila b le a s
p e r C lie n t s r e q u e s t( A s o p t io n a l ) p e r C lie n t re q u e s t (A s o p t io n a l)
E n c lo s u r e A B S G r a d e t h e r m o p la s t ic P o w d e r co ate d sh e e t m e tal
e n c lo s u r e
M o u n t in g D IN SU RFACE
D im e n s io n s (m m ) 7 0 X 1 0 5 X 6 0 (E x is t in g ) 1 5 3 X 1 3 7 X 2 0 0 ( U p to 4 0 A )
80 X 95 X 75 (N e w ) 2 8 0 X 1 7 5 X 1 9 3 ( U p to 6 3 A )

www.prokdvs.com
Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

MECHANICAL DIMENSION OF SINGLE PHASE DIGITAL


MICROCONTROLLER BASED AUTOMATIC SOURCE
CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

Existing Model New Model

MECHANICAL DIMENSION OF THREE PHASE DIGITAL


MICROCONTROLLER BASED AUTOMATIC SOURCE
CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL) –
(63Amps)

www.prokdvs.com
Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

MECHANICAL DIMENSION OF THREE PHASE DIGITAL


MICROCONTROLLER BASED AUTOMATIC SOURCE
CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL) –
(40Amps)

WIRING DIAGRAM FOR THREE PHASE DIGITAL


MICROCONTROLLER BASED AUTOMATIC SOURCE
CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

www.prokdvs.com
Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

WIRING DIAGRAM FOR SINGLE PHASE DIGITAL


MICROCONTROLLER BASED AUTOMATIC SOURCE
CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

WIRING DIAGRAM FOR THREE PHASE AUTOMATIC


SOURCE CHANGEOVER CUM / WITH CURRENT LIMITER

ACCL- LOGIC

www.prokdvs.com
Change Over with
Current Limiter
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER BASED AUTOMATIC SOURCE
Auto Source

CHANGEOVER CUM / WITH CURRENT LIMITER (ACCL)

ISO 9001-2008

Prok Devices Private Limited


SIMHADRI ,No.2930, 14 th Cross,
Banashankari II nd Stage, Off K.R. Road,
Bengaluru-560070