GEN SET(TEST REPORT)

COSTUMER CONCRETE STONE CORP.

ADDRESS RODRIGUEZ, RIZAL MONTALBAN

UNIT - DATE TESTED Sept 03,2020


RATING 800 kW NO. OF SLOTS -
VOLTAGE 440 SIZE OF WIRE -
AMPS - COIL PITCH -
RPM/POLES - WIEGHT -
PHASE 3 BEARINGS 6317C3
MAKE/MADE - SERIAL NO. -
DATE MFD. - DATE PICK-UP -

TEST DONE

I. INSULATION RESISTANCE TEST


STATOR WINDING VOLTAGE SETTING INSULATION RESULT
1min 10min P.I.
LINE – GROUND 500
1.26 MΩ 1.48 MΩ 1.18
Equipment Used INSULATION TESTER, KYORITSU, MODEL 3125
Remarks PASSED but RESULT is close to the minimum passing value

II. WINDING RESISTANCE TEST


DLRO (ROTOR EXCITER)
L1 – L2 L1-L3 L2-L3
TEST VALUE 163.7 mΩ 159.6 mΩ 164.2 mΩ
MAIN STATOR
L1 – L2 L1-L3 L2-L3
TEST VALUE 5.878 mΩ 5.769 mΩ 5.741 mΩ
L1 – G L2-G L3-G
TEST VALUE 2.949 mΩ 2.912 mΩ 2.836 mΩ
STATOR EXCITER
L1-L2
TEST VALUE 1.609 Ω
MAIN ROTOR
L1-L2
TEST VALUE 22.03 Ω
Equipment USE WINDING RESISTANCE METER (BRAND TELDAR MODEL TRM-10P)
Remark PASSED

TEST CONDUCTED BY: APPROVED BY:

NORVEN LEBRILLA
EIS Inc. TECHNICIAN
DATE: SEPT 03,2020