CUSTOMER: Lautan Luas Inc.

ATS TYPE: Unigear


PROJECT: Y-Building
S.O. NUMBER: 21-KCE-096
#82 Cordillera St., Corner Quezon Ave., Quezon City Ph. DATE: 5/19/21
Tel. Nos.: 781-0071, 781-0102 to 12 Fax No. 711-5115 EQUIPMENT LOCATION: EE Room 10th Floor
Email Address: tech_support@kcic.com.ph EQUIPMENT NAME: ATS-800 (MC-6)
ATS TESTING
THERMAL REPORT
PANEL NAME THERMAL FILE NUMBER REMARKS
ATS-800 (MC-6) IR009416 & IR009415 THERE WERE NO SIGNS OF HOTSPOT
TEST EQUIPMENT: FLUKE THERMAL SCANNER SERIAL NUMBER: 14060112
MODEL NUMBER: TiL25
COMMON BUSBAR INSULATION RESISTANCE TEST
APPLIED CIRCUIT TIME TEST VOLTAGE RESULT (NORMAL & EMERGENCY) REMARKS
PHASE A-B 1 MINUTE 1000 VDC 1.3 GΩ 3.1 GΩ PASSED
PHASE B-C 1 MINUTE 1000 VDC 1.2 GΩ 3.0 GΩ PASSED
PHASE C-A 1 MINUTE 1000 VDC 1.3 GΩ 3.7 GΩ PASSED
PHASE A-G 1 MINUTE 1000 VDC 1.5 GΩ 1.9 GΩ PASSED
PHASE B-G 1 MINUTE 1000 VDC 1.3 GΩ 3.0 GΩ PASSED
PHASE C-G 1 MINUTE 1000 VDC 1.4 GΩ 3.3 GΩ PASSED
PHASE A-N 1 MINUTE 1000 VDC 1.5 GΩ 1.9 GΩ PASSED
PHASE B-N 1 MINUTE 1000 VDC 1.3 GΩ 3.0 GΩ PASSED
PHASE C-N 1 MINUTE 1000 VDC 1.4 GΩ 3.3 GΩ PASSED
PHASE N-G 1 MINUTE 1000 VDC BONDED
TEST EQUIPMENT: INSULATION RESISTANCE TESTER SERIAL NUMBER: 101791210
MODEL NUMBER: MIT1525
ATS FUNCTIONALITY TEST
ITEM NO. DESCRIPTION CONFORME REMARKS
YES NO
1
Test automatic transfer switch for electrical operation ✔ PASSED
2 Test automatic transfer switch for manual operation ✔ PASSED

3 Test all electrical circuits and components if functional ✔ PASSED

4 Check for voltage input/output phase rotation ✔ PASSED


Conduct voltage measurements on line-to-line and line-to-ground
5 circuit for both normal and emergency power ✔ PASSED

Check for bolted connection if properly tightened using torque


6 wrench, and torque mark after checking bolt tightness ✔ PASSED

VOLTAGE READING
NORMAL BREAKER EMERGENCY BREAKER
A-B: 393 V A-G: 228 V A-B: 393 V A-G: 228 V
B-C: 399 V B-G: 228 V B-C: 400 V B-G: 227 V
C-A: 400 V C-G: 231 V C-A: 398 V C-G: 231 V
A-N: 228 V C-N: 231 V A-N: 228 V C-N: 231 V
B-N: 228 V N-G: 0 B-N: 227 V N-G: 0

EVALUATION AND REMARKS:


TESTED BY: K.OCAY /W. TUMULAK / A. MALAPIT /J. MASANQUE
WITNESSED BY:_______________________________
ATS IN GOOD CONDITION & LEFT IN "AUTO MODE"
NOTED BY:___________________________________
GΩ CUSTOMER: Lautan Luas Inc.
ATS TYPE: Unigear
PROJECT: Y-Building
S.O. NUMBER: 21-KCE-096
#82 Cordillera St., Corner Quezon Ave., Quezon City Ph. DATE: 5/19/21
Tel. Nos.: 781-0071, 781-0102 to 12 Fax No. 711-5115 EQUIPMENT LOCATION: EE Room 16th Floor
Email Address: tech_support@kcic.com.ph EQUIPMENT NAME: ATS-800 (MC-9)
ATS TESTING
THERMAL REPORT
PANEL NAME THERMAL FILE NUMBER REMARKS
ATS-800 (MC-6) IR009418 & IR009419 THERE WERE NO SIGNS OF HOTSPOT
TEST EQUIPMENT: FLUKE THERMAL SCANNER SERIAL NUMBER: 14060112
MODEL NUMBER: TiL25
COMMON BUSBAR INSULATION RESISTANCE TEST
APPLIED CIRCUIT TIME TEST VOLTAGE RESULT (NORMAL & EMERGENCY) REMARKS
PHASE A-B 1 MINUTE 1000 VDC 4.17 GΩ 3.74 GΩ PASSED
PHASE B-C 1 MINUTE 1000 VDC 4.34 GΩ 4.07 GΩ PASSED
PHASE C-A 1 MINUTE 1000 VDC 4.02 GΩ 3.98 GΩ PASSED
PHASE A-G 1 MINUTE 1000 VDC 3.46 GΩ 2.78 GΩ PASSED
PHASE B-G 1 MINUTE 1000 VDC 3.81 GΩ 3.84 GΩ PASSED
PHASE C-G 1 MINUTE 1000 VDC 3.45 GΩ 4.15 GΩ PASSED
PHASE A-N 1 MINUTE 1000 VDC 3.46 GΩ 2.78 GΩ PASSED
PHASE B-N 1 MINUTE 1000 VDC 3.81 GΩ 3.84 GΩ PASSED
PHASE C-N 1 MINUTE 1000 VDC 3.45 GΩ 4.15 GΩ PASSED
PHASE N-G 1 MINUTE 1000 VDC BONDED
TEST EQUIPMENT: INSULATION RESISTANCE TESTER SERIAL NUMBER: 101791210
MODEL NUMBER: MIT1525
ATS FUNCTIONALITY TEST
ITEM NO. DESCRIPTION CONFORME REMARKS
YES NO
1
Test automatic transfer switch for electrical operation ✔ PASSED
2 Test automatic transfer switch for manual operation ✔ PASSED

3 Test all electrical circuits and components if functional ✔ PASSED

4 Check for voltage input/output phase rotation ✔ PASSED


Conduct voltage measurements on line-to-line and line-to-ground
5 circuit for both normal and emergency power ✔ PASSED

Check for bolted connection if properly tightened using torque


6 wrench, and torque mark after checking bolt tightness ✔ PASSED

VOLTAGE READING
NORMAL BREAKER EMERGENCY BREAKER
A-B: 397 V A-G: 231 V A-B: 397 V A-G: 231 V
B-C: 404 V B-G: 230 V B-C: 403 V B-G: 230 V
C-A: 405 V C-G: 234 V C-A: 404 V C-G: 234 V
A-N: 231 V C-N: 234 V A-N: 231 V C-N: 234 V
B-N: 230 V N-G: 0 B-N: 230 V N-G: 0

EVALUATION AND REMARKS:


TESTED BY: K.OCAY /W. TUMULAK / A. MALAPIT /J. MASANQUE
WITNESSED BY:_______________________________
ATS IN GOOD CONDITION & LEFT IN "AUTO MODE"
NOTED BY:___________________________________
GΩ CUSTOMER: Lautan Luas Inc.
ATS TYPE: Unigear
PROJECT: Y-Building
S.O. NUMBER: 21-KCE-096
#82 Cordillera St., Corner Quezon Ave., Quezon City Ph. DATE: 5/19/21
Tel. Nos.: 781-0071, 781-0102 to 12 Fax No. 711-5115 EQUIPMENT LOCATION: EE Room 7th Floor
Email Address: tech_support@kcic.com.ph EQUIPMENT NAME: ATS-800 (MC-7)
ATS TESTING
THERMAL REPORT
PANEL NAME THERMAL FILE NUMBER REMARKS
ATS-800 (MC-6) IR009405 & IR009406 THERE WERE NO SIGNS OF HOTSPOT
TEST EQUIPMENT: FLUKE THERMAL SCANNER SERIAL NUMBER: 14060112
MODEL NUMBER: TiL25
COMMON BUSBAR INSULATION RESISTANCE TEST
APPLIED CIRCUIT TIME TEST VOLTAGE RESULT (NORMAL & EMERGENCY) REMARKS
PHASE A-B 1 MINUTE 1000 VDC 2.32 GΩ 4.74 GΩ PASSED
PHASE B-C 1 MINUTE 1000 VDC 3.47 GΩ 3.73 GΩ PASSED
PHASE C-A 1 MINUTE 1000 VDC 4.63 GΩ 5.93 GΩ PASSED
PHASE A-G 1 MINUTE 1000 VDC 3.31 GΩ 3.46 GΩ PASSED
PHASE B-G 1 MINUTE 1000 VDC 3.55 GΩ 5.19 GΩ PASSED
PHASE C-G 1 MINUTE 1000 VDC 3.74 GΩ 5.57 GΩ PASSED
PHASE A-N 1 MINUTE 1000 VDC 3.31 GΩ 3.46 GΩ PASSED
PHASE B-N 1 MINUTE 1000 VDC 3.55 GΩ 3.19 GΩ PASSED
PHASE C-N 1 MINUTE 1000 VDC 3.74 GΩ 5.57 GΩ PASSED
PHASE N-G 1 MINUTE 1000 VDC BONDED
TEST EQUIPMENT: INSULATION RESISTANCE TESTER SERIAL NUMBER: 101791210
MODEL NUMBER: MIT1525
ATS FUNCTIONALITY TEST
ITEM NO. DESCRIPTION CONFORME REMARKS
YES NO
1 *FOR RETESTING OF ATS DUE TO
Test automatic transfer switch for electrical operation ✔ DEFECTIVE ITEM
2 Test automatic transfer switch for manual operation ✔ PASSED
*DAMAGED SELECTOR SWITCH AND
3 Test all electrical circuits and components if functional ✔ HUMMING CONTACTOR

4 Check for voltage input/output phase rotation ✔ PASSED


Conduct voltage measurements on line-to-line and line-to-ground
5 circuit for both normal and emergency power ✔ PASSED

Check for bolted connection if properly tightened using torque


6 wrench, and torque mark after checking bolt tightness ✔ PASSED

VOLTAGE READING
NORMAL BREAKER EMERGENCY BREAKER
A-B: 393 V A-G: 228 V A-B: 393 V A-G: 228 V
B-C: 399 V B-G: 227 V B-C: 398 V B-G: 227 V
C-A: 400 V C-G: 231 V C-A: 400 V C-G: 231 V
A-N: 228 V C-N: 231 V A-N: 228 V C-N: 231 V
B-N: 231 V N-G: 0 B-N: 227 V N-G: 0

EVALUATION AND REMARKS:


TESTED BY: K.OCAY /W. TUMULAK / A. MALAPIT /J. MASANQUE *1 PC SELECTOR SWITCH (3 POS) W/ 2- NO CONTACTS- FOR REPLACEMENT
WITNESSED BY:_______________________________ *2 UNITS FUJI CONTACTOR SC-05 W/ INTERLOCK SZ-RM - FOR REPLACEMENT
NOTED BY:___________________________________ *ATS DID NOT FUNCTION IN AUTO DUE TO DEFECTIVE ITEMS
GΩ CUSTOMER: Lautan Luas Inc.
ATS TYPE: Unigear
PROJECT: Y-Building
S.O. NUMBER: 21-KCE-096
#82 Cordillera St., Corner Quezon Ave., Quezon City Ph. DATE: 5/19/21
Tel. Nos.: 781-0071, 781-0102 to 12 Fax No. 711-5115 EQUIPMENT LOCATION: EE Room 8th Floor
Email Address: tech_support@kcic.com.ph EQUIPMENT NAME: ATS-800 (MC-5)
ATS TESTING
THERMAL REPORT
PANEL NAME THERMAL FILE NUMBER REMARKS
ATS-800 (MC-6) IR009412 & IR009413 THERE WERE NO SIGNS OF HOTSPOT
TEST EQUIPMENT: FLUKE THERMAL SCANNER SERIAL NUMBER: 14060112
MODEL NUMBER: TiL25
COMMON BUSBAR INSULATION RESISTANCE TEST
APPLIED CIRCUIT TIME TEST VOLTAGE RESULT (NORMAL & EMERGENCY) REMARKS
PHASE A-B 1 MINUTE 1000 VDC 1.42 GΩ 2.02 GΩ PASSED
PHASE B-C 1 MINUTE 1000 VDC 1.49 GΩ 1.9 GΩ PASSED
PHASE C-A 1 MINUTE 1000 VDC 1.47 GΩ 1.7 GΩ PASSED
PHASE A-G 1 MINUTE 1000 VDC 934 MΩ 1.8 GΩ PASSED
PHASE B-G 1 MINUTE 1000 VDC 991 MΩ 1.2 GΩ PASSED
PHASE C-G 1 MINUTE 1000 VDC 965 MΩ 1.6 GΩ PASSED
PHASE A-N 1 MINUTE 1000 VDC 934 MΩ 1.8 GΩ PASSED
PHASE B-N 1 MINUTE 1000 VDC 991 MΩ 1.2 GΩ PASSED
PHASE C-N 1 MINUTE 1000 VDC 965 MΩ 1.6 GΩ PASSED
PHASE N-G 1 MINUTE 1000 VDC BONDED
TEST EQUIPMENT: INSULATION RESISTANCE TESTER SERIAL NUMBER: 101791210
MODEL NUMBER: MIT1525
ATS FUNCTIONALITY TEST
ITEM NO. DESCRIPTION CONFORME REMARKS
YES NO
1 *FOR RETESTING OF ATS DUE TO
Test automatic transfer switch for electrical operation ✔ DEFECTIVE ITEM
2 Test automatic transfer switch for manual operation ✔ PASSED

3 Test all electrical circuits and components if functional ✔ *DAMAGED 1 UVR CHINT 400 V

4 Check for voltage input/output phase rotation ✔ PASSED


Conduct voltage measurements on line-to-line and line-to-ground
5 circuit for both normal and emergency power ✔ PASSED

Check for bolted connection if properly tightened using torque


6 wrench, and torque mark after checking bolt tightness ✔ PASSED

VOLTAGE READING
NORMAL BREAKER EMERGENCY BREAKER
A-B: 395 V A-G: 230 V A-B: 396 V A-G: 230 V
B-C: 401 V B-G: 229 V B-C: 401 V B-G: 229 V
C-A: 402 V C-G: 232 V C-A: 404 V C-G: 232 V
A-N: 230 V C-N: 232 V A-N: 230 V C-N: 232 V
B-N: 229 V N-G: 0 B-N: 229 V N-G: 0

EVALUATION AND REMARKS:


TESTED BY: K.OCAY /W. TUMULAK / A. MALAPIT /J. MASANQUE *FOR REPLACEMENT OF 1 UNIT (CHINT UVR 400 SYSTEM)
WITNESSED BY:_______________________________ *ATS UNIGEAR MISALIGNED BUT FIXED ON SITE.
NOTED BY:___________________________________ ATS TRANSFERRING AUTOMATICALLY JUST TO REPLACE UVR
GΩ CUSTOMER: Lautan Luas Inc.
ATS TYPE: Unigear
PROJECT: Y-Building
S.O. NUMBER: 21-KCE-096
#82 Cordillera St., Corner Quezon Ave., Quezon City Ph. DATE: 5/19/21
Tel. Nos.: 781-0071, 781-0102 to 12 Fax No. 711-5115 EQUIPMENT LOCATION: EE Room Floor
Email Address: tech_support@kcic.com.ph EQUIPMENT NAME: ATS-800 (MC-8)
ATS TESTING
THERMAL REPORT
PANEL NAME THERMAL FILE NUMBER REMARKS
ATS-800 (MC-6) IR009402 & IR009403 THERE WERE NO SIGNS OF HOTSPOT
TEST EQUIPMENT: FLUKE THERMAL SCANNER SERIAL NUMBER: 14060112
MODEL NUMBER: TiL25
COMMON BUSBAR INSULATION RESISTANCE TEST
APPLIED CIRCUIT TIME TEST VOLTAGE RESULT (NORMAL & EMERGENCY) REMARKS
PHASE A-B 1 MINUTE 1000 VDC 3.72 GΩ 3.15 GΩ PASSED
PHASE B-C 1 MINUTE 1000 VDC 3.88 GΩ 3.09 GΩ PASSED
PHASE C-A 1 MINUTE 1000 VDC 3.80 GΩ 3.05 GΩ PASSED
PHASE A-G 1 MINUTE 1000 VDC 3.01 GΩ 3.03 GΩ PASSED
PHASE B-G 1 MINUTE 1000 VDC 3.23 GΩ 3.09 GΩ PASSED
PHASE C-G 1 MINUTE 1000 VDC 3.09 GΩ 3.12 GΩ PASSED
PHASE A-N 1 MINUTE 1000 VDC 3.37 GΩ 3.37 GΩ PASSED
PHASE B-N 1 MINUTE 1000 VDC 3.04 GΩ 3.04 PASSED
PHASE C-N 1 MINUTE 1000 VDC 3.40 GΩ 3.40 GΩ PASSED
PHASE N-G 1 MINUTE 1000 VDC BONDED
TEST EQUIPMENT: INSULATION RESISTANCE TESTER SERIAL NUMBER: 101791210
MODEL NUMBER: MIT1525
ATS FUNCTIONALITY TEST
ITEM NO. DESCRIPTION CONFORME REMARKS
YES NO
1 *FOR RETESTING OF ATS DUE TO
Test automatic transfer switch for electrical operation ✔ DEFECTIVE ITEM
2 Test automatic transfer switch for manual operation ✔ PASSED
*HUMMING OF CONTACTOR 2-UNIT
3 Test all electrical circuits and components if functional ✔ SC-05W/ AUX BLOCK SZ-RM

4 Check for voltage input/output phase rotation ✔ PASSED


Conduct voltage measurements on line-to-line and line-to-ground
5 circuit for both normal and emergency power ✔ PASSED

Check for bolted connection if properly tightened using torque


6 wrench, and torque mark after checking bolt tightness ✔ PASSED

VOLTAGE READING
NORMAL BREAKER EMERGENCY BREAKER
A-B: 395 V A-G: 230 V A-B: 396 V A-G: 230 V
B-C: 401 V B-G: 229 V B-C: 401 V B-G: 229 V
C-A: 402 V C-G: 232 V C-A: 404 V C-G: 232 V
A-N: 230 V C-N: 232 V A-N: 230 V C-N: 232 V
B-N: 229 V N-G: 0 B-N: 229 V N-G: 0

EVALUATION AND REMARKS:


TESTED BY: K.OCAY /W. TUMULAK / A. MALAPIT /J. MASANQUE *2 UNITS FUJI CONTACTOR SC-05 W/ INTERLOCK SZ-RM - FOR REPLACEMENT
WITNESSED BY:_______________________________
NOTED BY:___________________________________ *ATS DID NOT FUNCTION IN AUTO DUE TO DEFECTIVE ITEMS
GΩ CUSTOMER: Lautan Luas Inc.
ATS TYPE: Unigear
PROJECT: Y-Building
S.O. NUMBER: 21-KCE-096
#82 Cordillera St., Corner Quezon Ave., Quezon City Ph. DATE: 5/19/21
Tel. Nos.: 781-0071, 781-0102 to 12 Fax No. 711-5115 EQUIPMENT LOCATION: EE Room 18th Floor
Email Address: tech_support@kcic.com.ph EQUIPMENT NAME: ATS-800 (MC-8)
ATS TESTING
THERMAL REPORT
PANEL NAME THERMAL FILE NUMBER REMARKS
ATS-800 (MC-6) IR009409 & IR009410 THERE WERE NO SIGNS OF HOTSPOT
TEST EQUIPMENT: FLUKE THERMAL SCANNER SERIAL NUMBER: 14060112
MODEL NUMBER: TiL25
COMMON BUSBAR INSULATION RESISTANCE TEST
APPLIED CIRCUIT TIME TEST VOLTAGE RESULT (NORMAL & EMERGENCY) REMARKS
PHASE A-B 1 MINUTE 1000 VDC 2.02 GΩ 2.68 GΩ PASSED
PHASE B-C 1 MINUTE 1000 VDC 2.59 GΩ 2.98 GΩ PASSED
PHASE C-A 1 MINUTE 1000 VDC 2.61 GΩ 3.45 GΩ PASSED
PHASE A-G 1 MINUTE 1000 VDC 2.26 GΩ 2.33 GΩ PASSED
PHASE B-G 1 MINUTE 1000 VDC 2.01 GΩ 3.44 GΩ PASSED
PHASE C-G 1 MINUTE 1000 VDC 2.20 GΩ 3.91 GΩ PASSED
PHASE A-N 1 MINUTE 1000 VDC 2.26 GΩ 2.33 GΩ PASSED
PHASE B-N 1 MINUTE 1000 VDC 2.01 GΩ 3.44 GΩ PASSED
PHASE C-N 1 MINUTE 1000 VDC 2.20 GΩ 3.91 GΩ PASSED
PHASE N-G 1 MINUTE 1000 VDC BONDED
TEST EQUIPMENT: INSULATION RESISTANCE TESTER SERIAL NUMBER: 101791210
MODEL NUMBER: MIT1525
ATS FUNCTIONALITY TEST
ITEM NO. DESCRIPTION CONFORME REMARKS
YES NO
1 PASSED
Test automatic transfer switch for electrical operation ✔
2 Test automatic transfer switch for manual operation ✔ PASSED

3 Test all electrical circuits and components if functional PASSED



4 Check for voltage input/output phase rotation ✔ PASSED
Conduct voltage measurements on line-to-line and line-to-ground
5 circuit for both normal and emergency power ✔ PASSED

Check for bolted connection if properly tightened using torque


6 wrench, and torque mark after checking bolt tightness ✔ PASSED

VOLTAGE READING
NORMAL BREAKER EMERGENCY BREAKER
A-B: 394 V A-G: 228 V A-B: 394 V A-G: 228 V
B-C: 399 V B-G: 227 V B-C: 398 V B-G: 227 V
C-A: 400 V C-G: 231 V C-A: 400 V C-G: 231 V
A-N: 228 V C-N: 231 V A-N: 228 V C-N: 231 V
B-N: 227 V N-G: 0 B-N: 227 V N-G: 0

EVALUATION AND REMARKS:


TESTED BY: K.OCAY /W. TUMULAK / A. MALAPIT /J. MASANQUE
WITNESSED BY:_______________________________
ATS IN GOOD CONDITION & LEFT IN "AUTO MODE"
NOTED BY:___________________________________