PLUMBING AND SANITARY SYSTEM QC-MEPF-015A-DU
(PRIOR TO TOG/QMD/UNIT OWNER ACCEPTANCE)
Project : Ref. No. :
Building : Time of Request :
Unit/Level : Date of Request :
Location :
Subcontractor :
12. Others
C. Toilet and Bath 2
Check hand holes if P-traps above (Shower Drain, Floor Drain and Washing Machine
10. P-Traps Above Ceiling Drain) are accessible. Double check if debris inside P-traps were removed. P-trap caps
must be properly returned.
a. Flow Test of Pour 2 pails of water each for Shower drain, Floor Drain, Floor Clean-out and Washing
T&B Above Machine drain above the unit you are dressing.
Ensure that the gully trap is free from any solid waste, and free from excess application of
11. Gully Ttrap waterproofing. Check inside the gully trap if the baffle is inserted properly. Rubber seal in
the baffle must be attached and fitted properly.
Pour 2 pails of water (16L/pail)
a. Flow Test of T&B above
b. Accessories Install complete accessories: odor trap, gasket, strainer, floor drain
12. Others
D. Bedroom 1
1. Balcony drain 1 Pour 2 pails of water (16L/pail)
2. Balcony drain 2 Pour 2 pails of water (16L/pail)
3. FCU/ACU Stubout 1 Pour 1 bottle of water (1.5L/btl) using funnel with clear hose (1/4"-3/8" dia)
4. FCU/ACU Stubout 2 Pour 1 bottle of water (1.5L/btl) using funnel with clear hose (1/4"-3/8" dia)
5. Others
E. Bedroom 2
1. Balcony drain 1 Pour 2 pails of water (16L/pail)
2. Balcony drain 2 Pour 2 pails of water (16L/pail)
3. FCU/ACU Stubout 1 Pour 1 bottle of water (1.5L/btl) using funnel with clear hose (1/4"-3/8" dia)
4. FCU/ACU Stubout 2 Pour 1 bottle of water (1.5L/btl) using funnel with clear hose (1/4"-3/8" dia)
5. Others
Serial No.: Check if water meter is functioning correctly. Check all
F. Water Meter Initial Reading : joints/connections if there are traces of leaks. Check if
the water meter cover is intact.
G. Gate Valve Check if gate valve is passing. Open the faucet & close the gate valve, if water is still
flowing the gate valve is defective.