You are on page 1of 2

FUJI-HAYA ELECTRIC CORP.

1/2

FACTORY TEST REPORT

TEST REPORT NO. : 33540 PANEL DESIGNATION: MVSG-LBS


DATE TESTED: JULY 2016 QUANTITY: 1 ASSY
CUSTOMER: JFA ELECTRICAL MAIN CIRCUIT VOLTAGE : 13.8KV 3PH 3W 60HZ
PROJECT: CONTROL CIRCUIT VOLTAGE: N/A
SALES ORDER NO: 0852 APPLICABLE STANDARD: ds
ITEM NO 01 QA SERIAL NUMBER: W1525-01
PRODUCT LINE: MEDIUM VOLTAGE SWITCHGEAR

I. CONSTRUCTION CHECK SATISFACTORY

1. Visual inspection of MEDIUM VOLTAGESWITCHGEAR


arrangement and assembly condition.
2. Measurement of outline dimension.
3. Visual inspection of painting color and
surface final condition.
4. Visual inspection of fitting apparatus and
material inspection.
5. Inspection of nameplates and rating panel and apparatus.

II. ELECTRICAL OPERATION TEST SATISFACTORY

1. Check the sequential operation test of control circuits in accordance


with the schematic diagram and the operation test of control circuits
at rated control voltage.

III. MECHANICAL OPERATION TEST SATISFACTORY

IV. PHASE SEQUENCE CHECK OF MAIN CIRCUITS SATISFACTORY

V. POTENTIAL AND CURRENT CIRCUITS TEST

1. Primary and Secondary injection test of potential circuits. SATISFACTORY

2. Secondary injection test of current circuits. NOT APPLICABLE


2/2

TEST REPORT NO. : 33540

CUSTOMER: JFA ELECTRICAL

PROJECT:

VI. MEASUREMENT OF INSULATION RESISTANCE AND SATISFACTORY


POWER FREQUENCY TEST RESULT.

6.1) Shop Test Date 8/22/2015

TEMPERATURE: 29 CELSIUS
HUMIDITY: 77 %
6.2) Witness Test Date

TEMPERATURE: CELSIUS
HUMIDITY: %

APPLIED CIRCUITS SHOP TEST (MOHMS) WITNESS TEST (MOHMS) Applied Voltage @ 1
minute
BEFORE AFTER BEFORE AFTER

1. PHASE R,S,T,(N) - G - - - - 32kV

2. PHASE R - S,T,(N),G 11G 11G - -

3. PHASE S - R,T,(N),G 11G 11G - -

4. PHASE T - R,S,(N),G 11G 11G - -

5. CONTROL CIRCUIT - - - - -

Witnessed by:
Tested by:

AL MARASIGAN

Approved by:

EDGARDO A. ALBO