You are on page 1of 5

Alternator IR Test Sheet

26071 V67 331 A 105 GEN1 00074_Attachment #7

Project: RDMP Project Client: PT PERTAMINA


(Persero)
Project No.: 26071-203-PO-MGED-00067 Job No: 26071 Date: 08 Agustus 2022
System: Report No.:
Sub-system: Drawing/Area Ref:
Contractor: Equipment No.: EDG-B
Station Reference: Rated Current: 218.7
Alternator Model: HVSI804W2 Connection Type: STAR
Sr. No. C20G310080 Frequency: 50 HZ
Rated Power: 2000 kW/2500 kVA Power Factor: 0.8
Rated Voltage: 6600 V

INSULATION RESISTANCE
TEST EQUIPMENT USED:
Insulation
Voltage Resistance Standard
Sr. No. Duration Phase Applied Minimum Remarks
Applied
(M /G )
1 5000 1 minute U-GROUND OL 1.66 M GO

2 5000 1 minute V-GROUND OL 1.66 M GO

3 5000 1 minute W-GROUND OL 1.66 M GO

4 5000 1 minute U-V OL 1.66 M GO

5 5000 1 minute U-W OL 1.66 M GO

6 5000 1 minute V-W OL 1.66 M GO

Polarization Index (PI) (PI recommended when IR value is less)


1 minute IR: 10-minute IR: PI (IR10/IR1): (shall be>1)
Resistance Measurement for Winding and Bearing RTD’s
W2 V2 U2 W1 V1 U1 BRG1/NDE BRG2/DE
RTD-1 RTD-2 RTD-3 RTD-4 RTD-5 RTD-6 RTD-7 RTD-8

114.6 115.6 114.2 114.9 114.2 115.7 112.3 111.9

114.6 116.3 114.2 114.7 114.6 115.5 111.0 111.9


0.6 0.6 1.2 0.6 1.3 0.6 1.3 1.2

REMARKS

CERTIFIED, TESTED AND CHECKED:

CONTRACTOR:
Name Signature Date

CUMMINS:
Name Signature Date

CLIENT:
Name Signature Date
Activity Winding IR Test

Genset EDG-B

U-GND V-GND W-GND


331-A-105B-GEN1

U-V U-W V-W


Activity RTDs Resistance Measurement (U1, V1, W1)

Genset EDG-B

U1-R2 U1-R1:R2
U1-R1
331-A-105B-GEN1

V1-R2 V1-R1:R2
V1-R1

W1-R2 W1-R1:R2
W1-R1
Activity RTDs Resistance Measurement (U2, V2, W2)

Genset EDG-B

U2-R2 U2-R1:R2
U2-R1
331-A-105B-GEN1

V2-R2 V2-R1:R2
V2-R1

W2-R2 W2-R1:R2
W2-R1
Activity RTDs Resistance Measurement (BRG1/ NDE, BRG2/ DE)

Genset
331-A-105B-GEN1 EDG-B

NDE-R2 NDE-R1:R2
NDE-R1

DE-R1 DE-R2 DE-R1:R2

You might also like