The cable test report summarizes insulation resistance and high potential DC tests on a 2500 meter, 33kV cable for a 50MW solar PV project in Bhadla, India. Insulation resistance measurements were taken before and after a 5000V DC test and found to be within acceptable ranges. A 55kV, 1 minute DC high potential test was also completed with leakage currents remaining at or below 0.5mA, indicating the cable withstood the test voltage. The cable was determined to be fit for charging based on the successful test results.

Uploaded by

SARAVANAN A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
80% found this document useful (5 votes)
14K views1 page

33kV Cable Test Report for Solar Project

The cable test report summarizes insulation resistance and high potential DC tests on a 2500 meter, 33kV cable for a 50MW solar PV project in Bhadla, India. Insulation resistance measurements were taken before and after a 5000V DC test and found to be within acceptable ranges. A 55kV, 1 minute DC high potential test was also completed with leakage currents remaining at or below 0.5mA, indicating the cable withstood the test voltage. The cable was determined to be fit for charging based on the successful test results.

Uploaded by

SARAVANAN A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
  • Cable Test Report: This section provides a summary of the cable test report including client information and details about the testing setup.

Cable Test Report

PROJECT 50MW SOLAR PV PROJECT,Bhadla Page 1 of 1


CLIENT M/s Azure Power Date :12/03/2019
CUSTOMER M/s GE T&D INDIA LTD

1. GENERAL DETAILS

Make:- APAR Rating:- 33 KV


From :- MCR-1/0UT GOING-1 Length:- 2500 Meters
To:- 9A PSS

2. INSULATION RESISTANCE TEST


Applied voltage: - 5000V DC Duration: - 60s
PHASE REF. UNIT BEFORE HIPOT AFTER HIPOT
R1 – E GΩ 80.7 62.0
R2 – E GΩ 10.7 8.59
Y1 – E GΩ 57.0 63.8
Y2 – E GΩ 26.2 32.5
B1 – E GΩ 59.8 42.2
B2 – E GΩ 76.6 59.0

3. DC HIGH POTENTIAL TEST

Applied voltage: - 55 KV Duration:- 1 min


LEAKAGE CURRENT IN mA
PHASE REFERENCE RESULT
STARTING ENDING
R1 – E 0.4 0 WITHSTOOD
R2 – E 0.4 0 WITHSTOOD
Y1 – E 0.3 0 WITHSTOOD
Y2 – E 0.4 0 WITHSTOOD
B1 – E 0.5 0 WITHSTOOD
B2 – E 0.5 0 WITHSTOOD

CABLE IS FIT FOR CHARGING YES NO

Tested By: Witnessed By: Witnessed By: Verified By:


Mr Mr Mr.
Signature: Signature: Signature: Signature:
Snipe Engineers Pvt. Ltd. GE T&D INDIA LTD Azure Power

Cable Test Report
PROJECT
50MW SOLAR PV PROJECT,Bhadla
Page 1 of 1
CLIENT
M/s Azure Power
Date :12/03/2019
CUSTOMER