SITE TEST REPORT : HV CABLE TEST REPORT

Client ARLA FOODS


Consultant BILFINGER TEBODIN
Contractor POULLAIDES CONSTRUCTION COMPANY
Project BLUE at BIIP, HIDD (ARLA FOOD FACTORY)

1. GENERAL DATA AND INFORMATION

Make DUCAB A BICC ELECTRIC CABLE

Circuit RMU1 to RMU2

Cable Size 3Cx300

Cable Type CU/XLPE/SWA

Conductor Type Copper


Rated Voltage 11KV

2. MECHANICAL CHECK AND VISUAL INSPECTION:

Item Description Checked


2.1 Inspect For Physical Damage or Defects OK
2.2 Verify All Cable Connections As Per Drawing OK
2.3 Check all cables and cores are labelled correctly OK
2.4 Check tightness of terminals and confirm the cables are secured OK
2.5 Check cable size against rating required OK
2.6 Check cable entry path trench or ducts are to be properly sealed OK
Check cable bends to ensure that the bending radius is equal to or
2.7 OK
greater than that specified
2.8 Check that phases are identified OK

Prepared by Witnessed by Approved by


Representative Castillo PCC
Name
Date
Signature
Test Equipment Used: High-Voltage Kit, Megger and Multimeter
SITE TEST REPORT : HV CABLE TEST REPORT

Client ARLA FOODS


Consultant BILFINGER TEBODIN
Contractor POULLAIDES CONSTRUCTION COMPANY
Project BLUE at BIIP, HIDD (ARLA FOOD FACTORY)

3. Continuity Check Test

Phase Continuity resistance checked


R Y+B+Earth OK
Y R+B+Earth OK
B R+Y+Earth OK

4. INSULATION RESISTANCE TEST BEFORE HIGH-VOLTAGE

Applied Measured Resistance in


Phase Duration Acceptable Value
Voltage GΩ

R to Y+B+E 290 GΩ
Y to R+B+E 5kV DC 1 Minute 300 GΩ > 1 GΩ
B to R+Y+E 280 GΩ

5. DC HIGH-VOLTAGE TEST

Measured Leakage Cable Withstand Applied


Phase Applied Voltage Duration
Current in mA Voltage
R to Y+B+E >1mA Pass
Y to R+B+E 17.5kV DC 5 Minutes >1mA Pass
B to R+Y+E >1mA Pass

Prepared by Witnessed by Approved by


Representative Castillo PCC
Name
Date
Signature
Test Equipment Used: High-Voltage Kit, Megger and Multimeter
SITE TEST REPORT : HV CABLE TEST REPORT

Client ARLA FOODS


Consultant BILFINGER TEBODIN
Contractor POULLAIDES CONSTRUCTION COMPANY
Project BLUE at BIIP, HIDD (ARLA FOOD FACTORY)

6. INSULATION RESISTANCE TEST AFTER HIGH-VOLTAGE

Measured Resistance in
Phase Applied Voltage Duration Acceptable Value
GΩ

R to Y+B+E 250 GΩ
Y to R+B+E 5kV DC 1 Minute 290 GΩ >1 GΩ
B to R+Y+E 250 GΩ

7. REMARKS: The tested cable found satisfactory results

Prepared by Witnessed by Approved by


Representative Castillo PCC
Name
Date
Signature
Test Equipment Used: High-Voltage Kit, Megger and Multimeter