SITE ACCEPTANCE TEST REPORT FOR MV PANEL

PROJECT WO # DC EQUIPMENT 22 kV MV PANEL


CLIENT ADDC DATE
CONTRACTOR GULF LOGIC LLC SUBSTATION
TESTING COMPANY ALPHA POWER LLC PAGE Page 1 of 1

HIGH VOLTAGE TEST


1. INSULATION RESISTANCE TEST APPLIED VOLTAGE 5000 V DC, 1 MIN.

MEASURED VALUE in TW MEASURED VALUE in TW


TEST POINT REMARKS
(BEFORE HV TEST) (AFTER HV TEST)
R to Y+B+E OK

Y to B+R+E OK

B to R+Y+E OK

2. HIGH VOLTAGE TEST

LEAKAGE
TEST POINT APP VOLTAGE DURATION REMARKS
CURRENT (mA)
R& Y+B+E 40.0 kV 1 min 24.0 WITHSTOOD
Y& R+B+E 40.0 kV 1 min 24.0 WITHSTOOD
B& Y+R+E 40.0 kV 1 min 24.0 WITHSTOOD

3. PHASE SEQUENCE CHECK: OK

4. REMARKS:--

5. TEST EQUIPMENT DETAILS:

Description of Test
Serial Number Calibration Due Date
Equipment
AC HV TEST KIT 1110 11.10.2018
INSULATION TESTER 101574096 05.03.2019

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC GULF LOGIC LLC ADDC