HIGH VOLTAGE VACUUM CONTACTOR TEST CERTIFICATE

1 High Voltage Contactor


Type CS-VP 11
Rating 12kV, 400A
Control Voltage 220VAC
No. of Aux. Contacts 3 NO + 2 NC

2 Dispatch Details
Customer M/s. Innovative Engg.
Month of Manufacturing Dec. 2022
Month of Dispatch Dec. 2022
Quantity in Nos 4 Nos.

3 This is to certify that the MVCs listed under point no 4 have passed below tests
The Routine Tests specified as per following test standards.(IEC-62271-106/IS 9046)
Sr.No Test Acceptance Criterion (A.C) With in A.C (Yes/No)
3.1 Physical Verification As per GA drawing Yes
3.2 HV. Withstand Test 28 kV for 1 Minute Withstood
Across contacts
3.3 ON – OFF Operations 85% - 50 Operations Yes
100%- 50 Operations Yes
110%- 50 Operations Yes
3.4 Contact Resistance < 450 µΩ Yes
3.5 Holding Current <1Amps at 220VAC Yes

4 List of MVCs tested


Sr.No Dispatch No Sr.No Dispatch NO Sr.No Dispatch NO
1 V-1345 2 V-1346 3 V-1347
4 V-1348

We hereby confirm the authenticity & correctness of the above data.

For CG Power & Industrial Solutions Ltd.

Quality Assurance.

Manufacturing Unit:
CG Power and Industrial Solutions Limited,
Vacuum Interrupters & Inst. Trf. Division
D2, MIDC, Waluj, Aurangabad 431 136 T: +91 240 255 8031
W: www.cgglobal.com